LIBRA LIB-P432EX Series Programming Instructions 

Page 19

 

SYSTEM OPTIONS (ADDRESS 1420-1424, 2051-2054) 

FOOTNOTES 

 

*Address 1423:  Default depends on Easy Menu Question :"

EZ ZONE 

DOUBLING? Y/N

".  If yes, then [Default = 1].  If no, then [Default = 

blank (•)]. 

**To select "Line-Fault Test only when Armed", you must also select 

"Enable Line-Fault Test" at address 1423. 

***If "Enable Global Ambush Code" in Address 1422 is selected, then pro-

gram the 2-digit "Global Ambush Code" in Address 2045.  If Address 
2045 is left blank (•), then, the 2-digit "Global Ambush Code" will be "99". 

****If this feature is not selected, the E15 Lug will, by default, activate 

when the system is armed (all areas). 

††For reference only and cannot be changed. 
§This feature must be programmed in Fire Alarm applications. 

 

1420  System Options 

   

1421 

 

 

Default   

 

 

Option 

   

Default   

   Option 

 

  OFF   

Opening Report Only after Alarm Report 

    OFF 

 

Auto Bell Test on Arming 

 

  OFF   

Closing Report Only on Conditional Close 

    OFF 

 

Auto Reset after Burglary Output Timeout 

 

  OFF   

Incl. Sel./Grp. Bypass in Cond. Close /Status 

    OFF 

 

Suppress Bypass Reminder when Armed 

 

  OFF   

Status Report 

    OFF 

 

Enable Local Alarm on First Zone AND Trip 

 

 

 

 

RESERVED 

    OFF 

 

Access Control on PGM2 Output 

 

  OFF   

Enable AutoArm if not closed at end of Window      OFF 

 

Maintained Keyswitch Arming 

 

  OFF   

Enable Keypad Time/Date Display 

    OFF 

 

Enable Manager's Mode 

 

  OFF   

Disable Zone Fault Scrolling 

    OFF 

 

Disable Keypad Instant Mode 

 

System Options 

 

1422  System Options 

   

1423  System Options 

 

  Default   

   Option 

    Default*   

   Option 

 

  OFF   

Interior Normally Bypassed 

    OFF*   

Enable Zone Doubling (Zones 9-12) 

 

  OFF   

Enable Global Ambush Code *** 

    OFF*   

Wireless Trouble Activates Telco 1 

 

  OFF   

Reset Day Zone with Arm/Disarm Only 

    OFF*   

Wireless Trouble Activates Telco 3 

 

  OFF   

Enable Residential Fire 

    OFF*   

Enable Alarm Output on Telco Fail only when Armed 

 

  OFF   

Disable Keypad Function Mode Download 

    OFF*   

Line-Fault Test only when Armed**

 

 

  OFF   

Disable Callback Download 

    OFF*   

Enable Line-Fault Test** 

 

  OFF   

Chirp Output on Keyfob Arm/Disarm 

    OFF*   

Inhibit System Trouble Audible at Keypad 

 

  OFF   

Change Pulse Output to Temporal Output

§

 

    OFF*   

Select Alarm Output for Keyfob Chirp 

 

 

 

   

 

   

 

   

 

2051  System Options 

 

Default   

   Option 

 

OFF 

 

Enable Keypad Set Time/Date Message 

 

OFF 

 

Enable Cancel Report to Telco 3 

 

OFF 

 

Disable [ON/OFF] as Easy Exit 

 

 

 

RESERVED 

 

 

 

RESERVED 

 

 

 

RESERVED 

 

OFF 

 

Disable System Trouble Audible Timeout 

 

OFF 

 

Enable "K Series" Style Keypads

 

†† 

 

 
 

 

 

1424 

  Default   

   Option 

  OFF   

Automatic Interior Bypass/Easy Exit 

 

 

 

RESERVED 

 

 

 

RESERVED 

  OFF   

Resound on Wireless Smoke Low Battery 

  OFF   

Don't Clear PGM2 Output with Disarm 

  OFF   

Disable 2nd Call Ans. Machine Override 

  ON 

 

Enable Loop Supervision 

  OFF   

Disable Code Required for Bypass (Enable EZ Bypass) 

System Options 

2053 

 

Default   

   Option 

 

OFF 

 

Exit Time Restart 

 

OFF 

 

Sound Alarm On Exit Error 

 

OFF 

 

Rpt Exit Err/Recent Close 

 

OFF 

 

Enable CP-01 Limits 

 

OFF 

 

Digital Dialer Rpt Enter /Exit Test Mode 

 

OFF 

 

Disable Call Waiting on 1st Attempt 

 

OFF 

 

Enable Keypad 1 Only Programming 

 

OFF 

 

Enable CP-01 Egress Tones Only 

 

System Options 

2054 

 

Default   

   Option 

 

OFF 

 

Enable TCP/IP Communications 

 

ON 

 

Enable EN501 User Code Access Level 

 

 

 

RESERVED 

 

ON 

 

Enable Display Time On Blanked Keypads 

 

ON 

 

Enable EN501 Grade 3 Operation  

 

 

 

RESERVED 

 

ON 

 

Enable 2-Count Swinger Shutdown 

 

ON 

 

Enable Keypad Blanking 

 

System Options 

 

2052  E15 Lug / System Options 

  Default   

   Option 

 

 

 

RESERVED 

 

 

 

RESERVED 

  OFF   

Lug E15 Area 1 Armed Away Only**** 

  OFF   

PGM on RF Transmitter Tamper 

 

 

 

RESERVED 

 

 

 

RESERVED 

 

 

 

RESERVED 

 

 

 

RESERVED 

Summary of Contents for GEM-DXK1

Page 1: ...he battery 3 Configure the keypad see page 42 4 Access the Easy Menu Driven Dealer Program Mode Press 456789 w Press NO q until ACTIVATE PROGRAM Y N appears on the keypad display Press YES p to Enter...

Page 2: ...s manual as well The Instant z button and the AWAY q button operate identically in Program Mode for both keypads These buttons are also used to answer NO or PRIOR to questions that appear on the keypa...

Page 3: ...ormat 8 Enter User Codes 8 RF Transmitter Points 9 Key Fob Transmitters as Arm Disarm Control Devices 9 Key Fob Transmitters as Zone Input Devices 10 Enter Zone Descriptions 10 Enter Date 10 Enter Tim...

Page 4: ...the Dealer Program Mode wherein data is entered at the keypad by location This mode is accessed from the Easy Menu Driven Program Mode by pressing the y button at any time User Program Mode Keypad Pr...

Page 5: ...nes in Area 1 50mS Loop Response Zones Aux Output Activated on Alarm Zones Sensor Watch Zones Keypad Sounder on Alarm Zones Auto Bypass re entry Zones Enable no EOLR Zones Enable Telco Line Fault Test...

Page 6: ...ectly enter each zone number including leading zeros Press u to save and repeat for any additional zone s press p to proceed NOTE Exit Entry Entry time of 30 seconds will automatically be programmed I...

Page 7: ...leading zeros Press u to save and then repeat for any additional zone s Press p to proceed NOTE A PGM2 Timeout of 15 minutes will automatically be programmed Sensor Watch Zones New Program Only Enter...

Page 8: ...or p to proceed Enter User Codes Press w to set cursor For default program enter up to 64 User Codes with Area 1 2 3 4 Options Press the w button once to set the cursor to the User Code Press 0 throu...

Page 9: ...ammed Transmitter 287613 1 point 1 will be mapped to Zone 6 5 Enter Zone 09 6 Close point 1 loop and open point 2 loop 7 Remove the transmitter battery then re install it The keypad will beep once to...

Page 10: ...on Press u to save Press NEXT r or p to proceed Dealer Code Directly enter the Dealer Code default 456789 using 0 through 9 buttons Press u to save Re enter the Dealer Code to verify the previous code...

Page 11: ...splay and accept data in number format For example Zone Features are turned on by the pressing of keypad buttons 1 through 8 with the activated Zone s displaying the corresponding decimal digit replac...

Page 12: ...automatically moving to the right upon each key press EXAMPLE DECIMAL Format with the GEM DXRP1 DXK1 Program Abort Delay to be 15 seconds DETERMINE THE DATA ENTRIES 1 Referring to SYSTEM DELAYS TIMEOU...

Page 13: ...1 Referring to SYSTEM DELAYS TIMEOUTS in the Programming Worksheets that follow the Chime Timeout is located at address 1418 In the Chime Timeout Options table the data entries needed to assign a time...

Page 14: ...ws software following any keypad programming and that the PCD Windows s error check feature be utilized to reduce the possibility of programming omissions or conflicts 3 Keep the Keypad Programming Wo...

Page 15: ...is page and on the following pages are automatically set after exiting the Easy Menu Driven Mode 1 Enter delay timeout in corresponding address locations above Note All entries for address 1418 are in...

Page 16: ...AT In Pager Format reporting the message typically begins with 00 However for some pager services this will cause the Pager s Voice Mail feature to activate This option allows you to program these dig...

Page 17: ...Ambush Code is selected and Address 2045 is not left blank then the 2 digit Global Ambush Code is the two digits entered in address 2045 Enter in address location both 1st and 2nd digits valid entries...

Page 18: ...FIRE KEYPAD AUX KEYPAD TAMPER FAIL TO OPEN FAIL TO CLOSE Keyfob Low Batt 1 2 3 4 5 6 7 8 Pulsed Alarm Output 0872 Alarm Output 0873 PGM1 Output 0874 PGM2 Output 0876 Report Event Telco 1 0877 Report...

Page 19: ...F 3 Reset Day Zone with Arm Disarm Only OFF 3 Wireless Trouble Activates Telco 3 OFF 4 Enable Residential Fire OFF 4 Enable Alarm Output on Telco Fail only when Armed OFF 5 Disable Keypad Function Mod...

Page 20: ...for dial tone F Ignore location Default for CS Receiver 1 Tele phone Number depends on Easy Menu Question C E N T R A L PHONE Default blank across digits 1 20 for CS Receiver Telephone Num bers 2 and...

Page 21: ...RIGHT DIGITS 1 4 0596 0597 0598 0599 CS Telco 3 Sub scriber Event ID Number Area 1 ADDRESS 0648 0651 RIGHT DIGITS 1 4 0648 0649 0650 0651 CS Telco 3 Sub scriber Opening Closing ID Number Area 3 ADDRES...

Page 22: ...0 0705 CS AREA SYSTEM REPORTING OPTIONS ADDRESS 0785 0786 0788 Default blank blank DISABLE OPENING REPORTS LEFT DIGIT RIGHT DIGIT SUM OF DATA VALUES blank ADDRESS 0785 NOTE If neither Touch tone Diali...

Page 23: ...al requires a Set Unset code Enter level 2 3 4 to come alive The keypad will stay alive Normal for 128 seconds default or for a time in a programma ble EEProm location in seconds This location 2060 co...

Page 24: ...ZONE 22 ZONE 23 ZONE 24 0740 0741 0742 0743 NOTE If Zone Doubling Address 1423 is not enabled then Zones 1 4 are included in the control panel and Zones 5 32 are wireless Zones If Zone Doubling is en...

Page 25: ...n not available 3 Press u to save USERS 49 56 USERS 57 64 Enable Users to Report Opening and Closings ADDR U49 U50 U51 U52 U53 U54 U55 U56 ADDR U57 U58 U59 U60 U61 U62 U63 U64 1 2 3 4 5 6 7 8 1 2 3 4...

Page 26: ...LIBRA LIB P432EX Series Programming Instructions NAPCO Security Systems Page 26 This page left blank intentionally...

Page 27: ...sarm Default Option Disarming Area 1 ON 1 Area 1 Pulsed Burg Output Silenced OFF 2 Area 2 Pulsed Burg Output Silenced OFF 3 Area 3 Pulsed Burg Output Silenced OFF 4 Area 4 Pulsed Burg Output Silenced...

Page 28: ...eypad Area Assignment KEYPAD TYPE Up to 7 key pads may be programmed if they are connected NOTE See Keypad Configura tion Mode 1 Select keypad type for each keypad from the tables shown 2 Enter data i...

Page 29: ...NAPCO Security Systems LIBRA LIB P432EX Series Programming Instructions Page 29 This page left blank intentionally...

Page 30: ...d to a new global value Address 2062 accepts three decimal digits which are multiplied by 10 milli seconds to get a new value that replaces the default value of 750ms If the loca tion is set to 000 th...

Page 31: ...98 Trouble on Short 0935 0999 Zone Area 1 0936 1000 Zone Area 2 0937 1001 Zone Area 3 0938 1002 Keypad Sounder on Alarm 0941 1005 2 Wire Smoke Detectors 0942 1006 Fire 0943 1007 Fire Alarm Verificatio...

Page 32: ...1129 Interior Stay Bypass 1068 1132 Keypad Sounder on Alarm 1069 1133 Fire 1071 1135 Fire Alarm Verification 1072 1136 Zone ANDing Group 1 1074 1138 Zone ANDing Group 2 1075 1139 Zone ANDing Group 3...

Page 33: ...NAPCO Security Systems LIBRA LIB P432EX Series Programming Instructions Page 33 This page left blank intentionally...

Page 34: ...LIBRA LIB P432EX Series Programming Instructions NAPCO Security Systems Page 34 This page left blank intentionally...

Page 35: ...LAY EVENT 15 1559 1560 1561 1562 1563 RELAY AREA TIMEOUT EVENT ID COND ADDRESS 1554 1558 RELAY EVENT 14 1554 1555 1556 1557 1558 RELAY AREA TIMEOUT EVENT ID COND ADDRESS 1574 1578 RELAY EVENT 18 1574...

Page 36: ...and Timeout Type from Table 5A on next page enter in corresponding left address location 5B Select Activation Conditions from Table 5B on next page enter in corresponding right address location STEP 2...

Page 37: ...General System Alarm D 8 Area 1 General System Alarm D 9 Area 2 General System Alarm D 0 Area 3 General System Alarm D B Area 4 General System Alarm F blank Relay Control Group 1 F 1 Relay Control Gr...

Page 38: ...nutes 2 Enter in corresponding address locations below right nibble 3 Press u to save NOTE These timers apply only to Supervised RF Transmitters see RF Transmitters in Easy Menu Driven Mode Programmin...

Page 39: ...chedules can only be programmed again with the Downloading Software If power fails time and date restarts at 00 00 00 and a date of 01 01 04 January 1 2004 2285 XX H 2286 XX H USER PROGRAM MODE PRELIM...

Page 40: ...s The cursor will then advance to the User Code and read the existing code if any Enter the new User Code using the number buttons 0 9 If an old code is displayed program over it To erase the digit at...

Page 41: ...change to uppercase Press u to save To advance to the next zone or to any other zone move the cursor to the displayed zone number i e 01 using w and x Change the zone number using keys 0 through 9 Ent...

Page 42: ...M DXRP1 GEM DXK1 keypad must be configured for a keypad tactile beep b entry sounder c keypad address and d compatibility number To enter the Keypad Configuration Mode 1 Move jumper JP1 located in the...

Page 43: ...press the y button to exit Zone Response THIS FEATURE IS NOT COMPATIBLE WITH THE LIB P432EX CON TROL PANEL DO NOT CHANGE THIS SETTING Press the w button to continue or press the y button to exit Prog...

Page 44: ...ccount Number Central Station Receiver 1 Format blank Ademco Slow Silent Knight Slow 2 Radionics Fast 3 Silent Knight Fast 4 Radionics DCI Franklin Slow 5 Universal High Speed B SIA C Ademco Point ID...

Page 45: ...RF Transmitter Points XMTR ZONE CHECK SUM POINT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 RF ID printed on xmtr box XMTR ZONE CHECK SUM POINT 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 RF ID printe...

Page 46: ...9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 CHARACTERS AVAILABLE See below Dealer Code Charact...

Page 47: ...NAPCO Security Systems LIBRA LIB P432EX Series Programming Instructions Page 47 This page left blank intentionally...

Page 48: ...NTROL OPTIONS ADDRESS 1473 1488 27 AREA BURG OUTPUT SILENCED 27 AREA OPTIONS 8 9 AUTO ARMING DISARMING USER 65 25 AUTO BELL TEST ON ARMING 19 AUTO BYPASS RE ENTRY ZONES 7 AUTO RESET AFTER BURGLARY OUT...

Page 49: ...AT 22 DISABLE ZONE FAULT SCROLLING 19 DISARMING AREAS 1 4 BURG OUTPUT SILENCED 27 DON T CLEAR PGM2 OUTPUT WITH DISARM 19 DOWNLOAD FUNCTION OVERVIEW 4 DOWNLOAD CALLBACK OPTIONS ADDRESS 0526 0545 16 DOW...

Page 50: ...KEYPAD ADDRESS 42 KEYPAD AUX 17 KEYPAD AUX KEYPAD OPTION 28 KEYPAD CONFIGURATION MODE 42 KEYPAD ENTRY SOUNDER 42 KEYPAD FIRE 17 KEYPAD FIRE KEYPAD OPTION 28 KEYPAD NUMBER ASSIGNING 42 KEYPAD OPTIONS...

Page 51: ...MING USER 66 25 R RADIONICS FAST 20 RADIONICS DCI 20 RELAY CONTROL EXTERNAL ADDRESS 1489 1648 35 REMOTE DOWNLOADING OVERVIEW 4 REPORT CANCEL WINDOW ADDRESS 2055 15 REPORT EVENT TELCO 1 ADDRESS 0840 17...

Page 52: ...ORT ZONE OPTION 31 32 33 34 TROUBLE RESTORE ADDRESS 0672 22 TROUBLE RESTORE 1 ZONE OPTION 31 32 33 34 TROUBLE RESTORE 3 ZONE OPTION 31 32 33 34 TROUBLE TELCO 1 ZONE OPTION 31 32 33 34 TROUBLE TELCO 3...

Page 53: ...ERVISION 22 ADDRESS 0675 XMITTER TAMPER 22 ADDRESS 0677 OPENING 22 ADDRESS 0678 CLOSING 22 ADDRESS 0679 OPENING AFTER ALARM 22 ADDRESS 0680 CONDITIONAL CLOSE 22 ADDRESS 0681 CANCEL 22 ADDRESS 0682 TES...

Page 54: ...ESS 0872 0887 SYSTEM OPTIONS 18 ADDRESS 0873 ALARM OUTPUT 18 ADDRESS 0874 PGM1 OUTPUT 18 ADDRESS 0876 PGM2 OUTPUT 18 ADDRESS 0877 REPORT EVENT TELCO 1 18 ADDRESS 0879 REPORT EVENT TELCO 3 18 ADDRESS 0...

Page 55: ...Y CONTROL EXTERNAL 35 ADDRESS 2029 2044 RF RECEIVER SUPERVISORY TIMER OPTIONS 38 ADDRESS 2045 GLOBAL AMBUSH CODE 17 ADDRESS 2045 SYSTEM OPTIONS 17 ADDRESS 2050 SENSOR WATCH TIME 15 ADDRESS 2050 SYSTEM...

Page 56: ...LIBRA LIB P432EX Series Programming Instructions NAPCO Security Systems Page 56 LIB P432EX WIRING DIAGRAM...

Page 57: ...NAPCO Security Systems LIBRA LIB P432EX Series Programming Instructions Page 57 LIB P432EXT WIRING DIAGRAM...

Page 58: ...LIBRA LIB P432EX Series Programming Instructions NAPCO Security Systems Page 58 LIB P432EXT 230 WIRING DIAGRAM...

Page 59: ...NAPCO Security Systems LIBRA LIB P432EX Series Programming Instructions Page 59 NOTES...

Page 60: ...60 R Publicly traded on NASDAQ Symbol NSSC NAPCO Security Group Inc 333 Bayview Avenue Amityville New York 11701 For Sales and Repairs call toll free 800 645 9445 For direct line to Technical Service...