W415-1789 / C / 01.29.19
EN
6
installation planning
!
WARNING
• Do NOT cover or place any items in the
Dynamic Heat Control™
air outlet. Failure to comply with these
instructions could create a fire hazard.
• Ensure a
ir flow within the air passage is not restricted in any way with the exception of an approved appliance
vent system or the
DHC™ Plus
system.
• The DHC™ Plus system draws air from the appliance enclosure and should be mounted in the
enclosure above the appliance. NEVER make a direct connection to the appliance itself.
3”
*** Restrictions also apply to see-thru when one or more recess is used. See your appliance manual for details.
Air flow in the hatched areas
must
not be restricted in any way with the exception of an approved appliance vent
system or the
DHC™ Plus
system. No other items are allowed in this area.
See your appliance manual for more information about clearance to combusible materials. No combustible materi-
als allowed in the hatched areas or the space between studs (i.e. no wiring, conduits, electrical bores, combus-
tible framing members, etc.).
1.6
placement in enclosure
important:
** DHC™ Plus
collar plate assembly
must be installed above the appliance vent shield (not illustrated) (minimum
33” (83cm) from the top of the appliance).
enclosure top and/or ceiling
No materials of any type permitted in this area with the exception of an approved appliance vent system or
the
DHC™ Plus
system.
*
Dynamic Heat
Control™
air
outlet opening
Stud
Stand-Off
Upper
Frame
Deflector
Single-Sided
Single-Sided
(Recessed)***
See-thru
Single-Sided
(Exterior Recess)
Minimum
33” (83cm)
above
appliance
**
Minimum
33” (83cm)
above
appliance
**
*
*
*
*
Recommended
DHC™ Plus
collar plate assembly installation zone -
within the top 12” (30.5cm) of the
appliance enclosure.