BASIC ZONE CONFIGURATION
The basic zone configuration for the GEM-P3200 is 8 zones. Connect as shown above to terminals 16-27. Normally
Closed (N.C.) devices may be wired in series or Normally Open (N.O.) devices may be wired in parallel. Use the 2.2K
Ohm end-of-line (E.O.L.) resistor in each zone, if selected in programming (refer to the GEM-P3200 Programming In-
structions). Zones 1-8 can be selected for a “Fast Loop Response (10ms or 50 ms)” or a “Normal Loop Response (750
ms)”. Other zone options include Entry/Exit, Interior, 24 Hour Protection, Trouble, Fire, Instant, Chime, Area Selection
and Relay Output selection.
RESET OUTPUT
Reset Output can be activated depending on the programming options selected (see GEM-
P3200 Programming Instructions). Connect the device controlled by the programmable output
between terminal 15 (+) and terminal 14 (-).
15
RESET
OUTPUT
EXPANDED ZONE CONFIGURATION
The GEM-P3200 Control Panel may be expanded up to 48 zones. This may be accomplished by adding 40 zones to the
basic 8 zone configuration. Hardwired zone expanders include: GEM-EZM4 (4 additonal zones per module), GEM-EZM8
(8 additional zones per module) and GEM-RP1CAe2 Keypad (4 additional zones per keypad). Wireless zone expanders
include: GEM-RECV8 (8 additional zones per receiver), GEM-RECV16 (16 additional zones per receiver) and GEM-
RECV96 (88 additional zones per receiver). Wireless transmitters include: GEM-TRANS2, GEM-KEYF, GEM-SMK, GEM-
PIR, GEM-DT and GEM-GB.
Additional Zones are numbered 9-48.
R
C OMPUTERIZED SEC URITY SYSTEM
GEMINI
AR
M E
D ST
A TU
S
SYSTEM ARMED
01/01/97 12:00AM
1 2
4
3
5 6
7 8 9 0
A
B
C
D
E
F
G
N EXT/YE S
PRIO R/NO
A REA
GEM-RP1CAe2
(2 LINE LCD KEYPAD)
WIRIN
G
CONNECTIO
N
S
Summary of Contents for Gemini GEM-P3200
Page 58: ...X GEM P3200 Installation Instructions L NAPCO Security Systems WI817F 10 05 Page 58 NOTES...
Page 66: ...X GEM P3200 Installation Instructions L NAPCO Security Systems WI817F 10 05 Page 66 Notes...
Page 67: ...L NAPCO Security Systems X GEM P3200 Installation Instructions WI817F 10 05 Page 67 Notes...