Turn on the power source to the device. After about 15 seconds, the STATUS LED blinks
red indicating that the device has been restored to factory-default settings.
4.
Reconnect the Ethernet port 0 to the host.
5.
Turn off and then turn on the power source to the device.
The FieldDAQ device factory-set defaults are listed in the following table.
Table 11. Device Default Settings
Attribute
Value
Hostname
FD11613-<
serial number
>
IP
DHCP or Link Local
Comment
Empty
Default login
User name = admin
Password = no password required
Mounting
FieldDAQ can be mounted on any substrate in any orientation if the ambient temperature is
75 °C or less. However, to ensure proper functionality during use above 75 °C, you must
mount the FieldDAQ device in the reference mounting configuration shown in the following
figure. Observe the following guidelines to mount the FieldDAQ device in the reference
mounting configuration.
FD-11613 User Guide
|
© National Instruments
|