Comfort Pack Airflow Data @208 Volts

Unit Size

Color

Speed Tap

0.1

TR

0.2

TR

0.3

TR

0.4

TR

0.5

TR

CPE41103

Red

1

780

10.6

770

10.7

760

10.9

725

11.4

680

12.2

Yellow

2

715

11.6

690

12.0

660

12.5

620

13.3

560

14.8

Blue

3

620

13.3

580

14.3

520

15.9

450

18.4

380

21.8

Black

4

550

15.0

500

16.5

430

19.2

340

24.3

240

34.5

Orange

5

415

19.9

325

25.5

225

36.8

n/a

n/a

n/a

n/a

CPE41703

Red

1

780

10.6

770

10.7

760

10.9

725

11.4

680

12.2

Yellow

2

715

11.6

690

12.0

660

12.5

620

13.3

560

14.8

Blue

3

620

13.3

580

14.3

520

15.9

450

18.4

380

21.8

Black

4

550

15.0

500

16.5

430

19.2

340

24.3

240

34.5

Orange

5

415

19.9

325

25.5

225

36.8

n/a

n/a

n/a

n/a

CPE42303

Red

1

850

9.7

833

9.9

815

10.1

803

10.3

790

10.5

Yellow

2

750

11.0

730

11.3

710

11.7

698

11.9

685

12.1

Blue

3

635

13.0

613

13.5

590

14.0

576

14.4

562

14.7

Black

4

555

14.9

533

15.5

510

16.2

493

16.8

475

17.4

Orange

5

405

20.4

378

21.9

350

23.6

328

25.2

305

27.1

CPE41105

Red

1

780

15.5

770

15.7

760

15.9

725

16.7

680

17.8

Yellow

2

715

16.9

690

17.5

660

18.3

620

19.5

560

21.6

Blue

3

620

19.5

580

20.8

520

23.3

450

26.9

380

31.8

Black

4

550

22.0

500

24.2

430

28.1

340

35.6

240

50.4

Orange

5

415

29.1

325

37.2

225

53.7

n/a

n/a

n/a

n/a

CPE41705

Red

1

780

15.5

770

15.7

760

15.9

725

16.7

680

17.8

Yellow

2

715

16.9

690

17.5

660

18.3

620

19.5

560

21.6

Blue

3

620

19.5

580

20.8

520

23.3

450

26.9

380

31.8

Black

4

550

22.0

500

24.2

430

28.1

340

35.6

240

50.4

Orange

5

415

29.1

325

37.2

225

53.7

n/a

n/a

n/a

n/a

CPE42305

Red

1

850

14.2

833

14.5

815

14.8

803

15.1

790

15.3

Yellow

2

750

16.1

730

16.6

710

17.0

698

17.3

685

17.7

Blue

3

635

19.0

613

19.7

590

20.5

576

21.0

562

21.5

Black

4

555

21.8

533

22.7

510

23.7

493

24.5

475

25.5

Orange

5

405

29.9

378

32.0

350

34.6

328

36.9

305

39.6

CPE41107

Red

1

780

21.7

770

22.0

760

22.3

725

23.4

680

24.9

Yellow

2

715

23.7

690

24.6

660

25.7

620

27.3

560

30.3

Blue

3

620

27.3

580

29.2

520

32.6

450

37.7

380

44.6

Black

4

550

30.8

500

33.9

430

39.4

340

49.9

240

70.6

Orange

5

415

40.9

325

52.2

225

75.4

n/a

n/a

n/a

n/a

CPE41707

Red

1

780

21.7

770

22.0

760

22.3

725

23.4

680

24.9

Yellow

2

715

23.7

690

24.6

660

25.7

620

27.3

560

30.3

Blue

3

620

27.3

580

29.2

520

32.6

450

37.7

380

44.6

Black

4

550

30.8

500

33.9

430

39.4

340

49.9

240

70.6

Orange

5

415

40.9

325

52.2

225

75.4

n/a

n/a

n/a

n/a

CPE42307

Red

1

850

19.9

833

20.4

815

20.8

803

21.1

790

21.5

Yellow

2

750

22.6

730

23.2

710

23.9

698

24.3

685

24.8

Blue

3

635

26.7

613

27.7

590

28.7

576

29.4

562

30.2

Black

4

555

30.6

533

31.8

510

33.2

493

34.4

475

35.7

Orange

5

405

41.9

378

44.9

350

48.4

328

51.7

305

55.6

CPE41110

Red

1

780

30.9

770

31.3

760

31.7

725

33.3

680

35.5

Yellow

2

715

33.7

690

35.0

660

36.5

620

38.9

560

43.1

Blue

3

620

38.9

580

41.6

520

46.4

450

53.6

380

63.5

Black

4

550

43.9

500

48.2

430

56.1

340

70.9

240

100.5

Orange

5

415

58.1

325

74.2

225

107.2

n/a

n/a

n/a

n/a

CPE41710

Red

1

780

30.9

770

31.3

760

31.7

725

33.3

680

35.5

Yellow

2

715

33.7

690

35.0

660

36.5

620

38.9

560

43.1

Blue

3

620

38.9

580

41.6

520

46.4

450

53.6

380

63.5

Black

4

550

43.9

500

48.2

430

56.1

340

70.9

240

100.5

Orange

5

415

58.1

325

74.2

225

107.2

n/a

n/a

n/a

n/a

CPE42310

Red

1

850

28.4

833

29.0

815

29.6

803

30.0

790

30.5

Yellow

2

750

32.2

730

33.0

710

34.0

698

34.6

685

35.2

Blue

3

635

38.0

613

39.4

590

40.9

576

41.9

562

42.9

Black

4

555

43.5

533

45.3

510

47.3

493

48.9

475

50.8

Orange

5

405

59.6

378

63.8

350

68.9

328

73.5

305

79.1

CPE41715

Red

1

780

46.4

770

47.0

760

47.7

725

50.0

680

53.3

Yellow

2

715

50.7

690

52.5

660

54.9

620

58.4

560

64.7

Blue

3

620

58.4

580

62.4

520

69.6

450

80.5

380

95.3

Black

4

550

65.8

500

72.4

430

84.2

340

106.5

240

150.9

Orange

5

415

87.3

325

111.4

225

161.0

n/a

n/a

n/a

n/a

CPE42315

Red

1

850

42.6

833

43.5

815

44.4

803

45.1

790

45.8

Yellow

2

750

48.3

730

49.6

710

51.0

698

51.9

685

52.9

Blue

3

635

57.0

613

59.1

590

61.4

576

62.9

562

64.4

Black

4

555

65.3

533

67.9

510

71.0

493

73.5

475

76.2

Orange

5

405

89.4

378

95.8

350

103.5

328

110.4

305

118.7

**CPE4XX00-U MODELS DO NOT REQUIRE A HEAT TEMPERATURE RISE

Summary of Contents for CPE Series

Page 1: ...This manual must be left with the homeowner for future reference National Comfort Products A Division of National Refrigeration and Air Conditioning Products Inc 539 Dunksferry Road Bensalem PA 19020...

Page 2: ......

Page 3: ...e 11 Maintenance page 12 Dimensional Drawing page 13 Electric Data Performance Data page 14 Comfort Pack Electric CFM Temperature Rise page 15 Air Flow page 15 U 0 Wiring Schematic 0 kw page 18 U 3 Wi...

Page 4: ...Universal Chassis Edition Generation Nominal Cooling Capacity 11 12 000Btu 17 18 000Btu 23 24 000Btu A No Grille B Slotted Filter Door C No Grille with Slotted Filter Door Heating Capacity Electric 0...

Page 5: ...CE PERSONNEL FOR PROPER INSTALLATION ADJUSTMENT AND OPERATION OFTHISUNIT READTHESEINSTRUCTIONSTHOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN...

Page 6: ...elay Once W1 W2 or G is energized the fan will be operated Once de energized the fan will run for an additional 5 seconds Faults If multiple inputs are received with a cooling input Y than the board w...

Page 7: ...SECONDARY DRAIN THROUGH GROMMET OF CHASSIS AND CONNECT TO FLEXIBLE TUBING PRIME TRAP PRIOR TO OPERATING INSTALL THE LOWER ACCESS PANEL ON THE CABINET TURN ON POWER TO THE UNIT ALL phases of this insta...

Page 8: ...ure proper drainage and allow chassis removal The drain line should pitch downward at least 1 per 10 ft to an open building drain trap SECONDARY DRAIN TRAP MUST BE INSTALLED Drain Pan 3 4 I D Flexible...

Page 9: ...iods of rain and wind the primary drainage path may not be adequate to handle the load Secondary precautions may also be required but not limited to the following Seal flashing to unit Floor drain Add...

Page 10: ...C22 1 In addition the installer should be aware of any local ordinances or utility company requirements that might apply Check the rating plate for the supply voltage and current requirements A dedica...

Page 11: ...nd that the service provided by the utility is sufficient to handle the additional load imposed by this equipment Power wiring must comply with national state and local codes Follow instructions on un...

Page 12: ...and do not require routine service The refrigeration system is sealed and factory charged with R 410A so that routine maintenance is not required The electrical controls do not require routine service...

Page 13: ...ion Manual for Comfort Pack Electric Units Comfort Pack Dimension Drawing Option B Slotted Filter Door for Open Returns 43 26 57 64 7 15 16 31 13 32 7 21 32 1 1 64 28 15 13 16 Side view 3 3 4 7 43 64...

Page 14: ...30 CPE41107 U 208 230 60 1 4 7 29 5 1 4 2 4 1 3 3 0 38 8 35 3 40 40 CPE41110 U 208 230 60 1 4 7 29 5 1 4 2 4 1 3 3 0 53 8 48 9 55 50 CPE41700 U 208 230 60 1 6 5 37 5 1 4 1 8 3 6 1 3 3 0 13 13 15 15 CP...

Page 15: ...80 29 2 520 32 6 450 37 7 380 44 6 Black 4 550 30 8 500 33 9 430 39 4 340 49 9 240 70 6 Orange 5 415 40 9 325 52 2 225 75 4 n a n a n a n a CPE41707 Red 1 780 21 7 770 22 0 760 22 3 725 23 4 680 24 9...

Page 16: ...80 35 8 520 40 0 450 46 2 380 54 7 Black 4 550 37 8 500 41 6 430 48 3 340 61 1 240 86 6 Orange 5 415 50 1 325 63 9 225 92 3 n a n a n a n a CPE41707 Red 1 780 26 6 770 27 0 760 27 3 725 28 7 680 30 6...

Page 17: ...715 690 660 620 560 Blue 3 620 580 520 450 380 Black 4 550 500 430 340 240 Orange 5 415 325 225 X X CPE417 Red 1 780 770 760 725 680 Yellow 2 715 690 660 620 560 Blue 3 620 580 520 450 380 Black 4 55...

Page 18: ...18 Installation Manual for Comfort Pack Electric Units U 00 Wiring Schematic 0Kw...

Page 19: ...19 Installation Manual for Comfort Pack Electric Units U 3 Wiring Schematic Electric Heat 3 5 7 10Kw...

Page 20: ...20 Installation Manual for Comfort Pack Electric Units U 3 Wiring Schematic Electric Heat 15Kw...

Page 21: ...12 Fuse Panel 14693031 14693030 14693029A Top Mount Angle 14256101 Control Board Wiring 14299001 14299002 Upper Intake Grille 14256438 Control Board 14262041 Lower Discharge Grille 14256437 Contactor...

Page 22: ...25397 TXV 14275100 14275117 14275118 Outdoor Fan Motor 14270057 14270044 14270057 Outdoor Coil Mount 14256430 14256434 Drier 14275947 Outdoor Fan 14214042 Outdoor Motor Mount 14270101 Indoor Blower Mo...

Page 23: ...Reading between Terminals C R __________ 5 Compressor Winding OHM Reading between Terminals R S __________ 6 Compressor Winding OHM Reading between Terminals C Ground __________ 7 Compressor Winding O...

Page 24: ...to the goods and are in lieu of and exclude all other warranties express or implied arising by operation of law or otherwise including without limitation merchantability and fitness for a particular p...

Page 25: ...ure shall render the warranty void B Compressors In addition to the above referenced requirements Customer is also required to purchase a replacement compressor and return the original compressor to N...

Page 26: ...26 Installation Manual for Comfort Pack Electric Units Notes...

Page 27: ...27 Installation Manual for Comfort Pack Electric Units Notes...

Page 28: ...TING A C EQUIPMENT NATIONAL COMFORT PRODUCTS National Comfort Products A Division of National Refrigeration Air Conditioning Products Inc 539 Dunksferry Road Bensalem PA 19020 1 800 523 7138 Fax 215 6...

Reviews: