Input/output settings
Below is the settings for the I/O, for all commands are the mandatory start sequence look like
this: NEUNIT=<A>,SETTINGS=IO,IO=<B>
Where <A> as default is 1 and <B> is the number of the I/O you want to configured. All com-
mands must be started with a “,” and all lines must end with a \CR
Description:
Syntax
<A>
Default <A>
R/W
Set the I/O to input or output FUNCTION=<A>
INPUT or OUTPUT INPUT
R/W
Set to use PUSH or PULL
mode for status change on
input. This is a global setting
that applies for all IO.
In PULL mode you have to
request the status of all
input you want to know the
state of like this;
NEUNIT=1,SET-
TINGS=IO,MESSAGE=PUSH\
CR
In PUSH mode the Relay – 8
will send a message to you
when there is a change on
one of the inputs.
E.g. NEUNIT=1,IO=1,STA-
TUS=HIGH\CR
MESSAGE=<A>
PUSH or PULL
PULL
R/W
Link input to relay activation
Input 1 is linked to relay 1
Input 2 is linked to relay 2
…
Input 8 is linked to relay 8
When a relay is linked to
an input this will apply until
they are either unlinked or a
command that control either
the relay or the input are
received.
LINK=<A>
TRUE or FALSE
TRUE
R/W
Example:
NEUNIT=1,SETTINGS=IO,IO=2,FUNCTION=INPUT\CR <- This set output 2 to input