24
Gas Furnace
Flame Rollout Limit Switch
The flame rollout switch protects the burner area from high temperatures. The switch is
normally closed, opens on temperature rise and breaks a circuit back to the DSI Control Board
when tripped. These switches are manual reset switches.
On Non-Condensing Furnaces the Flame Rollout Switch is located on top of the burner
assembly with (2) ¼” screws. It is wired in series with the main air high temperature limit
switch.
Furnace Size (Btuh)
28k
38k
51k
64k
Temperature Limit +/- 5°F
225°F
225°F
225°F
225°F
Furnace Size (Btuh)
25k
32k
43k
50k
Temperature Limit +/- 5°F
235°F
210°F
210°F
210°F
On Condensing Furnaces, the Flame Rollout Switch is located on top of the burner assembly
with (2) small phillips head screws. It is wired in series with the main air high temperature limit
switch and the inducer limit.