Station Reference Ground
Install a station reference ground that provides a continuous, low impedance path to the earth.
Prepare to connect the transmitter cabinet's designated safety ground point (see
), the shield of the coaxial feedline, the ground connection of the power source and the ground
connection on the surge protector directly to the station reference ground, using a 10 cm (4 in.) wide
copper strap.
Ensure that the transmitter site’s grounding rods are adequate. For more information about electrical
grounding protection, see Nautel’s
Recommendations for Transmitter Site Preparation Manual.