Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp or American Metal Amerivent venting components.
For Simpson Dura-Vent, Selkirk Direct Temp and American Metal Amerivent, follow the installation procedure provided with the venting
components.
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using a red high temperature
silicone (RTV). This same sealant maybe used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems
except for the exhaust vent pipe connection to the fi replace fl ue collar which must be sealed using the black high temperature sealant Mill
Pac.
Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp and American Metal Amerivent venting systems must not be combined.
A starter adaptor must be used and may be purchased from the corresponding supplier:
Supplier 5&8
ZC
Dura-Vent W175-0170
Amerivent 5DSC-N2
Direct Temp
5DT-AA
For Simpson Dura-Vent, Selkirk Direct Temp and American Metal Amerivent, follow the installation procedure found on the website for your
venting supplier.
VENTING SUPPLIER
WEBSITE
Simpson Dura-Vent
www.duravent.com
Selkirk Direct Temp
www.selkirkcorp.com
American Metal Amerivent
www.americanmetalproducts.com
VENTING
VENTING LENGTHS AND AIR TERMINAL LOCATIONS
When using Wolf Steel Ltd. venting components, use only approved Wolf Steel Ltd. rigid / fl exible vent components with the following ter-
mination kits: WALL TERMINAL KIT
GD422R
, or 1/12 TO 7/12 PITCH ROOF TERMINAL KIT
GD410
, 8/12 TO 12/12 ROOF TERMINAL
KIT
GD411
, FLAT ROOF TERMINAL KIT
GD412
or PERISCOPE KIT
GD401
(for wall penetration below grade). With fl exible venting,
in
conjunction with the various terminations, use either the 5 foot vent kit
GD420
or the 10 foot vent kit
GD430
. These vent kits allow for either
horizontal or vertical venting of the fi replace.
The
maximum allowable vertical vent length is 40 feet.
The maximum number of allowable 5” vent connections is
three horizontally
or
vertically
(excluding the fi replace and the air terminal connections).
For optimum fl ame appearance and fi replace performance, keep the vent
length and number of elbows to a minimum. The air terminal must remain
unobstructed at all times. Examine the air terminal at least once a year to
verify that it is unobstructed and undamaged.
When venting, the horizontal run must be kept to a minimum of 16“ or a
maximum of 20 feet. If a 20 foot horizontal run is required, the fi replace
must have a minimum vertical rise immediately off the fi replace of 57“.
FIGURES 2a-c. When terminating vertically, the vertical rise is a minimum
3 feet and a maximum 40 feet above the fi replace.
FIGURE 3.
FIGURES 3a
CARE OF GLASS, AND PLATED PARTS
Do not use abrasive cleaners to clean plated parts. Buff lightly with
a clean dry cloth. The glass is 3/16” ceramic glass available from
your Authorized dealer. DO NOT SUBSTITUTE MATERIALS. Clean
the glass after the fi rst 10 hours of operation with a recommended
gas fi replace glass cleaner. Thereafter clean as required. DO NOT
CLEAN GLASS WHEN HOT! If the glass is not kept clean permanent
discolouration and / or blemishes may result.
Summary of Contents for Madison GD80NT
Page 1: ...1 W415 0695 05 12 08 10 00 W415 0695 05 12 08...
Page 4: ...4 W415 0695 05 12 08 FIGURE 1 INSTALLATION OVERVIEW FIREPLACE DIMENSIONS FIGURE 2...
Page 12: ...12 W415 0695 05 12 08 MINIMUM AIR TERMINAL LOCATION CLEARANCES GD 301 FIGURE 13...
Page 35: ...35 W415 0695 05 12 08...
Page 39: ...39 W415 0695 05 12 08 NOTES...
Page 40: ...40 W415 0695 05 12 08 NOTES...