background image

condition  could  compromise  safety  and  invalidate  the  benefits  contained  in  the 
warranty for the appliance. 
In  the  event  of  any  problems  or  queries,  consult  your  agent  or  contact  the 
manufacturer directly. 

2. 

Formulas and recommendations for installation  

2.1.  Calculation of opening / closure force 

Using  the  formulas  on  this  page,  approximate  calculations  can  be  made  for  the  force 
required  to  open  or  close  the  window  considering  all  the  factors  that  determine  the 
calculation.  

Symbols used for the calculation  

F (Kg) = Force for opening or closing 

P (Kg)  = Weight of the window (mobile sash only) 

C (cm) = Opening stroke (actuator stroke) 

H (cm) = Height of the mobile sash 

 
 
 
 
 
 
 
 
 
 
 

For horizontal light domes or skylights 

 
 

F = 0,54 x P 

(Eventual  weight  of  snow  or  wind  on  the 
cupola should be calculated separately)

For vertical windows 

 

TOP HUNG WINDOWS

,

 OUTWARD OPENING

 (A) 

 

BOTTOM HUNG WINDOWS

 (B) 

F = 0,54 x P x C : H 

(Eventual  load  of  favourable  or  unfavourable 
wind  on  the  sash  should  be  calculated 
separately.)

 

2.2.  Maximum opening in accordance with sash height 

The actuator stroke should be selected in accordance with the height of the sash and 
its application. Make sure that the actuator does not touch the profile of the sash when 
moving along its track, and ensure there are no obstacles blocking the opening and that 
the rack moves smoothly along the window frame.  

A

TTENTION

.  For safety  reasons,  always  check  application  before  fixing  the  actuator to 

the frame or sash. In the event of difficulty, request assistance from the manufacturer to 
check application. 

3. 

Technical information about function 

The  rack  actuator  performs  opening  and  closing  movements  for  the  window  using  a 
round  section  steel  rack.  Movement  is  powered  by  electricity  that  feeds  a  reduction 
motor controlled by an electronic board. 
The opening stroke for the window CANNOT be programmed as it is regulated by the 
length of the rod on the reduction motor. The electronic control device allows the rack to 
protrude until it encounters an obstacle that blocks its stroke. This could be provided by 
the internal lock on the rack or complete closing/opening of the window. 
In  both  outwards  and  return  directions  the  stroke-end  uses  a  self-defining  electronic 
process with power absorption, and for this reason, no adjustment is required. 

4. 

Technical data 

Model 

SKY 450 

Thrust and traction force (F

N

450 N 

Course lengths (S

V

180, 230, 350, 550, 750, 1000 mm (*) 

Input voltage (U

N

110-230V~ 50/60 Hz 

Current absorption at nominal load (I

N

0,28 A - 0,19 A 

Power absorption at nominal load (P

N

21,6 – 24 W 

Travel speed without load 

6,7 mm/s 

Length of run without load  

In accordance with length of truck run 

Electrical insulation 

Class II 

Type of service (D

R

2 cycles 

Max. and min. temperatures for function 

-5 +65 ºC 

Degree of protection for electrical devices 

IP44 

Adjustment of socket at casing 

Position self regulating 

Connection in parallel of two or more motors 

Yes 

Connection in tandem or in series 

Yes 

Holding nominal force 

(it can vary according 

to the chosen brackets)

 

2200 N 

Limit switch stop at opening and closure 

At absorption of power 

Protection against overload at opening and 
closure 

At absorption of power 

Feeding cable length 

1 m 

Dimensions  

103x47x(Course 135) mm 

Weight 

Varies according to construction 

Information presented in these illustrations is not binding and is also subject to variation without prior notice. 

(*) Technical personnel can shorten track runs by adjusting the internal limit switches. 

5.  Id plate and marking data 

The  SKY450  actuators  have  CE  marking  and  comply  with  the  Standards  listed  in  the 
Declaration  of Conformity. They also come with  a Declaration of Incorporation, due to 
their  classification  by  the  Machinery  Directive  as  “partly  completed  machines”.  Both 
declarations are included in the final pages of this manual. 

Summary of Contents for SKY 450

Page 1: ...if repair or adjustment is required CAUTION if the power cable is damaged it must be replaced by qualified personnel from a service centre authorised by the manufacturer CAUTION Disconnect the power s...

Page 2: ...lity to ensure the compliance of the entire system with the applicable standards and to issue CE certification We strongly discourage any use of the actuators other than that specified and therefore i...

Page 3: ...roke for the window CANNOT be programmed as it is regulated by the length of the rod on the reduction motor The electronic control device allows the rack to protrude until it encounters an obstacle th...

Page 4: ...closed 8 8 Instructions for assembly These indications are for specialised technical personnel and basic work and safety techniques are not indicated All preparatory assembly and electrical connection...

Page 5: ...e of drill head for perforation and assemble the front bracket taking care to fix the screws securely into position Fig 5 and Fig 5bis F Take the clamp screws and assemble them onto the motor support...

Page 6: ...the clamp screws slightly into the profile and lightly fix the screws into position Check the rack is aligned with that of the motorised actuator G Loosen the clamp screws and place the eyebolt heads...

Page 7: ...ts 1 and 2 in reverse order In the event in which the cable of feeding it is damaged to make to replace it from the constructor or a qualified technician 13 Environmental protection All materials used...

Page 8: ...otti sono conformi alle disposizioni pertinenti delle seguenti Direttive Furthermore the products listed above complies with the provisions of followings Directives 2014 30 EU Direttiva Compatibilit E...