USER GUIDE

MON-10467

12-Channel Wireless Vibration Measurement Device

MON-10467

This document explains how to install the MON-10467. You can use the MON-10467 to
wirelessly connect up to 12 sensors, such as piezoelectric accelerometers, proximity probes,
tachometers, voltage, and temperature, to your network without conduit for power or network
lines. This device is available in lithium battery, 24 V DC, and 120/220 V AC variants to
support your application’s requirements. Rated for outdoor use, the MON-10467 has a rugged

Summary of Contents for MON-10467

Page 1: ...to wirelessly connect up to 12 sensors such as piezoelectric accelerometers proximity probes tachometers voltage and temperature to your network without conduit for power or network lines This device...

Page 2: ...ent in the system to determine the safety and EMC ratings for the entire system Contents Related Documentation 3 Unpacking 3 Kit Contents 3 What You Need to Get Started 4 Safety 5 Electromagnetic Comp...

Page 3: ...SD prevention measures during unpacking installation maintenance and operation Notice Never touch exposed signal terminals power terminals or antenna connector Remove the device from the package and i...

Page 4: ...n for unused ports PG16 gland supplied by NI or 0 5 in conduit fitting Power cable with a smooth round jacket and individual conductors up to 12 AWG that comply with your local electrical code Tools n...

Page 5: ...g actuation tool WAGO part number 279 433 Optional 19 mm gland dome nut tightening tool SEALCON part number S 1900 WR Optional 24 mm gland dome nut tightening tool SEALCON part number S 2400 WR MON 10...

Page 6: ...al codes by trained personnel to serve as the power disconnect when installing the MON 10467 AC The circuit breaker box must be easy to reach and marked as the power disconnect for the device Attentio...

Page 7: ...For EMC declarations and certifications and additional information refer to the Product Certifications and Declarations section Notice The length of the signal cable must be no longer than 30 m 100 f...

Page 8: ...Parts Diagrams MON 10467 with Door Closed MON 10467 1 2 3 3 3 3 2 4 5 1 Antenna 2 Mounting flanges 3 Captive screws 4 Glands 5 Door 8 ni com MON 10467 User Guide...

Page 9: ...0467 AC Parts Diagram 3 5 2 1 4 1 24 V DC power bus terminals 2 Reset button 3 Analog input terminals 4 AC power input terminals 5 Door pocket for desiccant pack MON 10467 User Guide National Instrume...

Page 10: ...0467 DC Parts Diagram 1 2 3 6 5 4 1 24 V DC power bus terminals 2 Reset button 3 Analog input terminals 4 Chassis ground screw 5 Ground shelf 6 Door pocket for desiccant pack 10 ni com MON 10467 User...

Page 11: ...t 3 Reset button 4 Analog input terminals 5 Chassis ground screw 6 Ground shelf 7 Door pocket for desiccant pack Pinouts Analog Input Pinout AI0 AI0 AI4 AI4 AI8 AI8 AI1 AI1 AI5 AI5 AI9 AI9 AI2 AI2 AI6...

Page 12: ...ction to the MON 10467 enclosure to which the input signal cable shield or drain wire can be connected Notice Refer to the MON 10467 Specifications on ni com manuals to ensure that the devices you con...

Page 13: ...he MON 10467 1 Loosen the four captive screws on the door of the device with a 1 4 in socket or 6 mm 1 4 in flat blade screwdriver 2 Open the door of the device slowly 3 Clean the gasket and gasket ma...

Page 14: ...he device against the surface on which you want to mount it 2 Insert bolts into the mounting holes placing at least two bolts on each flange You must use at least four bolts in total to secure the dev...

Page 15: ...nic Accessories You can use third party accessories such as proximity probe drivers with the MON 10467 AC and MON 10467 DC You can install up to two proximity probe drivers per device using the indust...

Page 16: ...and three dimensional models of your device visit ni com dimensions Figure 3 MON 10467 AC Proximity Probe Drivers and Electronic Accessories Hole Pattern 14 90 mm 0 587 in 72 60 mm 2 858 in 50 80 mm 2...

Page 17: ...08 mm 4 252 in 27 40 mm 1 079 in 27 60 mm 1 087 in 50 80 mm 2 00 in 88 90 mm 3 50 in 119 90 mm 4 720 in 3 90 mm 0 547 in 6 20 mm 0 638 in 6 20 mm 0 638 in 6 20 mm 0 638 in If you are planning to use p...

Page 18: ...ng Wiring Guidelines Adhere to the following guidelines when wiring the MON 10467 Caution All wiring must be insulated for the highest voltage used Attention Tout le c blage doit tre isol pour la plus...

Page 19: ...ground is not directly accessible The MON 10467 provides overvoltage protection for each channel Refer to the MON 10467 Specifications on ni com manuals for more information about overvoltage protect...

Page 20: ...2 OUT Note You must install a jumper wire between the two AI terminals as shown above Note Connect the two dual sensor outputs to simultaneously sampled channels Hardware needed 0 08 mm2 to 1 5 mm2 24...

Page 21: ...the spring terminal by inserting a 2 5 mm flat blade screwdriver and pressing the lever Tip Try using a prying motion to move the lever as shown below if you are having difficulty You can also activa...

Page 22: ...or example a sensor fault could cause a short circuit If an open or short event occurs the hardware will continue to perform the configured acquisition and return the acquisition to InsightCM but will...

Page 23: ...and comes with a 5 mm to 9 mm grommet 5 Open the AC power input spring terminals by inserting a 2 5 mm flat blade screwdriver and pressing the lever 6 Connect the line neutral and protective earth gro...

Page 24: ...nt signal integrity Complete the following steps 1 Confirm that the power source has been turned off 2 Install the gland on the device enclosure You may use the gland provided by NI or your own gland...

Page 25: ...th inspecting proper insertion and to prevent any stray strands from contacting adjacent connections 7 Install the chassis ground connection to the ground shelf using the provided M4 ground screw and...

Page 26: ...ew and tighten with a 2 Phillips screwdriver to a torque of 1 3 N m 11 5 lb in Note You must use a ring or spade lug for this connection 4 Insert the earth ground cable through the gland using the app...

Page 27: ...tion Mettez le MON 10467 DC hors tension avant de l ouvrir pour l entretien Notice Do not put a load on the device door while it is open Figure 12 Puncturing and Inserting the Desiccant Pack Puncture...

Page 28: ...int gr e Renvoyez les mod les endommag s NI pour r paration Caution Risk of fire explosion and burns Do not open crush charge incinerate operate above 75 C or expose contents to water Attention Risqu...

Page 29: ...torque of 1 3 N m 11 5 in lb while holding it in place Be careful not to overtighten the captive screws 8 Connect the new battery pack by inserting the connector of the battery pack cable into the ba...

Page 30: ...nect external power to the MON 10467 AC and use the external circuit breaker box to completely remove mains power before opening the device for service Attention D branchez l alimentation externe du M...

Page 31: ...slowly 9 Tighten the four captive screws on the door of the device to 1 3 N m 11 5 lb in Using the Reset Button on the MON 10467 BATTERY To restart the device complete the following steps 1 Loosen th...

Page 32: ...dditional regulatory compliance information To obtain product certifications and the DoC for NI products visit ni com product certifications search by model number and click the appropriate link World...