50
Connecting the Gas Supply
Maximum Liquefied Propane Delivery Capacity
In Thousands of BTU/H (0.5 in WC pressure drop)
Pipe Size
Length (including fittings)
10 ft
(3 m)
20 ft
(6 m)
30 ft
(9 m)
40 ft
(12 m)
50 ft
(15 m)
60 ft
(18 m)
80 ft
(24 m)
100 ft
(30 m)
125 ft
(38 m)
150 ft
(45 m)
175 ft
(53 m)
200 ft
(60 m)
250 ft
(76 m)
3
/
4
in
608
418
336
287
255
231
212
197
185
175
155
140
129
1 in
1,150
787
632
541
480
434
400
372
349
330
292
265
243
1
1
/
4
in
2,350
1,620
1,300
1,110
985
892
821
763
716
677
600
543
500
1
1
/
2
in
3,520
2,420
1,940
1,660
1,480
1,340
1,230
1,140
1,070
1,010
899
814
749
2 in
6,790
4,660
3,750
3,210
2,840
2,570
2,370
2,200
2,070
1,950
1,730
1,570
1,440
4.2 Measuring the Inlet Gas Pressure
WARNING
The boiler cannot function properly without sufficient inlet gas pressure. Measuring the inlet gas pressure should be performed by a
licensed professional only.
Ɣ
The inlet gas pressure must be maintained between 3.5 in and 10.5 in WC for natural gas and between 8.0 in and 13.5 in WC for liquefied
propane.
Ɣ
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that
system at test pressures in excess of
1
/
2
psi (3.5 kPa).
Ɣ
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing
of the gas supply piping system at test pressures equal to or less than
1
/
2
psi (3.5 kPa).
Summary of Contents for NHB Series
Page 120: ...120 Appendixes 12 6 Component Assembly Diagrams and Part Lists 12 6 1 Case Assembly NFB 301C...
Page 122: ...122 Appendixes 12 6 2 Case Assembly NFB 399C...
Page 124: ...124 Appendixes 12 6 3 Heat Exchanger and Waterway Assembly NFB 301C...
Page 126: ...126 Appendixes 12 6 4 Heat Exchanger and Waterway Assembly NFB 399C...
Page 128: ...128 Appendixes 12 6 5 Combustion Parts Assembly NFB 301C...
Page 131: ...131 Appendixes 12 6 6 Combustion Parts Assembly NFB 399C...
Page 134: ...Memo...