THIS GAS FIREPLACE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER 

to conform with local 

codes. Installation practices vary from region to region and  it is important to know the specifi cs that apply to your area, 
for example: in Massachusetts State:

• The fi replace damper must be removed or welded in the open position prior to installation of a fi replace insert or gas log.
• A carbon monoxide detector is required in all rooms containing gas fi red appliances
• The appliance off valve must be a “T” handle gas cock.
• The fl exible connector must not be longer than 36".
• The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product.
• WARNING: This product must be installed by a licensed plumber or gas fi tter when installed within the commonwealth of 
Massachusetts.

In absence of local codes, install to the current National Fuel Gas Code, ANSI Z223.1, or the current CAN/CGA B149, Installation 
Codes. Mobile home installation must conform with local codes or in the absence of  local codes, install to the current standard 
for gas equipped mobile housing CAN/CSA ZA240 MH Series in Canada or the Manufactured Home Construction and Safety 
Standard, Title 24 CFR, Part 3280, or the Fire Safety Criteria for Manufactured Home Installations, Sites and Communities 
Standard ANSI/NFPA 501A in the United States.

The fi replace and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure 
testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). The fi replace must be isolated from the gas supply 
piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping  system at test 
pressures equal to or less than 1/2 psig (3.5 kPa).

When the fi replace is installed directly on carpeting, vinyl tile or other combustible 
material other than wood fl ooring, the fi replace shall be installed on a metal or 
wood panel extending the full width and depth.

If the optional fan or blower is installed, the junction box must be electrically 
connected and grounded in accordance with local codes. In the absence of local 
codes, use the current CSA C22.1 CANADIAN ELECTRICAL CODE in Canada 
or the ANSI/NFPA 70 NATIONAL ELECTRICAL CODE in the United States. 

GENERAL INSTRUCTIONS

GENERAL INFORMATION

FOR YOUR SATISFACTION, THIS FIREPLACE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND QUALITY!  

This  fi replace is approved for bathroom, bedroom and bed-sitting room installations and is suitable for mobile home 
installation.

No external electricity (110 volts or 24 volts) is required for the gas system operation.

  

Expansion / contraction noises during heating up and cooling down cycles are normal and are to be expected.
Provide adequate ventilation air. Provide adequate accessibility clearance for servicing and operating the 

fi

 replace. 

Never obstruct the front opening of the 

fi

 replace.

Objects placed in front of the 

fi

 replace must be kept a minimum of 48" away from the front face of the unit.

Use only Napoleon® accessories designed for and listed with the model.

GD36 RATES AND EFFICIENCIES

BGD36 RATES AND EFFICIENCIES

NG

LP

NG

LP

ALTITUDE (FT)

0 - 4,500

0 - 4,500

ALTITUDE (FT)

0 - 4,500

0 - 4,500

MAX. INPUT (BTU/HR)

26,000

26,000

MAX. INPUT (BTU/HR)

18,000

17,000

MAX. OUTPUT (BTU/HR)

22,360

22,880

MAX. OUTPUT (BTU/HR)

11,500

10,900

EFFICIENCY (w/ the fan on)

86%

88%

EFFICIENCY (w/ the fan on)

64%

64%

A.F.U.E.

64%

65%

A.F.U.E.

53%

53%

MINIMUM INLET GAS SUPPLY 
PRESSURE

4.5" WATER 

COLUMN

11" WATER

COLUMN

MINIMUM INLET GAS SUPPLY
PRESSURE

4.5" WATER

COLUMN

11" WATER

COLUMN

MAXIMUM INLET GAS SUPPLY 
PRESSURE

7" WATER

COLUMN

13" WATER

COLUMN

MAXIMUM INLET GAS SUPPLY 
PRESSURE

7" WATER

COLUMN

13" WATER

COLUMN

MANIFOLD PRESSURE 
(under fl ow conditions)

3.5" WATER

COLUMN

10" WATER

COLUMN

MANIFOLD PRESSURE 
(under fl ow conditions)

3.5" WATER

COLUMN

10" WATER

COLUMN

NorthlineExpress.com

http://www.northlineexpress.com

Toll-Free 1-866-667-8454

Summary of Contents for GD36NTR

Page 1: ...other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighb...

Page 2: ...ace is out the glass and or screen will remain hot for an extended period of time Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfac...

Page 3: ...3 W415 0210 R 02 27 08 NorthlineExpress com http www northlineexpress com Toll Free 1 866 667 8454...

Page 4: ...le or other combustible material other than wood flooring the fireplace shall be installed on a metal or wood panel extending the full width and depth If the optional fan or blower is installed the ju...

Page 5: ...r the first 10 hours of operation with a recommended gas fireplace glass cleaner Thereafter clean as required DO NOT CLEAN GLASS WHEN HOT If the glass is not kept clean permanent discolouration and or...

Page 6: ...RISE ON HORIZONTAL VENTING BGD36 REQUIRED RISE ON HORIZONTAL VENTING REAR VENT RIGID VENTING 1 FT REAR VENT RIGID VENTING 0 FT FLEXIBLE VENTING 1 FT FLEXIBLE VENTING 0 FT TOP VENT RIGID VENTING 0 FT...

Page 7: ...4a 20 MAXIMUM FIGURE 4b BGD36 ONLY WITH RIGID ONLY 6 RISE MINIMUM FIGURE 2c FIGURE 2d GD36 See chart on Page 6 20 MAXIMUM 241 4 MINIMUM PLUS RISE 24 MAXIMUM 24 MINIMUM 57 MINIMUM PLUS RISE 33 BGD36 F...

Page 8: ...8 W415 0210 R 02 27 08 FIGURE 5 MINIMUM AIR TERMINAL LOCATION CLEARANCES NorthlineExpress com http www northlineexpress com Toll Free 1 866 667 8454...

Page 9: ...to or greater t h a n t h e horizontal run Horizontal run verti cal rise to m a x i m u m of 40 feet Vertical rise is equal to or greater t h a n t h e horizontal run Horizontal run verti cal rise to...

Page 10: ...than less than equal to or less than HT total of both horizontal vent lengths HR and offsets HO in feet HR combined horizontal vent lengths in feet HO offset factor 03 total degrees of offset 90 in f...

Page 11: ...1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 four 90 elbows 90 03 360 90 8 1 ft HT HR HO 5 5 8 1 13 6 ft HT VT 13 6 5 5 19 1 ft Formula 1 HT 4 2 VT 4 2 VT 4 2 x 5 5 23 1 ft 13 6 23 1 Formula 2 HT VT 24 75 feet 1...

Page 12: ...0 03 90 90 90 90 90 8 1 ft HT HR HO 6 5 8 1 14 6 ft HT VT 14 6 15 29 6 ft Formula 1 HT VT 14 6 15 Formula 2 HT VT 40 feet 29 6 40 Since both formulas are met this vent configuration is acceptable FIGU...

Page 13: ...4 75 Since both formulas are met this vent configuration is acceptable FIGURE 14 For vent configurations requiring more than two 90 elbows the following formulas apply Formula 1 HT 3 5VT Formula 2 HT...

Page 14: ...this vent configuration is acceptable Simple venting configurations FIGURE 15 For vent configurations requiring more than zero 90 elbow top exit or one 90 elbow rear exit the following formulas apply...

Page 15: ...t this vent configuration is unacceptable and a new fireplace location or vent configuration will need to be established to satisfy both formulas Example 8 V1 1 5 ft V2 5 ft VT V1 V2 1 5 5 6 5 ft H1 1...

Page 16: ...through the heat shield and out through the retaining ring Secure the assembly to the rear and top of the unit using 4 8 x Hex Head Wildrill screws supplied Do not overtighten The gasket needs only to...

Page 17: ...may need to be repositioned to ensure a rigid assembly is maintained Figure 25 2 Apply a bead of caulking not supplied to the inside surface of the firestop flange and secure the assembly to the wall...

Page 18: ...nt any materials such as insulation from filling up the 1 air space around the pipe VERTICAL INSTALLATION FIGURE 29 FIGURE 28 FIRESTOP UNDERSIDE OF JOIST 9 1 2 9 1 2 SHIELD FIGURE 30 VENT PIPE COLLAR...

Page 19: ...IBLE VENT PIPE SCREWS 10x2 VENT PIPE 2 OVERLAP 7 FLEXIBLE 4 FLEXIBLE VENT PIPE CAULKING ATTENTIO N C HAUD CAUTIO N HOT HIGH TEMPERATURE SEALANT FIGURE 32 1 Stretch the 4 flexible vent pipe to the requ...

Page 20: ...ing material Figure 36 6 Aligning the seams of the terminal and air terminal connector place the terminal over the air terminal connector making sure the vent pipe goes into the hole in the terminal S...

Page 21: ...this case the venting is to be adequately supported using either an alternate method suitable to the authority having jurisdiction or the optional roof support 3 Apply high temperature sealant W573 0...

Page 22: ...tes or the Mobile Home Standard CAN CSA Z240 MH Series in Canada This appliance is only for use with the type s of gas indicated on the rating plate A conversion kit is supplied with the mobile home a...

Page 23: ...material brick stone or ceramic tile may protrude in these areas FIGURE 45 Bend and secure the top stand off s as illustrated A B C STAND OFF ASSEMBLY MINIMUM FRAMING DIMENSIONS FIGURE 44 a d Combust...

Page 24: ...ace areas of the fireplace Non combustible material brick stone or ceramic tile may protrude in these areas MINIMUM FRAMING DIMENSIONS FIGURE 46 a d Combustion protrusions such as mantels and shelves...

Page 25: ...ires a minimum enclosure height of 483 8 Fortemperaturerequirements theenclosurespace around and above the fireplace must be left unobstructed The fireplace requires a minimum enclosure height of 63 F...

Page 26: ...on of the nailing tab you must first determine the thickness of your finishing material i e drywall This will determine the dimension from the front edge of the corner post to the nailing tab Once the...

Page 27: ...t LOWER LOUVRES Insert the hinge clips into the slots located at the bottom left and right corners of the unit To remove the louvres pull the back tabs of the clips forward while pushing the louvre as...

Page 28: ...of the bag should not be used Sprinkle vermiculite around the charcoal embers Note Both charcoal embers and vermiculite are not to be placed on the burner Tear the embers into pieces and place along...

Page 29: ...touch the fireplace base or the firebox FIGURE 59 FIGURE 60 Attach the connectors from the black and white wires to the thermodisc and secure the thermodisc bracket to the securing stud at the bottom...

Page 30: ...on box at the bottom left of the unit using the lock washer and wing nut Ensure that the thermodisc touches the firebox wall When installed ensure that any excess wire is contained pre venting it from...

Page 31: ...knob while lighting the pilot with the push button igniter Keep knob depressed for one minute then release If pilot does not continue to burn repeat steps 3 through 5 7 With pilot lit depress and tur...

Page 32: ...THERMOCOUPLE THERMOPILE Adjust the pilot screw to provide properly sized flame Turn in a clockwise direction to reduce the gas flow FIGURE 70 VENTURI ORIFICE AIR SHUTTER OPENING FIGURE 72 FIGURE 69 P...

Page 33: ...PLATE KIT 65 VS47KT VENT SLEEVE 66 W573 0002 HIGH TEMPERATURE SEALANT 67 W573 0007 HIGH TEMPERATURE SEALANT PART NO DESCRIPTION 1 W225 0058 BLACK DOOR FRAME 2 W357 0001 PIEZO IGNITER 3 W680 0004 THERM...

Page 34: ...0 1774 FIRESTOP SPACER BGD36 ACCESSORIES 76 W175 0159 CONVERSION KIT NG TO LP 77 W175 0164 CONVERSION KIT LP TO NG GD36 COMPONENTS 68 W455 0017 42 NATURAL GAS ORIFICE 68 W455 0003 54 PROPANE GAS ORIFI...

Page 35: ...ot burner check that the manual valve is turned on check the pilot orifice for blockage replace the valve call the gas distributor Pilot goes out when the gas knob is re leased The gas valve has an in...

Page 36: ...nt or other obstructions Pilot goes out while standing Main burner is in OFF position Gas piping is undersized turn on all gas appliances and see if pilot flame flutters diminishes or extinguishes esp...

Reviews: