Mount and screw the M8x14 mm flat headed screw
(
provided with connection bar
to prevent the bar from slipping out.
DISTANCE BETWEEN THE CENTRES OF THE CONNECTION BARS
Code
Description
4010009
Connection bar 1000 mm length
4010010
Connection bar 1500 mm length
4010011
Connection bar 2000 mm length
4010011
Connection bar 2500 mm length
For special measurements, consult the manufacturer
The drawing below shows an installation example with various push point solutions, with
actuators and rods on a large window or on “strip” windows. It should be noted that up to a
maximum of 8 Syncro actuators (4 for 230V) can be fitted, with various rod solutions for
additional push points.
Two or more Syncro³ version
motors in tandem
11. ELECTRICAL CONNECTIONS
Appliances are equipped with cable manufactured in accordance with safety standards and
protection against radio disturbances.
E
ACH ACTUATOR MODEL MUST USE ITS OWN SPEC
Before performing the electrical connection consult the table below and check
correspondence between the feeder cable and the tension data on the actuator label.
13
Mount and screw the M8x14 mm flat headed screw
provided with connection bar
), into the two ends of the bar
prevent the bar from slipping out.
DISTANCE BETWEEN THE CENTRES OF THE CONNECTION BARS
Description
Length of bar
(mm)
Connection bar 1000 mm length
1.035
Connection bar 1500 mm length
1.535
Connection bar 2000 mm length
2.035
Connection bar 2500 mm length
2.535
For special measurements, consult the manufacturer
The drawing below shows an installation example with various push point solutions, with
actuators and rods on a large window or on “strip” windows. It should be noted that up to a
maximum of 8 Syncro actuators (4 for 230V) can be fitted, with various rod solutions for
Two or more Syncro³ version
Two or more Syncro³
version 1 rod
with a connection bar in
tandem
One motor + 1 rod +
connection bar in tandem
ELECTRICAL CONNECTIONS
Appliances are equipped with cable manufactured in accordance with safety standards and
disturbances.
UST USE ITS OWN SPECIFIC CABLE
.
Before performing the electrical connection consult the table below and check
correspondence between the feeder cable and the tension data on the actuator label.
DISTANCE BETWEEN THE CENTRES OF THE CONNECTION BARS
“D”
distance between centres
(mm)
1.000
1.500
2.000
2.500
For special measurements, consult the manufacturer
The drawing below shows an installation example with various push point solutions, with
actuators and rods on a large window or on “strip” windows. It should be noted that up to a
maximum of 8 Syncro actuators (4 for 230V) can be fitted, with various rod solutions for
One motor + 1 rod +
connection bar in tandem
Appliances are equipped with cable manufactured in accordance with safety standards and
Before performing the electrical connection consult the table below and check
correspondence between the feeder cable and the tension data on the actuator label.
Tension
Cable length
110-230V~ 50/60Hz
2 m
110-230V~ 50/60Hz
Syncro
3
2,5 m
24V
Syncro³
2 m
If feeder cables require extending
cable sections should be selected accordingly. Conductor sections are indicated in the
table on page 9
(Selection of cable section)
IMPORTANT FOR PRODUCT SAFETY:
in 24V
actuators, wire Green if not used must be insulated.
11.1. Connections of SKYRO 650
For cabling, follow the diagrams below.
3
1
2
3
F N
10
0-
23
0V
~
50
/6
0H
z
1 2
110/230V ~
11.2. Connections of SKYRO
Cable supplied together with the SYNCRO
and 2 m long for 24V
Syncro³ version; it’s calculated in accordance with safety rules.
Electrical connection of the communication wires should be performed using a simple
appropriately sized bell clamp
electrical contact (copper to copper) are vital to avoid communication disturbs.
Maximum length of feeding cables can be 10 m.
14
Cable length
Number of
wires
Wire colours
2 m
3
L
IGHT
B
LUE
B
LACK
B
ROWN
2,5 m
4
L
IGHT
B
LUE
B
LACK
B
ROWN
2 m
3
R
ED
B
LACK
If feeder cables require extending to the control button for low voltage actuators (24V
cable sections should be selected accordingly. Conductor sections are indicated in the
(Selection of cable section)
.
IMPORTANT FOR PRODUCT SAFETY:
actuators, wire Green if not used must be insulated.
SKYRO 650
For cabling, follow the diagrams below.
110/230V ~
- +
24
V
1
2
SKYRO 650 Syncro³
the SYNCRO
3
actuator is 2,5 m long for 230V~ Syncro³ version
Syncro³ version; it’s calculated in accordance with safety rules.
Electrical connection of the communication wires should be performed using a simple
appropriately sized bell clamp
(supplied with the appliance)
. Secure connections with good
electrical contact (copper to copper) are vital to avoid communication disturbs.
Maximum length of feeding cables can be 10 m.
Colour of wires used
for notification
-
G
REEN
G
REEN
to the control button for low voltage actuators (24V
),
cable sections should be selected accordingly. Conductor sections are indicated in the
actuators, wire Green if not used must be insulated.
3
1
2
3
24V
m long for 230V~ Syncro³ version
Syncro³ version; it’s calculated in accordance with safety rules.
Electrical connection of the communication wires should be performed using a simple
. Secure connections with good
electrical contact (copper to copper) are vital to avoid communication disturbs.