background image

9.  ELECTRICAL POWER SUPPLY

The  actuator  is  commercially  available  in 
specifications: 

1. 

SKYRO  650  230V

:  runs  on  grid  tension  of 

cable 

(

L

IGHT 

B

LUE

, common neutral; 

2. 

SKYRO 650 230V S

YNCRO

four-wire  power  cord  (

B

LUE

and  a 

G

REEN

  fourth  wire  for  electronic  synchronisation  with  other  similar  (NEKOS 

patent) actuators. 

3. 

SKYRO 650 24V S

YNCRO

B

LACK

 connected to + (positive) open, 

3

”  third  wire  is  used  both  for  synchronisation  with  other  similar 

connection to the K-Lock electromechanical lock.

Low  tension  actuators  24V
emergency battery or a security feeder with an output tension of 24V

max. 28.8V)

.

 

 

IMPORTANT  FOR  PRODUCT  SAFETY

supplies, the 

G

REEN

 WI

9.1.  Selection of power cable section

The following table indicates maximum cable lengths for connection to a single motors.

CABLE SECTION

 

0,50 mm² 
0,75 mm² 
1,00 mm² 
1,50 mm² 
2,50 mm² 
4,00 mm² 
6,00 mm² 

10.  INSTRUCTIONS FOR ASSEMBLY

These indications are for specialised technical personnel and basic work and safety 

techniques are not indicated.

All  preparatory,  assembly  and  electrical  connection  operations  must  be  performed  by 
specialised technical personnel 
Check that the following funda

 

Before installing the actuator, check that the moving parts of the window on which 
it is to be installed are in perfect working cond
properly and are well balanced (where applicable). 

 

Actuator  specifications  must  be  sufficient  for  movement  of  the  window  without 
encountering  any  obstacle.  The  limits  indicated  in  the  technical  data  table  must 
not be superseded 

(page 8)

Calculations should be checked using the formula indicated on page 5.

SUPPLY 

The  actuator  is  commercially  available  in  three  versions  identified  according  to  electrical 

runs  on  grid  tension  of  110-230V~  50/60Hz, 

, common neutral; 

B

LACK

, phase open; 

B

ROWN

YNCRO

3

: is powered by 110-230V~ 50/60Hz mains voltage, with a 

LUE

,  common  neutral; 

B

LACK

,  open  live; 

fourth  wire  for  electronic  synchronisation  with  other  similar  (NEKOS 

YNCRO

3

: is powered by 24V  voltage with  a three

connected to + (positive) open, 

R

ED

 connected to + (positive) close. The 

”  third  wire  is  used  both  for  synchronisation  with  other  similar 

Lock electromechanical lock. 

  can  be  powered  using  a  specific  RWA  station  with 

emergency battery or a security feeder with an output tension of 24V

FOR  PRODUCT  SAFETY

:  in  Syncro³  motors  with  24V

WI

re 

must be insulated

 if not used. 

Selection of power cable section 

The following table indicates maximum cable lengths for connection to a single motors.

Actuator fed at

 

24V 

 

110V~

 

~20 m 

~300 m 

~30 m 

~450 m 

~40 m 

~600 m 

~60 m 

~900 m 

~100 m 

~1500 m 

~160 m 

~2500 m 

~240m 

~3700 m 

INSTRUCTIONS FOR ASSEMBLY 

These indications are for specialised technical personnel and basic work and safety 

techniques are not indicated. 

All  preparatory,  assembly  and  electrical  connection  operations  must  be  performed  by 
specialised technical personnel to guarantee optimal function and service of the actuator. 
Check that the following fundamental conditions have been met: 

Before installing the actuator, check that the moving parts of the window on which 
it is to be installed are in perfect working condition and that they open and close 
properly and are well balanced (where applicable).  
Actuator  specifications  must  be  sufficient  for  movement  of  the  window  without 

obstacle.  The  limits  indicated  in  the  technical  data  table  must 

(page 8)

 and the most appropriate stroke should be selected. 

Calculations should be checked using the formula indicated on page 5.

versions  identified  according  to  electrical 

50/60Hz,  with  a  three  wire 

ROWN

, phase closed)

230V~ 50/60Hz mains voltage, with a 

,  open  live; 

B

ROWN

,  close  live), 

fourth  wire  for  electronic  synchronisation  with  other  similar  (NEKOS 

is powered by 24V  voltage with a three-wire power cable: 

connected to + (positive) close. The 

G

REEN

 

”  third  wire  is  used  both  for  synchronisation  with  other  similar  actuators  and  for 

can  be  powered  using  a  specific  RWA  station  with 

emergency battery or a security feeder with an output tension of 24V 24V

 

(min. 20.4V, 

:  in  Syncro³  motors  with  24V

  power 

The following table indicates maximum cable lengths for connection to a single motors. 

230V~

 

~1400 m 
~2100 m 
~2800 m 
~4000 m 
~6800 m 

~11000 m 
~15000 m 

These indications are for specialised technical personnel and basic work and safety 

All  preparatory,  assembly  and  electrical  connection  operations  must  be  performed  by 

to guarantee optimal function and service of the actuator. 

Before installing the actuator, check that the moving parts of the window on which 

ition and that they open and close 

Actuator  specifications  must  be  sufficient  for  movement  of  the  window  without 

obstacle.  The  limits  indicated  in  the  technical  data  table  must 

and the most appropriate stroke should be selected. 

Calculations should be checked using the formula indicated on page 5. 

 

Attention

. Check that the electrical 

the technical data plate on the machine and that the indicated temperature range 
is compatible with the installation site
Ensure that the actuator has not been damaged during transport.

 

Check

, once the actuator is installed, that the window is fully closed

For bottom hung window frames injury could be caused by accidental falls of the 
window.  An  appropriately  sized  flexible  link  arm  or  fall  prevention  safety  system 
designed  to  resist  a  force  equal  to  at

window 

MUST

 be installed.

10.1.  Preparation of actuator for assembly

Before  starting  assembly  of  the  actuator,  prepare  the  following  material  for  completion, 
equipments and tools.  

 

For  fixing  onto  metal  window  frames
headed metric screws 

(6 pieces)

 

For fixing onto wooden window frames

 

For fixing onto PVC window frames

 

Equipment  and  tools:  measuring  tape,  pencil,  drill/screwdriver,  set  of  drill  heads  for 
metal, insert for screwing in, electricians pliers, screwdrivers.

10.2.  Calculation of the number of push / retention points

If the window has a width exceeding 120 cm, it is 
points by assembling several actuators. The simple formula below allows you to calculate 
the position of these points. 

Formula: 

The two side dimensions - 

LA : (PA x 2) = QL

The central dimensions  

QL x 2

 

Fig. 1 

Fig. 4 

10 

Check that the electrical supply used corresponds to the indications on 

the technical data plate on the machine and that the indicated temperature range 
is compatible with the installation site. 
Ensure that the actuator has not been damaged during transport.

actuator is installed, that the window is fully closed

For bottom hung window frames injury could be caused by accidental falls of the 

An  appropriately  sized  flexible  link  arm  or  fall  prevention  safety  system 

designed  to  resist  a  force  equal  to  at  least  three  times  the  total  weight  of  the 

be installed. 

Preparation of actuator for assembly 

Before  starting  assembly  of  the  actuator,  prepare  the  following  material  for  completion, 

For  fixing  onto  metal  window  frames:  M5  threaded  inserts 

pieces)

For fixing onto wooden window frames: self threading screws for wood Ø4.5 
For fixing onto PVC window frames: self threading screws for metal Ø4.8 

:  measuring  tape,  pencil,  drill/screwdriver,  set  of  drill  heads  for 

metal, insert for screwing in, electricians pliers, screwdrivers. 

Calculation of the number of push / retention points

If the window has a width exceeding 120 cm, it is advisable to use several push / retention 
points by assembling several actuators. The simple formula below allows you to calculate 

LA : (PA x 2) = QL 

QL x 2

 

Legend: 

LA

 = Window Sash Width (hinges side)

PA

 = Actuator Attachment Points

QL

 = Side Dimensions

Fig. 2 

Fig. 3 

Fig. 5 

Fig. 5 bis 

supply used corresponds to the indications on 

the technical data plate on the machine and that the indicated temperature range 

Ensure that the actuator has not been damaged during transport. 

actuator is installed, that the window is fully closed. 

For bottom hung window frames injury could be caused by accidental falls of the 

An  appropriately  sized  flexible  link  arm  or  fall  prevention  safety  system 

least  three  times  the  total  weight  of  the 

Before  starting  assembly  of  the  actuator,  prepare  the  following  material  for  completion, 

:  M5  threaded  inserts 

(6  pieces)

,  M5x12  flat 

: self threading screws for wood Ø4.5 

(6 pieces)

: self threading screws for metal Ø4.8 

(6 pieces)

:  measuring  tape,  pencil,  drill/screwdriver,  set  of  drill  heads  for 

Calculation of the number of push / retention points 

advisable to use several push / retention 

points by assembling several actuators. The simple formula below allows you to calculate 

Window Sash Width (hinges side) 

Actuator Attachment Points 
Side Dimensions 

Fig. 3 bis 

Fig. 6 

Summary of Contents for SKYRO 650

Page 1: ...performed periodically by qualified personnel from a service centre authorised by the manufacturer Do not use if repair or adjustment is required CAUTION if the power cable is damaged it must be repla...

Page 2: ...nsory or mental capabilities or lacking experience and not allow children to play with the fixed controls and keep any remote out of their reach The actuator is destined exclusively for installation i...

Page 3: ...an approved type of bipolar dead switch should be used An omnipolar general power switch with minimum distance of 3 mm between contacts should be installed upstream of the control line Application is...

Page 4: ...sed when the window is particularly heavy or wide and a single actuator doesn t allow complete closure of the window especially in the corners therefore making it necessary to have two or more When a...

Page 5: ...m 11000 m 15000 m These indications are for specialised technical personnel and basic work and safety All preparatory assembly and electrical connection operations must be performed by to guarantee op...

Page 6: ...fixing screws Fig 2 C Drill holes into the frame and screw in the motor support bracket making sure that all screws are fitted tightly Fig 3 and Fig 3bis 12 D Line up the front bracket along the centr...

Page 7: ...rip windows It should be noted that up to a maximum of 8 Syncro actuators 4 for 230V can be fitted with various rod solutions for One motor 1 rod connection bar in tandem Appliances are equipped with...

Page 8: ...e gives a flashing orange signal to indicate completion of the RESET procedure Each device will give a different number of flashes to indicate that the access code is received actuator 1 flash pause a...

Page 9: ...ess After programming the stroke end positions it is recommended to check the opening and closing of the window a few times In the case of error the programming can be repeated ESET procedure see the...