background image

6

W415-0210 / R / 02.27.08

** 

When a vertical rise is used as part of the venting confi guration, a 0" rise per foot is acceptable.

For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using a red high 
temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake vent pipe joints of all 
other approved vent systems except for the exhaust vent pipe connection to the fi replace fl ue collar which must be sealed 
using the black high temperature sealant Mill Pac.

When using Wolf Steel venting components, use only approved Wolf Steel rigid / fl exible components with the following 
termination kits: WALL TERMINAL KIT 

GD222

, or 1/12 TO 7/12 PITCH ROOF TERMINAL KIT

 GD110

, 8/12 TO 12/12 ROOF 

TERMINAL KIT

 GD111

, FLAT ROOF TERMINAL KIT

 GD112 

or PERISCOPE KIT

 GD201 

(for wall penetration below grade). 

With fl exible venting, in conjunction with the various terminations, use either the 5 foot vent kit 

GD220

 or the 10 foot vent 

kit 

GD330

For optimum 

fl

 ame appearance and 

fi

 replace performance, keep the vent length and number of elbows to a 

minimum.   
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that 
it is unobstructed and undamaged.
Wolf Steel rigid and 

fl

 exible venting systems must not be combined. 

Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp and American Metal Amerivent venting systems must not be 
combined.

These vent kits allow for either horizontal or vertical venting of the fi replace. The maximum allowable horizontal run is 20 
feet. 

The maximum allowable vertical vent length is 40 feet. The maximum number of 4" vent connections is two horizontally or 
three vertically (excluding the fi replace and the air terminal connections) when using fl exible vent pipe.

For optimum performance, it is recommended that all horizontal runs have a 1" rise per foot.

GD36 REQUIRED RISE ON HORIZONTAL VENTING

BGD36 REQUIRED RISE ON HORIZONTAL VENTING

REAR VENT

RIGID VENTING

1" / FT **

REAR VENT

RIGID VENTING

0" / FT

FLEXIBLE VENTING

1" / FT **

FLEXIBLE VENTING

0" / FT

TOP VENT

RIGID VENTING

0" / FT

TOP VENT

RIGID VENTING

0" / FT

FLEXIBLE VENTING

0" / FT

FLEXIBLE VENTING

0" / FT

CORNER VENT

RIGID VENTING

6"

CORNER VENT

RIGID VENTING

0"

FLEXIBLE VENTING

6"

FLEXIBLE VENTING

6"

VENT INSTALLATIONS

GD36

BGD36

HORIZONTAL VENT SECTIONS

A minimum clearance of 1" at the bottom and sides and 2" at 
the top of the vent pipe on all horizontal runs to combustibles 

is required.  Use fi restop spacer W010-1777 (supplied). 

HORIZONTAL VENT SECTIONS

A minimum clearance of 1" at the bottom and sides and 2" at 
the top of the vent pipe on all horizontal runs to combustibles 

is required.  Use fi restop spacer W010-1774 (supplied).

VERTICAL VENT SECTIONS

A minimum of 1" all around the vent pipe on all vertical runs 
to combustibles is required except for clearances in fi replace 
enclosures.  See "Minimum Enclosure Clearances" section.  

Use fi restop spacer W500-0096 (not supplied).

VERTICAL VENT SECTIONS

A minimum of 1" all around the vent pipe on all vertical runs 
to combustibles is required except for clearances in fi replace 
enclosures.  See "Minimum Enclosure Clearances" section.  

Use fi restop spacer W500-0096 (not supplied).

For safe and proper operation of the 

fi

 replace follow the venting instructions exactly.

Deviation from the minimum or maximum vertical vent length can create diffi culty in burner start-up and/or 
carboning.

Under extreme vent con

fi

 gurations, allow several minutes (5-15) for the 

fl

 ame to stabilize after ignition. 

Vent lengths that pass through unheated spaces (attics, garages, crawl spaces) should be insulated with the 
insulation wrapped in a protective sleeve to minimize condensation.

Provide a means for visually checking the vent connection to the fi replace after the fi replace is installed.

Use a fi restop, vent pipe shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.

FOR SPECIFIC VENTING PARAMETERS, REFER TO PAGES 10-15

NorthlineExpress.com

http://www.northlineexpress.com

Toll-Free 1-866-667-8454

Summary of Contents for GD36NTR

Page 1: ...other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighb...

Page 2: ...ace is out the glass and or screen will remain hot for an extended period of time Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfac...

Page 3: ...3 W415 0210 R 02 27 08 NorthlineExpress com http www northlineexpress com Toll Free 1 866 667 8454...

Page 4: ...le or other combustible material other than wood flooring the fireplace shall be installed on a metal or wood panel extending the full width and depth If the optional fan or blower is installed the ju...

Page 5: ...r the first 10 hours of operation with a recommended gas fireplace glass cleaner Thereafter clean as required DO NOT CLEAN GLASS WHEN HOT If the glass is not kept clean permanent discolouration and or...

Page 6: ...RISE ON HORIZONTAL VENTING BGD36 REQUIRED RISE ON HORIZONTAL VENTING REAR VENT RIGID VENTING 1 FT REAR VENT RIGID VENTING 0 FT FLEXIBLE VENTING 1 FT FLEXIBLE VENTING 0 FT TOP VENT RIGID VENTING 0 FT...

Page 7: ...4a 20 MAXIMUM FIGURE 4b BGD36 ONLY WITH RIGID ONLY 6 RISE MINIMUM FIGURE 2c FIGURE 2d GD36 See chart on Page 6 20 MAXIMUM 241 4 MINIMUM PLUS RISE 24 MAXIMUM 24 MINIMUM 57 MINIMUM PLUS RISE 33 BGD36 F...

Page 8: ...8 W415 0210 R 02 27 08 FIGURE 5 MINIMUM AIR TERMINAL LOCATION CLEARANCES NorthlineExpress com http www northlineexpress com Toll Free 1 866 667 8454...

Page 9: ...to or greater t h a n t h e horizontal run Horizontal run verti cal rise to m a x i m u m of 40 feet Vertical rise is equal to or greater t h a n t h e horizontal run Horizontal run verti cal rise to...

Page 10: ...than less than equal to or less than HT total of both horizontal vent lengths HR and offsets HO in feet HR combined horizontal vent lengths in feet HO offset factor 03 total degrees of offset 90 in f...

Page 11: ...1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 four 90 elbows 90 03 360 90 8 1 ft HT HR HO 5 5 8 1 13 6 ft HT VT 13 6 5 5 19 1 ft Formula 1 HT 4 2 VT 4 2 VT 4 2 x 5 5 23 1 ft 13 6 23 1 Formula 2 HT VT 24 75 feet 1...

Page 12: ...0 03 90 90 90 90 90 8 1 ft HT HR HO 6 5 8 1 14 6 ft HT VT 14 6 15 29 6 ft Formula 1 HT VT 14 6 15 Formula 2 HT VT 40 feet 29 6 40 Since both formulas are met this vent configuration is acceptable FIGU...

Page 13: ...4 75 Since both formulas are met this vent configuration is acceptable FIGURE 14 For vent configurations requiring more than two 90 elbows the following formulas apply Formula 1 HT 3 5VT Formula 2 HT...

Page 14: ...this vent configuration is acceptable Simple venting configurations FIGURE 15 For vent configurations requiring more than zero 90 elbow top exit or one 90 elbow rear exit the following formulas apply...

Page 15: ...t this vent configuration is unacceptable and a new fireplace location or vent configuration will need to be established to satisfy both formulas Example 8 V1 1 5 ft V2 5 ft VT V1 V2 1 5 5 6 5 ft H1 1...

Page 16: ...through the heat shield and out through the retaining ring Secure the assembly to the rear and top of the unit using 4 8 x Hex Head Wildrill screws supplied Do not overtighten The gasket needs only to...

Page 17: ...may need to be repositioned to ensure a rigid assembly is maintained Figure 25 2 Apply a bead of caulking not supplied to the inside surface of the firestop flange and secure the assembly to the wall...

Page 18: ...nt any materials such as insulation from filling up the 1 air space around the pipe VERTICAL INSTALLATION FIGURE 29 FIGURE 28 FIRESTOP UNDERSIDE OF JOIST 9 1 2 9 1 2 SHIELD FIGURE 30 VENT PIPE COLLAR...

Page 19: ...IBLE VENT PIPE SCREWS 10x2 VENT PIPE 2 OVERLAP 7 FLEXIBLE 4 FLEXIBLE VENT PIPE CAULKING ATTENTIO N C HAUD CAUTIO N HOT HIGH TEMPERATURE SEALANT FIGURE 32 1 Stretch the 4 flexible vent pipe to the requ...

Page 20: ...ing material Figure 36 6 Aligning the seams of the terminal and air terminal connector place the terminal over the air terminal connector making sure the vent pipe goes into the hole in the terminal S...

Page 21: ...this case the venting is to be adequately supported using either an alternate method suitable to the authority having jurisdiction or the optional roof support 3 Apply high temperature sealant W573 0...

Page 22: ...tes or the Mobile Home Standard CAN CSA Z240 MH Series in Canada This appliance is only for use with the type s of gas indicated on the rating plate A conversion kit is supplied with the mobile home a...

Page 23: ...material brick stone or ceramic tile may protrude in these areas FIGURE 45 Bend and secure the top stand off s as illustrated A B C STAND OFF ASSEMBLY MINIMUM FRAMING DIMENSIONS FIGURE 44 a d Combust...

Page 24: ...ace areas of the fireplace Non combustible material brick stone or ceramic tile may protrude in these areas MINIMUM FRAMING DIMENSIONS FIGURE 46 a d Combustion protrusions such as mantels and shelves...

Page 25: ...ires a minimum enclosure height of 483 8 Fortemperaturerequirements theenclosurespace around and above the fireplace must be left unobstructed The fireplace requires a minimum enclosure height of 63 F...

Page 26: ...on of the nailing tab you must first determine the thickness of your finishing material i e drywall This will determine the dimension from the front edge of the corner post to the nailing tab Once the...

Page 27: ...t LOWER LOUVRES Insert the hinge clips into the slots located at the bottom left and right corners of the unit To remove the louvres pull the back tabs of the clips forward while pushing the louvre as...

Page 28: ...of the bag should not be used Sprinkle vermiculite around the charcoal embers Note Both charcoal embers and vermiculite are not to be placed on the burner Tear the embers into pieces and place along...

Page 29: ...touch the fireplace base or the firebox FIGURE 59 FIGURE 60 Attach the connectors from the black and white wires to the thermodisc and secure the thermodisc bracket to the securing stud at the bottom...

Page 30: ...on box at the bottom left of the unit using the lock washer and wing nut Ensure that the thermodisc touches the firebox wall When installed ensure that any excess wire is contained pre venting it from...

Page 31: ...knob while lighting the pilot with the push button igniter Keep knob depressed for one minute then release If pilot does not continue to burn repeat steps 3 through 5 7 With pilot lit depress and tur...

Page 32: ...THERMOCOUPLE THERMOPILE Adjust the pilot screw to provide properly sized flame Turn in a clockwise direction to reduce the gas flow FIGURE 70 VENTURI ORIFICE AIR SHUTTER OPENING FIGURE 72 FIGURE 69 P...

Page 33: ...PLATE KIT 65 VS47KT VENT SLEEVE 66 W573 0002 HIGH TEMPERATURE SEALANT 67 W573 0007 HIGH TEMPERATURE SEALANT PART NO DESCRIPTION 1 W225 0058 BLACK DOOR FRAME 2 W357 0001 PIEZO IGNITER 3 W680 0004 THERM...

Page 34: ...0 1774 FIRESTOP SPACER BGD36 ACCESSORIES 76 W175 0159 CONVERSION KIT NG TO LP 77 W175 0164 CONVERSION KIT LP TO NG GD36 COMPONENTS 68 W455 0017 42 NATURAL GAS ORIFICE 68 W455 0003 54 PROPANE GAS ORIFI...

Page 35: ...ot burner check that the manual valve is turned on check the pilot orifice for blockage replace the valve call the gas distributor Pilot goes out when the gas knob is re leased The gas valve has an in...

Page 36: ...nt or other obstructions Pilot goes out while standing Main burner is in OFF position Gas piping is undersized turn on all gas appliances and see if pilot flame flutters diminishes or extinguishes esp...

Reviews: