W415-0695 / 05.12.08
HORIZONTAL INSTALLATION
VERTICAL INSTALLATION
INSTALLATION
WALL AND CEILING PROTECTION
FOR SAFE AND PROPER OPERATION OF THE FIREPLACE, FOLLOW THE VENTING INSTRUCTIONS EXACTLY.
**HORIZONTAL VENT SECTIONS:
A minimum clearance of 2" all around the vent pipe on all horizontal runs to combustibles is required
except for clearances in the fi replace enclosure. Use fi restop spacer W010-1800 (supplied).
VERTICAL VENT SECTIONS:
A minimum of 1" all around the vent pipe on all vertical runs to combustibles is required except for clearances
in fi replace enclosures. Use fi restop spacer W500-0367 (not supplied).
This application occurs when venting through a roof. Installation kits
for various roof pitches are available from your Authorized dealer.
See Accessories to order the specifi c kit required.
1.
Determine the air terminal location, cut and frame a 10 3/4”
square opening in the ceiling and the roof to provide the minimum
1“ clearance between the fi replace pipe / liner and any combustible
material. Try to centre the exhaust pipe location midway between
two joists to prevent having to cut them. Use a plumb bob to line
up the centre of the openings. DO NOT FILL THIS SPACE WITH
ANY TYPE OF MATERIAL.
A vent pipe shield and collar will prevent any materials such as
insulation, from fi lling up the 1” air space around the pipe. Nail
headers between the joist for extra support.
2.
Apply a bead of caulking (not supplied) to the framework or to
the Wolf Steel vent pipe shield plate or equivalent (in the case of
a fi nished ceiling), and secure over the opening in the ceiling.
A fi restop must be
placed on the bottom of each framed opening in a roof or ceiling that the venting
system passes through.
Apply a bead of caulking all around and place a fi restop
spacer over the vent shield to restrict cold air from being drawn into the room or
around the fi replace. Ensure that both spacer and shield maintain the required
clearance to combustibles. Once the vent pipe / liner is installed in its fi nal position,
apply high temperature sealant W573-0002 (not supplied) between the pipe / liner
and the fi restop spacer.
3.
In the attic, slide the vent pipe collar down to cover up the open end of the shield and tighten. This will prevent any
material, such as insulation, from fi lling up the 1” air space around the pipe.
FIGURE 14
FIGURE 15
This application occurs when venting through an exterior wall.
Having determined the air terminal location, cut and frame a hole
in an exterior wall. The recommended framed opening is 12
3
/
4
”
W x 12
3
/
4
” H.
See fi gure 14.
1.
Apply a bead of caulking (not supplied) all around and place
a fi restop spacer over the framed hole to restrict cold air from
being drawn into the room or around the fi replace. Ensure that
the spacer maintains the required clearance to combustibles.
Once the vent pipe / liner is installed in its fi nal position, apply
high temperature sealant W573-0002 (not supplied) between
the pipe / liner and the fi restop spacer.
FIGURE 16
Summary of Contents for Madison GD80NT
Page 1: ...1 W415 0695 05 12 08 10 00 W415 0695 05 12 08...
Page 4: ...4 W415 0695 05 12 08 FIGURE 1 INSTALLATION OVERVIEW FIREPLACE DIMENSIONS FIGURE 2...
Page 12: ...12 W415 0695 05 12 08 MINIMUM AIR TERMINAL LOCATION CLEARANCES GD 301 FIGURE 13...
Page 35: ...35 W415 0695 05 12 08...
Page 39: ...39 W415 0695 05 12 08 NOTES...
Page 40: ...40 W415 0695 05 12 08 NOTES...