SMOKE User Manual NE41 06004-02 v2.0
3 of 16
1
About SMOKE
SMOKE is a smoke detector with a radio adapter board and can be used
with all NEAT radio receivers and is inteded to be used in warden facilities
or in households.
This user manual is valid for SMOKE with ADAPTER board revision 2 or
later, see “2 Adapter board”.
When delivered SMOKE is configured by default to operate as Stand
Alone, see “5 Stand Alone mode”.
1
Picture 1.
The SMOKE detector
#
Denomination
1 SMOKE unit test button (B1)
Table 1.
SMOKE unit test button placing
1.1
Mounting
The smoke detector must be mounted at the ceiling preferably in the
middle of the room. It can cover a room with maximum 60 m2 floor
surface and at most 6 m room height. The minimum distance from the
walls and other equipment (for instance light tubes and lamps) should be
0.5 m. In a hall way and narrow passages (up to 3 m wide) the detector
covers 7.5 m to each side.
1.2
Installing
Use the accompanying screws and plugs to mount the socket at the
ceiling. Connect the battery, ensure to get the correct polarity. Then
connect the smoke detector to the socket by turning to the right. There is
a distinct click when the detector part is locked to the socket.
SMOKE can not be installed unless the battery is mounted.