NAPCO GEM-P800 Installation Instructions Manual Download Page 14

WI850D  GEM-P800 Installation Instructions 

14 

does not receive any signal (either a trip or a 
status) from a transmitter in the time speci-
fied, a system trouble 'RF Supervisory Fail-
ure' will be indicated at the keypad. Timer is 
programmable from 1-26 hours; 0 means 
NO supervision. 

Note:  

Wireless Supervi-

sory Timer must be set to 10 hours. 

 

[17] Wireless Smoke Supervisory Timer 

A smoke detector will send a transmission 
every time it is tripped; when there is NO 
activity, the smoke detector sends a supervi-
sory transmission about once an hour.  If the 
receiver does not receive a signal (either a 
trip or a status) from a transmitter in the time 
specified, a system trouble 'RF Supervisory 
Failure' will be indicated at the keypad. The 
Supervisory timer is programmable from 1-8 
hours; 0 means NO supervision.  

 

[18] Test Timer Offset  

Enter the time, in hours, that a Test Timer  
will be reported after Dealer Mode has been 
exited.  With the default value of 12,  the test 
timer will be sent 12 hours after exiting 
Dealer Mode.  The test timer can also be 
offset using NAPCO PCD3000 Downloading 
Software. On power up the test timer is sent 
immediately.  Follow the commands below 
to offset the test timer using Quickloader 
Software: 

 

From the Status Screen  
Press 

q

 

Select 

M

iscellaneous Control 

Select 

T

est Timer Offset 

Enter  
New Test Timer Offset: 12 hours 
Enter 

u

 to advance the test timer due in 

time by 12 hours. 

System Features 

 

[20] Keypad Features 1 

(1)    Enable Keypad Fire 

(

7G

Additional Programming required: 
Select reporting to Telco 1 [36-1] or Telco 3 
[56-1]. 

(2)    Enable Keypad AUX

 (

8G

Additional Programming required: 
Select reporting to Telco 1 [36-2] or Telco 3 
[56-2]. 
 

(3)    Enable Keypad Panic

 (

9G

)  

Additional Programming required: 
Select reporting to Telco 1 [36-3] or Telco 3 
[56-3]. 

(4)    Enable  Ambush  -

 If enabled, the 8th 

User Code will send an Ambush report 
when entered to disarm the system.   
Additional Programming required: 
Program User 8 Arm/Disarm Code.   
Select reporting to Telco 1 [36-2] or Telco 3 
[56-2]. 

UL Installations:

  If Keypad Fire [20-1] is 

enabled, the keypad must be mounted 
within (3) three feet from the Control Panel. 

 
[21] Keypad Features 2 

(1)    Audible  Panic

 - Keypad Panic will not 

turn the Bell on unless this option is pro-
grammed. 

(2)    Exit/Entry  with  Urgency

 - select to 

give an audible indication of Exit and Entry 
times.  During the last 10 seconds of entry 
and exit time, the keypad sounds a distinct 
sound to indicate the premises must be left 
or the panel must be disarmed. 

(3)    Display Bypassed (Armed)

 - Select to 

display bypassed zones while the panel is 
armed. 

(4)    Disable Code Entry Beeps - 

Program 

to disable keypad beeping on valid code and 
function entries. 
 

[22] Miscellaneous Features 1 

(1)    Abort  Delay

 - Program to allow a 15 

second Delay (except 

24 Hour Zones

) after 

a zone trip before reporting.  Disarm the 
system within 15 seconds to prevent report-
ing. 

(2)     Easy 

Exit/Easy 

Arm

- Enables 

A0

 command.  While the system is 

armed, entering this command allows 3 min-
utes to Exit through 

Exit/Entry 

and 

Exit/Entry 

Follower Zones

.  Enabling this option also 

enables Easy Arm,  press the 

D

 key to arm 

the system. 

(3)    Swinger  Shutdown

 - Automatically 

disables armed zones with excessive alarm/
restores (swingers).  Non-24-Hour Protec-
tion zones: allows only 3 alarms and 2 re-
stores per zone per arming before the zone 
is disabled. 

Summary of Contents for GEM-P800

Page 1: ...WI850E 04 10 NAPCO 2010 GEM P800 Control Panel Communicator Installation Instructions ...

Page 2: ... Wireless Ready Bell Supervision Line Cut Detection Answering Machine Override Second Call 50 Event Log Communicator 2 Telephone Numbers Backup Reporting Pager Format Point ID Format Individually Report 8 Users Opening after Alarm Report Cancel Code Conditional Closing Report For Technical Assistance Contact the NAPCO Toll Free Helpline 800 645 9440 NAPCO Security Technologies Inc 333 Bayview Aven...

Page 3: ...7 AH BATTERY minimal requirement Transformer and Battery Required Transformer NAPCO TRF12 OR BASLER 16 5 VAC 20VA Required Battery 12V 4 AH or 7 AH Rechargeable Change Battery every 5 years or as required Maximum Charging Current 165 mA Maximum Input Current 2 58 A Loop Characteristics Loop Voltage 5 Volts Loop Current Zones 1 2 3 0 9 mA 2 2 K Zones 4 5 6 0 5 mA 3 9 K Loop Resistance 100Ω per zone...

Page 4: ...iver Window Door Transmitter Keyfob Transmitter Wireless Smoke Detector Wireless PIR Wireless Dual Technology Sensor Wireless Glass Break Detector Relay Board Audio Verification Module Downloading Software for IBM PC Compatibles Software with Interface for IBM PC Compatibles Includes PCL2000A Local Download cable Local Download cable GEM RECV XP8 GEM TRANS2 GEM KEYF GEM SMK GEM PIR GEM DT GEM GB R...

Page 5: ...ing PCPreset For Site Initiated Downloaded see Auto Download ID Number 93 Local Downloading Wire as shown in Figure 1 Use the power up or A6 method of establishing a connection The power up method is recommended if the panel is at tempting to report Remote Downloading Wire as shown in Figure 2 The panel can be remotely download uploaded using any one of the following methods 1 The A6 method 2 Call...

Page 6: ...etectors are recommended in kitchens attics and garages due to conditions that may result in false alarms and improper operation Refer to NFPA Standard 74 National Fire Pro tection Association Batterymarch Park Quincy MA 02269 for additional information including proper mounting methods Wiring Terminal Block Wire Range 14 22 AWG Grounding the Panel Connect the control panel EARTH GROUND screw thro...

Page 7: ...mum load of 50 mA Keypad Operation Keypad zone LED s indicate zone status ARMED STATUS and H SYSTEM LED s pro vide system status The keypad sounder pro vides feedback beeps for correct and incorrect entries Keypad Sounder 3 QUICK BEEPS Panel Armed System ON Chime ON Fault Find Mode ON Keypad Sounder ON Zone Bypassed 6 QUICK BEEPS Panel Disarmed System OFF Chime OFF Fault Find Mode OFF Keypad Sound...

Page 8: ...Zones can be bypassed when the M or N keys on the Keyfob have been pro grammed for Interior 81 84 Zones pro grammed as Home Away with Delay Zones can be armed regardless of the state of the Exit Entry Zones when the M or N keys on the Keyfob have been programmed for Full Set 81 84 To arm the system with all zones protected press the K key Press and hold the M or N key for 1 5s to fully set the sys...

Page 9: ...nes From the Keypad Press BC to return protection to Home Away with Delay Zones that have been automatically bypassed Three min utes are allowed to walk through Exit Entry and Exit Entry Follower Zones Using A Keyfob GEM KF All zones in the system can be armed re gardless of the state of the Exit Entry Zone when arming with a Keyfob and using an AUX key programmed as Full Set Press K and press and...

Page 10: ...d you can test your new User Code IMPORTANT You MUST exit User Program Mode before testing your new User Code GEM P800 Commands User Commands A1 Bell Test Enter this command to turn on the Bell keypad sounder and keypad LED s for 2 seconds The battery is tested during a Bell Test and auto matically every 24 hours to ensure proper bat tery operation under load The Alarm output requires a battery in...

Page 11: ... zones are faulted and for 1 second when zones are restored Wireless Operation Signal Strength While in Fault Find mode the keypad will provide an audible Table 6 and visual Figure 5 indi cation of each transmitter s signal strength The signal strength metering is based on a scale of 4 to 10 with 4 being marginal and 10 being excel lent The keypad will beep out a number from 1 4 corresponding to t...

Page 12: ...lows the user time to enter and disarm Allows exit after the panel is armed without setting off an immediate alarm and allows entry only if an Exit Entry Zone 00 has been violated first Zones of this type have a three 3 minute power up delay and do not display or cause an alarm if faulted when the system powers up Pressing the C key cancels the 3 minute timer Group Bypassing Zones programmed as Ex...

Page 13: ...ay be programmed for up to 255 seconds 4 minutes a value of 0 defaults to 60 seconds 11 Entry Delay Delay time permits entry through Exit Entry Zone s after the system is armed without setting off an immediate alarm Entry Delay allows the user time to enter and disarm the system Upon entering the keypad sounder will sound a steady tone Entry Sound to remind the user to disarm the system En try Del...

Page 14: ... 1 2 Enable Keypad AUX 8G Additional Programming required Select reporting to Telco 1 36 2 or Telco 3 56 2 3 Enable Keypad Panic 9G Additional Programming required Select reporting to Telco 1 36 3 or Telco 3 56 3 4 Enable Ambush If enabled the 8th User Code will send an Ambush report when entered to disarm the system Additional Programming required Program User 8 Arm Disarm Code Select reporting t...

Page 15: ...ed The PGM output will flash when the panel has gone into alarm Includes Bell Cut Fire Trouble Receiver Fail to Respond Receiver Tamper Re ceiver JAM Wireless Smoke Low Battery Wireless Smoke Supervisory Fail 26 Miscellaneous Features 2 1 Momentary Keyswitch Arming Typi cally connect a normally open Keyswitch across the zone AND its 3 3K zone doubling resistor 2 Reserved 3 Inhibit Fail to Communic...

Page 16: ...G 3 Panic Program to activate a Panic report 9G 4 Test Timer Program to activate a Test Timer report 37 System Reporting Telco 1 1 AC Fail Report Program to activate an AC Fail report 15 minute fixed report delay 2 Low Battery Report Program to acti vate a Low Battery report 3 Trouble Report Program to activate a Trouble report 4 Fire Report Program to activate a Fire report Includes Bell Cut Fire...

Page 17: ...han 4 retries remaining 4 Reserved Pager Programming If Pager Format 32 and or 42 and or 52 7 is selected pager data will be displayed as shown in Figure 8 If Pager Format is selected 4 2 format must be programmed and Sumcheck is not permitted If a PIN number is required refer to Leading Digits 47 Pager Alarm data is the same as 4 2 format with the exception that the 2 digit Report Code is transmi...

Page 18: ... second digit of the restore code is the zone number of the restored zone For ex ample if the Zone Restore Code 62 is pro grammed to E the restore code for that zone would be E4 4 2 format 62 2 Trouble Code Conditional Closing Reports Zones that are bypassed at the time of arming send this code along with the zone number of the bypassed zone s For example a conditional closing by User 2 with zones...

Page 19: ...once every hour If the receiver does not receive a signal from a transmitter in the time pro grammed in Wireless Supervisory Timer a system trouble RF Supervisory Failure will be indicated at the keypad Program Wireless Supervisory Timer 16 to change the supervisory time from the default of 12 hours The Signal strength of a transmitter can be checked at the keypad see A7 Fault Find Mode or saved t...

Page 20: ... or Home Away with Delay Zones that have been by passed 8 Interior Program an 8 in the AUX 1 and or AUX 2 option to Bypass Exit Entry Follower Zones or Home Away with Delay Zones when the M or N buttons on the Keyfob are pressed only if the system is programmed exclusively for Home Away with Delay Zones 85 88 Wireless Smoke Detectors Enter the RF ID of the smoke detector A wireless smoke detector ...

Page 21: ... The Computer is now in STANDBY Site At the site perform the following three steps 1 Arm the panel 2 Disarm the panel 3 Enter A6 The panel will now call the download computer running PCPreset PCPreset will answer the call establish a connection and then download the account that matches the Auto Download ID Number 93 with the account of the same number in the list that PCPreset is currently runnin...

Page 22: ...ervision from the bell circuit 3 System Trouble Auto Restore Nor mally System troubles require acknowledg ment View System Trouble in order to re store If this option is selected troubles will restore without requiring acknowledgment 4 User 1 Code Program only If en abled User 1 Code will function only as the User Program Code and will not Arm Disarm the panel Note All programming within Programmi...

Page 23: ...f AC the keypad will beep once every 10 seconds The keypad will con tinue to beep until the reset button is pressed or the trouble has been acknowledged by pressing the C key System Trouble Reporting The following system troubles when enabled to report to Telco 1 37 3 or Telco 3 57 3 will send the report code programmed in Trouble Report 63 if reporting using a pulse format System Trouble Pulse Re...

Page 24: ...ted 4 Receiver Jam A signal is blocking the normal reception of transmissions from the wireless devices Ensure that the green LED on the receiver is not on continuously refer to receiver manual WI850 3 Beeps 1 6 Wireless Transmitter Low Battery The battery in the wireless transmitter is low and should be replaced This transmitter is on the zone corresponding to the number of the zone light flashin...

Page 25: ...or R26 which is located directly above Terminal 9 just below the heat sink 5 Where are the fuses The control panel incorporates advanced circuitry which automatically limits the current when an over current condition exists without the use of traditional fuses The circuit will restore automatically when the over current condition is corrected 6 The PGM Output Pulses in Alarm When the PGM lug of th...

Page 26: ...Point 1 and Point 2 terminals are jumped out 10 Keypad LED s Flicker The Keypad is not receiving a POLL from the Panel Check Keypad wiring The Panel is in the process of being Uploaded Downloaded The panel is powering up LED s will flicker until panel has reset and is polling the keypad The connection from the control panel to the keypad is open 11 No Keypad Entry Sounder during Entry Time The key...

Page 27: ...27 ...

Page 28: ...ut not limited to any or all of the following criminal tampering electrical or communications disruption it is possible for the system to fail to perform as expected NAPCO does not represent that the product system may not be compromised or circumvented or that the product or system will prevent any personal injury or property loss by burglary rob bery fire or otherwise nor that the product or sys...