Installation Manual for Comfort Pack

 

Electric Units

The unit should be provided with support inside the building in 

the area of the return air opening. The support should be high 

enough to allow for return air provisions to the unit. To reduce 

the possible transmission of sound and vibration, a resilient 

material such as rubber or cork should be installed between the 

support and the base of the unit. All spaces around the top, sides 

and bottom of the exterior grille area should be caulked and 

sealed to the wall, making sure that the openings for drainage in 

the bottom edge are not blocked. 

If the optional wall sleeve is used, caulk the spaces between the 

sleeve and the wall. Completely fill the clearance on all sides 

between the unit and the wall sleeve with a polyurethane foam 

sealant (follow manufacturer’s suggested application manual). 

Provide the unit with support inside the building in the area of 

the return air opening. Slide the unit into the wall sleeve and 

fasten the unit to the sleeve with the five screws provided with 

the sleeve.

NOTE: FOR EASE OF INSTALLATION, INSTALL 

THE CABINET INTO THE WALL SLEEVE FIRST 

WITHOUT THE COOLING CHASSIS. THEN SLIDE 

COOLING CHASSIS IN AFTER CABINET IS IN 

PLACE.

Drainage

The 3/4" I.D. flexible tubing included should be connected to the 

Comfort Pack primary drain connection so that it can easily be 

disconnected if the cooling chassis must be removed. A trap 

at least 2" deep should be provided close to the drain pan. The 

tubing should not be higher than the bottom of the unit drain 

pan at any point to assure proper drainage and allow chassis 

removal. The drain line should pitch downward at least 1" per  

10 ft. to an open building drain trap.

SECONDARY DRAIN TRAP

MUST BE INSTALLED

Drain Pan

3/4” I.D. Flexible Tubing Included

2” 

min.

Pitch Downward 1” per 10ft.

Shaded Area Represents Components 

Provided and Installed By Others

Highest Point Must Not Be Above 

Bottom of Drain Pan

3/4” O.D. Drain Connection

       (Primary Drain)

Secondary Drain Trap Install Instructions:

1.

 The trap and 2

"

 piece of clear flexible 1/2" ID tubing are 

shipped loose to prevent damage. They should be installed after 

the Comfort Pack unit is installed and the return air connection 

completed.

2.

 The trap must be primed (filled with water) for proper 

operation of the secondary drain system. This may be done prior 

to installation of the trap or after.

3.

 Insert trap into the grommet located in chassis base pan.

a. Apply force to section 1 (refer to drawing below)
b.  Ensure at least .5

"

 - 0.75

"

 of tubing is inserted into the 

grommet

c. PVC should be flush with drain pan connection

.

Secondary Drain Connection

Drain Pan

Apply 

Force

1/2” I.D. Tubing

Grommet

Trap

Chassis Base

1

4. 

Position the trap as shown and slide the 2

"

 piece of clear 

flexible tubing about 1

"

 onto the top end of the trap. Slide the 

top of the flexible tube on the trap onto the bottom of the 1/2

"

 

OD secondary drain connection and push the top of the trap up. 

The trap should be positioned so that there is only a small gap 

between the top of the trap and the bottom of the secondary 

drain connection.

5.

 To avoid damage whenever the slide-out chassis has to be 

removed from the cabinet, remove the secondary drain trap 

before sliding the chassis out. After the chassis is reinstalled in 

the cabinet, prime the trap with water before reinstalling it.

Summary of Contents for CPE Series

Page 1: ...This manual must be left with the homeowner for future reference National Comfort Products A Division of National Refrigeration and Air Conditioning Products Inc 539 Dunksferry Road Bensalem PA 19020...

Page 2: ......

Page 3: ...e 11 Maintenance page 12 Dimensional Drawing page 13 Electric Data Performance Data page 14 Comfort Pack Electric CFM Temperature Rise page 15 Air Flow page 15 U 0 Wiring Schematic 0 kw page 18 U 3 Wi...

Page 4: ...Universal Chassis Edition Generation Nominal Cooling Capacity 11 12 000Btu 17 18 000Btu 23 24 000Btu A No Grille B Slotted Filter Door C No Grille with Slotted Filter Door Heating Capacity Electric 0...

Page 5: ...CE PERSONNEL FOR PROPER INSTALLATION ADJUSTMENT AND OPERATION OFTHISUNIT READTHESEINSTRUCTIONSTHOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN...

Page 6: ...elay Once W1 W2 or G is energized the fan will be operated Once de energized the fan will run for an additional 5 seconds Faults If multiple inputs are received with a cooling input Y than the board w...

Page 7: ...SECONDARY DRAIN THROUGH GROMMET OF CHASSIS AND CONNECT TO FLEXIBLE TUBING PRIME TRAP PRIOR TO OPERATING INSTALL THE LOWER ACCESS PANEL ON THE CABINET TURN ON POWER TO THE UNIT ALL phases of this insta...

Page 8: ...ure proper drainage and allow chassis removal The drain line should pitch downward at least 1 per 10 ft to an open building drain trap SECONDARY DRAIN TRAP MUST BE INSTALLED Drain Pan 3 4 I D Flexible...

Page 9: ...iods of rain and wind the primary drainage path may not be adequate to handle the load Secondary precautions may also be required but not limited to the following Seal flashing to unit Floor drain Add...

Page 10: ...C22 1 In addition the installer should be aware of any local ordinances or utility company requirements that might apply Check the rating plate for the supply voltage and current requirements A dedica...

Page 11: ...nd that the service provided by the utility is sufficient to handle the additional load imposed by this equipment Power wiring must comply with national state and local codes Follow instructions on un...

Page 12: ...and do not require routine service The refrigeration system is sealed and factory charged with R 410A so that routine maintenance is not required The electrical controls do not require routine service...

Page 13: ...ion Manual for Comfort Pack Electric Units Comfort Pack Dimension Drawing Option B Slotted Filter Door for Open Returns 43 26 57 64 7 15 16 31 13 32 7 21 32 1 1 64 28 15 13 16 Side view 3 3 4 7 43 64...

Page 14: ...30 CPE41107 U 208 230 60 1 4 7 29 5 1 4 2 4 1 3 3 0 38 8 35 3 40 40 CPE41110 U 208 230 60 1 4 7 29 5 1 4 2 4 1 3 3 0 53 8 48 9 55 50 CPE41700 U 208 230 60 1 6 5 37 5 1 4 1 8 3 6 1 3 3 0 13 13 15 15 CP...

Page 15: ...80 29 2 520 32 6 450 37 7 380 44 6 Black 4 550 30 8 500 33 9 430 39 4 340 49 9 240 70 6 Orange 5 415 40 9 325 52 2 225 75 4 n a n a n a n a CPE41707 Red 1 780 21 7 770 22 0 760 22 3 725 23 4 680 24 9...

Page 16: ...80 35 8 520 40 0 450 46 2 380 54 7 Black 4 550 37 8 500 41 6 430 48 3 340 61 1 240 86 6 Orange 5 415 50 1 325 63 9 225 92 3 n a n a n a n a CPE41707 Red 1 780 26 6 770 27 0 760 27 3 725 28 7 680 30 6...

Page 17: ...715 690 660 620 560 Blue 3 620 580 520 450 380 Black 4 550 500 430 340 240 Orange 5 415 325 225 X X CPE417 Red 1 780 770 760 725 680 Yellow 2 715 690 660 620 560 Blue 3 620 580 520 450 380 Black 4 55...

Page 18: ...18 Installation Manual for Comfort Pack Electric Units U 00 Wiring Schematic 0Kw...

Page 19: ...19 Installation Manual for Comfort Pack Electric Units U 3 Wiring Schematic Electric Heat 3 5 7 10Kw...

Page 20: ...20 Installation Manual for Comfort Pack Electric Units U 3 Wiring Schematic Electric Heat 15Kw...

Page 21: ...12 Fuse Panel 14693031 14693030 14693029A Top Mount Angle 14256101 Control Board Wiring 14299001 14299002 Upper Intake Grille 14256438 Control Board 14262041 Lower Discharge Grille 14256437 Contactor...

Page 22: ...25397 TXV 14275100 14275117 14275118 Outdoor Fan Motor 14270057 14270044 14270057 Outdoor Coil Mount 14256430 14256434 Drier 14275947 Outdoor Fan 14214042 Outdoor Motor Mount 14270101 Indoor Blower Mo...

Page 23: ...Reading between Terminals C R __________ 5 Compressor Winding OHM Reading between Terminals R S __________ 6 Compressor Winding OHM Reading between Terminals C Ground __________ 7 Compressor Winding O...

Page 24: ...to the goods and are in lieu of and exclude all other warranties express or implied arising by operation of law or otherwise including without limitation merchantability and fitness for a particular p...

Page 25: ...ure shall render the warranty void B Compressors In addition to the above referenced requirements Customer is also required to purchase a replacement compressor and return the original compressor to N...

Page 26: ...26 Installation Manual for Comfort Pack Electric Units Notes...

Page 27: ...27 Installation Manual for Comfort Pack Electric Units Notes...

Page 28: ...TING A C EQUIPMENT NATIONAL COMFORT PRODUCTS National Comfort Products A Division of National Refrigeration Air Conditioning Products Inc 539 Dunksferry Road Bensalem PA 19020 1 800 523 7138 Fax 215 6...

Reviews: