EN
W415-3095 / 07.09.21
13
venting requirements
2.2 special vent installations
2.2.1 periscope termination
Use the periscope kit to locate the air termination above grade. The periscope must be installed so that when
fi nal grading is completed, the bottom air slot is located a minimum 12” (305mm) above grade. The maximum
allowable vent length (including both rise and run) is 10’ (3m) for a fi replace and 8’ (2m) for a stove. An insulation
sleeve is illustrated in the top vent image below, use only when supplied with the appliance.
(The insulation sleeve is not required with a stove appliance)
8.1
TOP VENT
REAR VENT
30”
MINIMUM
12”
MINIMUM
TOP EXIT INSTALLATION
REAR EXIT INSTALLATION
30”
MINIMUM
12”
MINIMUM
MAXIMUM 10FT VENT LENGTH
6” (152mm)
RISE MINIMUM
20” (50.8cm)
MAXIMUM
20” (50.8cm)
MAXIMUM
6” (152mm)
RISE MINIMUM
30”
MINIMUM
12”
MINIMUM
TOP EXIT INSTALLATION
REAR EXIT INSTALLATION
30”
MINIMUM
12”
MINIMUM
MAXIMUM 10FT VENT LENGTH
6” (152mm)
RISE MINIMUM
20” (50.8cm)
MAXIMUM
20” (50.8cm)
MAXIMUM
6” (152mm)
RISE MINIMUM
2.2.2 corner termination
12" (30.5cm)
minimum
to grade
12" (30.5cm)
minimum
to grade
30" (76.2cm)
minimum
30" (76.2cm)
minimum
34 5/8"
(87.9cm)
The maximum vent length for a corner installation is 20" (50.8cm) of horizontal run, in addition to the 45°
offset. Using rigid venting, a 0" rise is acceptable. Using flexible venting, a 6"(152mm) rise is required. See
illustrations below.
FLEXIBLE VENTING
RIGID VENTING