After programming the stroke end positions, it is recommended to check the opening and
closing of the window a few times. In the case of error, the programming can be repeated
to achieve the desired stroke. If you need to perform the
instructions given above.
12.3. Overlap acquisition
The operation that must be carried out to acquire the overlap (after the
has already been executed) is described below:
- The steps for installing the actuator/s on the window and the electrical connections
have already been explained (see § 10 and
- Use the controls to open the window a few centimetres
- Use the controls to close the window up to the stroke end
- When the window is completely closed, if acquisition of the overlap is successful, the
actuator will display an orange flashing light for 3 seconds
IMPORTANT:
If, for any reason, the actuator fails to complete the closure of
the window correctly, stopping before finishing the stroke, the
overlap acquisition operation will have to be repeated in that order, until the
procedure is completed correctly
12.4. LED Light signals
If there are any problems during installation or operation of the machines, consult the
possible causes listed below:
The LED can be seen on the cap that conceals the dip
gear reducer, and has three colours
R
ED
, indicates an error or malfunction
G
REEN
, operation is OK
O
RANGE
, wait: functions in progress
17
After programming the stroke end positions, it is recommended to check the opening and
closing of the window a few times. In the case of error, the programming can be repeated
to achieve the desired stroke. If you need to perform the
R
ESET
Overlap acquisition
The operation that must be carried out to acquire the overlap (after the
has already been executed) is described below:
The steps for installing the actuator/s on the window and the electrical connections
have already been explained (see § 10 and 11).
Use the controls to open the window a few centimetres.
Use the controls to close the window up to the stroke end.
indow is completely closed, if acquisition of the overlap is successful, the
actuator will display an orange flashing light for 3 seconds.
If, for any reason, the actuator fails to complete the closure of
the window correctly, stopping before finishing the stroke, the
overlap acquisition operation will have to be repeated in that order, until the
procedure is completed correctly
If there are any problems during installation or operation of the machines, consult the
The LED can be seen on the cap that conceals the dip-switch, positioned to the left of the
olours:
, indicates an error or malfunction;
, operation is OK;
, wait: functions in progress.
After programming the stroke end positions, it is recommended to check the opening and
closing of the window a few times. In the case of error, the programming can be repeated
ESET
procedure, see the
The operation that must be carried out to acquire the overlap (after the
RESET
procedure
The steps for installing the actuator/s on the window and the electrical connections
indow is completely closed, if acquisition of the overlap is successful, the
If, for any reason, the actuator fails to complete the closure of
the window correctly, stopping before finishing the stroke, the
RESET
and
overlap acquisition operation will have to be repeated in that order, until the
If there are any problems during installation or operation of the machines, consult the
switch, positioned to the left of the
18
WITH RED LED
Number
of
Flashes
Type of Error
Possible Solution
1
Current error:
The actuator has detected an
overcurrent in the motor.
Check that there are no obstacles preventing
the actuator from completing its stroke. Check
that the actuator is installed correctly.
2
Communication error:
Communication between the
devices is interrupted, or the
devices being used have
undergone the
R
ESET
procedure
separately
Check the condition of the connection cables,
and repeat the
R
ESET
procedure if necessary.
3
Electro-lock error
Check the electro-lock. See the relevant
manual
4
Discordant internal setting:
The internal setting of the actuators
is discordant.
Repeat the
R
ESET
procedure
5
RESET Procedure error:
The
R
ESET
procedure was not
completed successfully or was
interrupted.
Repeat the
R
ESET
procedure
6
Wiring error:
The power supply cables of the
devices configured in Syncro³ are
inverted.
Check and correct the wiring.
7
Encoder error:
The internal encoder had a
counting error
Repeat the
R
ESET
procedure
8
Electric power supply error:
The power supply voltage is outside
the permitted range or is unstable.
Check the electrical contacts at the ends of the
actuator cable and ensure that the power
supply is correct.
9
Alignment error:
The rack position displacement of
the actuators connected in Syncro
is beyond the permitted maximum.
Repeat the
R
ESET
procedure
10
Memory error:
The internal memory write process
failed.
Repeat the
R
ESET
procedure
11
Connection error:
A RESET procedure is being
started with actuators different than
Syncro³
Check the type of actuators chosen for the
system.
Repeat the
R
ESET
procedure
WITH GREEN LED
LED Status
Meaning
STEADY-ON
Device powered correctly.
The device has correctly performed a return stroke and is completing the
operation by memorising the position, or is currently in movement.
FLASHING
Device correctly powered. The device has successfully performed an
outward stroke. The number of flashes indicates the number previously
assigned to the device during the
R
ESET
procedure