National Comfort Products CPE Series Installation Manual Download Page 6

6

Installation Manual for Comfort Pack

 

Electric Units

Before You Start

This unit is shipped with a cooling chassis installed in the 

cabinet. Prior to installing the unit in the wall opening, the 

shipping bolts located at the bottom on both sides of the cabinet 

must be removed to allow for removal of the cooling chassis. 

1/4" hole plugs provided with the unit should be installed in the 

holes to prevent air leakage. Shipping bolts are located on both 

sides below this sticker:

THE SHIPPING BOLTS MUST BE REMOVED PRIOR 

TO INSTALLATION OF THE CABINET TO PERMIT  

REMOVAL OF THE CHASSIS. INSTALL THE HOLE 

PLUGS PROVIDED.

14299588

This unit is designed and approved for through-the-wall 

installation only. The unit must be installed a minimum of 8” 

above finish floor. If this unit is installed in a residential 

garage, it must be installed so that the ignition source and 

burners are located not less than 18 inches (457 mm) above 

the floor, and it must be located or protected to avoid physical 

damage by vehicles. The entire unit must not be installed 

outside.

 The grille side of the unit should extend 3/4" beyond the 

exterior wall to allow moisture that may enter the outdoor 

section to drain. The pitch of the internal drain pans toward the 

outside will assure proper drainage when the cabinet is installed 

level. 

Masonry walls must have a lintel to support the wall.

The interior of the unit may be installed with zero clearances to 

adjacent combustible surfaces. 

The unit shall not be installed 

directly on carpeting, tile or other combustible material, 

except wood flooring. 

In order to be able to remove the chassis, 

29” of open area must be left unobstructed in front of the access 

panels. The 3/4” O.D. drain pan connection should be connected 

to the building drain using the flexible tubing included and 

a trap. The secondary drain offers protection from overflow.  

When a call for heat is active sending power to the W1 and W2 

heating terminals on the control board, the board will begin to 

sequence the heating outputs to energize the heat contactors. 

Once W1 is energized the board will sequence output W1A after 

a 3 second delay and W1B after a 28 second delay. Once W2 

is energized the board will sequence out W2 after a 45 second 

delay. Once W1, W2, or G is energized the fan will be operated. 

Once de-energized the fan will run for an additional 5 seconds. 

Faults

If multiple inputs are received with a cooling input (Y) than the 

board will automatically fault and run in cooling. 

Cooling Blower Operation

Cooling fan will delay 5 seconds on a call for cooling and  

will delay off when a call is terminated for the duration of the 

board jumper set point. (A = 5 sec., B = 30 sec., C = 60 sec., & 

D = 90 sec.)  

The secondary drain feature is piped into the base of the unit 

and drains through the weep holes outside. Reconnect 3” piece 

of clear flexible tubing to secondary drain on drain pan. Position 

secondary drain through grommet of chassis and connect to 

flexible tubing (prime trap prior to operating).

The grille side must be kept free of any obstructions that will 

reduce or alter the air flow pattern. 

If an optional architectural grille is to be used on standard units, 

the stamped and louvered grille provided 

must 

be removed. 

Consult the factory prior to ordering product(s) that require an 

optional architectural grille.

THE INSTALLATION OF THIS APPLIANCE 

MUST CONFORM TO THE REQUIREMENTS 

OF THE NATIONAL FIRE PROTECTION 

ASSOCIATION; THE NATIONAL ELECTRIC 

CODE, ANSI/NFPA NO. 70 (LATEST EDITION) 

IN THE UNITED STATES; THE CANADIAN 

ELECTRICAL CODE PART 1, CSA 22.1 (LATEST 

EDITION) IN CANADA; AND ANY STATE OR 

PROVINCIAL LAWS OR LOCAL ORDINANCES. 

LOCAL AUTHORITIES HAVING JURISDICTION 

SHOULD BE CONSULTED BEFORE 

INSTALLATION IS MADE. SUCH APPLICABLE 

REGULATIONS OR REQUIREMENTS TAKE 

PRECEDENCE OVER THE GENERAL 

INSTRUCTIONS IN THE MANUAL.

!

CAUTION

TO REMOVE THE CHASSIS FROM THE CABINET:

TURN OFF POWER TO THE UNIT. REMOVE THE LOWER 

ACCESS PANEL FROM THE CABINET. DISCONNECT 

THE DRAIN LINE FROM THE EVAPORATOR COIL DRAIN 

CONNECTION. DISCONNECT THE SECONDARY DRAIN 

FLEXIBLE TUBING & TRAP TO AVOID DAMAGE (PRIME 

TRAP WHEN REINSTALLING). DEPRESS AND HOLD THE 

RELEASE LATCH ON THE CHASSIS POWER WIRING 

CONNECTOR AND UNPLUG IT FROM THE CABINET POWER 

WIRING CONNECTOR. 

DEPRESS AND HOLD THE RELEASE LATCH ON THE 

CONTROL WIRING CONNECTOR AND UNPLUG IT FROM 

THE CABINET CONTROL WIRING CONNECTOR. REMOVE 

THE SCREWS ATTACHING THE CONTROLS ENCLOSURE TO 

THE INDOOR COIL COVER. REMOVE THE SCREWS FROM 

THE INDOOR BLOWER COVER PLATE. REMOVE THE PLATE 

FROM THE UNIT. TEMPORARILY SECURE THE CHASSIS 

POWER AND CONTROL WIRING AND CONNECTORS TO THE 

TOP OF THE INDOOR COIL COVER TO PREVENT DAMAGE 

DURING CHASSIS REMOVAL. 

Summary of Contents for CPE Series

Page 1: ...This manual must be left with the homeowner for future reference National Comfort Products A Division of National Refrigeration and Air Conditioning Products Inc 539 Dunksferry Road Bensalem PA 19020...

Page 2: ......

Page 3: ...e 11 Maintenance page 12 Dimensional Drawing page 13 Electric Data Performance Data page 14 Comfort Pack Electric CFM Temperature Rise page 15 Air Flow page 15 U 0 Wiring Schematic 0 kw page 18 U 3 Wi...

Page 4: ...Universal Chassis Edition Generation Nominal Cooling Capacity 11 12 000Btu 17 18 000Btu 23 24 000Btu A No Grille B Slotted Filter Door C No Grille with Slotted Filter Door Heating Capacity Electric 0...

Page 5: ...CE PERSONNEL FOR PROPER INSTALLATION ADJUSTMENT AND OPERATION OFTHISUNIT READTHESEINSTRUCTIONSTHOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN...

Page 6: ...elay Once W1 W2 or G is energized the fan will be operated Once de energized the fan will run for an additional 5 seconds Faults If multiple inputs are received with a cooling input Y than the board w...

Page 7: ...SECONDARY DRAIN THROUGH GROMMET OF CHASSIS AND CONNECT TO FLEXIBLE TUBING PRIME TRAP PRIOR TO OPERATING INSTALL THE LOWER ACCESS PANEL ON THE CABINET TURN ON POWER TO THE UNIT ALL phases of this insta...

Page 8: ...ure proper drainage and allow chassis removal The drain line should pitch downward at least 1 per 10 ft to an open building drain trap SECONDARY DRAIN TRAP MUST BE INSTALLED Drain Pan 3 4 I D Flexible...

Page 9: ...iods of rain and wind the primary drainage path may not be adequate to handle the load Secondary precautions may also be required but not limited to the following Seal flashing to unit Floor drain Add...

Page 10: ...C22 1 In addition the installer should be aware of any local ordinances or utility company requirements that might apply Check the rating plate for the supply voltage and current requirements A dedica...

Page 11: ...nd that the service provided by the utility is sufficient to handle the additional load imposed by this equipment Power wiring must comply with national state and local codes Follow instructions on un...

Page 12: ...and do not require routine service The refrigeration system is sealed and factory charged with R 410A so that routine maintenance is not required The electrical controls do not require routine service...

Page 13: ...ion Manual for Comfort Pack Electric Units Comfort Pack Dimension Drawing Option B Slotted Filter Door for Open Returns 43 26 57 64 7 15 16 31 13 32 7 21 32 1 1 64 28 15 13 16 Side view 3 3 4 7 43 64...

Page 14: ...30 CPE41107 U 208 230 60 1 4 7 29 5 1 4 2 4 1 3 3 0 38 8 35 3 40 40 CPE41110 U 208 230 60 1 4 7 29 5 1 4 2 4 1 3 3 0 53 8 48 9 55 50 CPE41700 U 208 230 60 1 6 5 37 5 1 4 1 8 3 6 1 3 3 0 13 13 15 15 CP...

Page 15: ...80 29 2 520 32 6 450 37 7 380 44 6 Black 4 550 30 8 500 33 9 430 39 4 340 49 9 240 70 6 Orange 5 415 40 9 325 52 2 225 75 4 n a n a n a n a CPE41707 Red 1 780 21 7 770 22 0 760 22 3 725 23 4 680 24 9...

Page 16: ...80 35 8 520 40 0 450 46 2 380 54 7 Black 4 550 37 8 500 41 6 430 48 3 340 61 1 240 86 6 Orange 5 415 50 1 325 63 9 225 92 3 n a n a n a n a CPE41707 Red 1 780 26 6 770 27 0 760 27 3 725 28 7 680 30 6...

Page 17: ...715 690 660 620 560 Blue 3 620 580 520 450 380 Black 4 550 500 430 340 240 Orange 5 415 325 225 X X CPE417 Red 1 780 770 760 725 680 Yellow 2 715 690 660 620 560 Blue 3 620 580 520 450 380 Black 4 55...

Page 18: ...18 Installation Manual for Comfort Pack Electric Units U 00 Wiring Schematic 0Kw...

Page 19: ...19 Installation Manual for Comfort Pack Electric Units U 3 Wiring Schematic Electric Heat 3 5 7 10Kw...

Page 20: ...20 Installation Manual for Comfort Pack Electric Units U 3 Wiring Schematic Electric Heat 15Kw...

Page 21: ...12 Fuse Panel 14693031 14693030 14693029A Top Mount Angle 14256101 Control Board Wiring 14299001 14299002 Upper Intake Grille 14256438 Control Board 14262041 Lower Discharge Grille 14256437 Contactor...

Page 22: ...25397 TXV 14275100 14275117 14275118 Outdoor Fan Motor 14270057 14270044 14270057 Outdoor Coil Mount 14256430 14256434 Drier 14275947 Outdoor Fan 14214042 Outdoor Motor Mount 14270101 Indoor Blower Mo...

Page 23: ...Reading between Terminals C R __________ 5 Compressor Winding OHM Reading between Terminals R S __________ 6 Compressor Winding OHM Reading between Terminals C Ground __________ 7 Compressor Winding O...

Page 24: ...to the goods and are in lieu of and exclude all other warranties express or implied arising by operation of law or otherwise including without limitation merchantability and fitness for a particular p...

Page 25: ...ure shall render the warranty void B Compressors In addition to the above referenced requirements Customer is also required to purchase a replacement compressor and return the original compressor to N...

Page 26: ...26 Installation Manual for Comfort Pack Electric Units Notes...

Page 27: ...27 Installation Manual for Comfort Pack Electric Units Notes...

Page 28: ...TING A C EQUIPMENT NATIONAL COMFORT PRODUCTS National Comfort Products A Division of National Refrigeration Air Conditioning Products Inc 539 Dunksferry Road Bensalem PA 19020 1 800 523 7138 Fax 215 6...

Reviews: