9. ELECTRICAL POWER SUPPLY
The actuator is commercially available in
specifications:
1.
SKYRO 650 230V
: runs on grid tension of
cable
(
L
IGHT
B
LUE
, common neutral;
2.
SKYRO 650 230V S
YNCRO
four-wire power cord (
B
LUE
and a
G
REEN
fourth wire for electronic synchronisation with other similar (NEKOS
patent) actuators.
3.
SKYRO 650 24V S
YNCRO
B
LACK
connected to + (positive) open,
“
3
” third wire is used both for synchronisation with other similar
connection to the K-Lock electromechanical lock.
Low tension actuators 24V
emergency battery or a security feeder with an output tension of 24V
max. 28.8V)
.
IMPORTANT FOR PRODUCT SAFETY
supplies, the
G
REEN
WI
9.1. Selection of power cable section
The following table indicates maximum cable lengths for connection to a single motors.
CABLE SECTION
0,50 mm²
0,75 mm²
1,00 mm²
1,50 mm²
2,50 mm²
4,00 mm²
6,00 mm²
10. INSTRUCTIONS FOR ASSEMBLY
These indications are for specialised technical personnel and basic work and safety
techniques are not indicated.
All preparatory, assembly and electrical connection operations must be performed by
specialised technical personnel
Check that the following funda
Before installing the actuator, check that the moving parts of the window on which
it is to be installed are in perfect working cond
properly and are well balanced (where applicable).
Actuator specifications must be sufficient for movement of the window without
encountering any obstacle. The limits indicated in the technical data table must
not be superseded
(page 8)
Calculations should be checked using the formula indicated on page 5.
9
SUPPLY
The actuator is commercially available in three versions identified according to electrical
runs on grid tension of 110-230V~ 50/60Hz,
, common neutral;
B
LACK
, phase open;
B
ROWN
YNCRO
3
: is powered by 110-230V~ 50/60Hz mains voltage, with a
LUE
, common neutral;
B
LACK
, open live;
fourth wire for electronic synchronisation with other similar (NEKOS
YNCRO
3
: is powered by 24V voltage with a three
connected to + (positive) open,
R
ED
connected to + (positive) close. The
” third wire is used both for synchronisation with other similar
Lock electromechanical lock.
can be powered using a specific RWA station with
emergency battery or a security feeder with an output tension of 24V
FOR PRODUCT SAFETY
: in Syncro³ motors with 24V
WI
re
must be insulated
if not used.
Selection of power cable section
The following table indicates maximum cable lengths for connection to a single motors.
Actuator fed at
24V
110V~
~20 m
~300 m
~30 m
~450 m
~40 m
~600 m
~60 m
~900 m
~100 m
~1500 m
~160 m
~2500 m
~240m
~3700 m
INSTRUCTIONS FOR ASSEMBLY
These indications are for specialised technical personnel and basic work and safety
techniques are not indicated.
All preparatory, assembly and electrical connection operations must be performed by
specialised technical personnel to guarantee optimal function and service of the actuator.
Check that the following fundamental conditions have been met:
Before installing the actuator, check that the moving parts of the window on which
it is to be installed are in perfect working condition and that they open and close
properly and are well balanced (where applicable).
Actuator specifications must be sufficient for movement of the window without
obstacle. The limits indicated in the technical data table must
(page 8)
and the most appropriate stroke should be selected.
Calculations should be checked using the formula indicated on page 5.
versions identified according to electrical
50/60Hz, with a three wire
ROWN
, phase closed)
.
230V~ 50/60Hz mains voltage, with a
, open live;
B
ROWN
, close live),
fourth wire for electronic synchronisation with other similar (NEKOS
is powered by 24V voltage with a three-wire power cable:
connected to + (positive) close. The
G
REEN
” third wire is used both for synchronisation with other similar actuators and for
can be powered using a specific RWA station with
emergency battery or a security feeder with an output tension of 24V 24V
(min. 20.4V,
: in Syncro³ motors with 24V
power
The following table indicates maximum cable lengths for connection to a single motors.
230V~
~1400 m
~2100 m
~2800 m
~4000 m
~6800 m
~11000 m
~15000 m
These indications are for specialised technical personnel and basic work and safety
All preparatory, assembly and electrical connection operations must be performed by
to guarantee optimal function and service of the actuator.
Before installing the actuator, check that the moving parts of the window on which
ition and that they open and close
Actuator specifications must be sufficient for movement of the window without
obstacle. The limits indicated in the technical data table must
and the most appropriate stroke should be selected.
Calculations should be checked using the formula indicated on page 5.
Attention
. Check that the electrical
the technical data plate on the machine and that the indicated temperature range
is compatible with the installation site
Ensure that the actuator has not been damaged during transport.
Check
, once the actuator is installed, that the window is fully closed
For bottom hung window frames injury could be caused by accidental falls of the
window. An appropriately sized flexible link arm or fall prevention safety system
designed to resist a force equal to at
window
MUST
be installed.
10.1. Preparation of actuator for assembly
Before starting assembly of the actuator, prepare the following material for completion,
equipments and tools.
For fixing onto metal window frames
headed metric screws
(6 pieces)
For fixing onto wooden window frames
For fixing onto PVC window frames
Equipment and tools: measuring tape, pencil, drill/screwdriver, set of drill heads for
metal, insert for screwing in, electricians pliers, screwdrivers.
10.2. Calculation of the number of push / retention points
If the window has a width exceeding 120 cm, it is
points by assembling several actuators. The simple formula below allows you to calculate
the position of these points.
Formula:
The two side dimensions -
LA : (PA x 2) = QL
The central dimensions
-
QL x 2
Fig. 1
Fig. 4
10
Check that the electrical supply used corresponds to the indications on
the technical data plate on the machine and that the indicated temperature range
is compatible with the installation site.
Ensure that the actuator has not been damaged during transport.
actuator is installed, that the window is fully closed
For bottom hung window frames injury could be caused by accidental falls of the
An appropriately sized flexible link arm or fall prevention safety system
designed to resist a force equal to at least three times the total weight of the
be installed.
Preparation of actuator for assembly
Before starting assembly of the actuator, prepare the following material for completion,
For fixing onto metal window frames: M5 threaded inserts
pieces)
.
For fixing onto wooden window frames: self threading screws for wood Ø4.5
For fixing onto PVC window frames: self threading screws for metal Ø4.8
: measuring tape, pencil, drill/screwdriver, set of drill heads for
metal, insert for screwing in, electricians pliers, screwdrivers.
Calculation of the number of push / retention points
If the window has a width exceeding 120 cm, it is advisable to use several push / retention
points by assembling several actuators. The simple formula below allows you to calculate
LA : (PA x 2) = QL
QL x 2
Legend:
LA
= Window Sash Width (hinges side)
PA
= Actuator Attachment Points
QL
= Side Dimensions
Fig. 2
Fig. 3
Fig. 5
Fig. 5 bis
supply used corresponds to the indications on
the technical data plate on the machine and that the indicated temperature range
Ensure that the actuator has not been damaged during transport.
actuator is installed, that the window is fully closed.
For bottom hung window frames injury could be caused by accidental falls of the
An appropriately sized flexible link arm or fall prevention safety system
least three times the total weight of the
Before starting assembly of the actuator, prepare the following material for completion,
: M5 threaded inserts
(6 pieces)
, M5x12 flat
: self threading screws for wood Ø4.5
(6 pieces)
.
: self threading screws for metal Ø4.8
(6 pieces)
.
: measuring tape, pencil, drill/screwdriver, set of drill heads for
Calculation of the number of push / retention points
advisable to use several push / retention
points by assembling several actuators. The simple formula below allows you to calculate
Window Sash Width (hinges side)
Actuator Attachment Points
Side Dimensions