CLEAR PROGRAM OPTIONS (ADDRESS 2285 & 2286)
Clear Dealer Program (Erases Dealer Program)
This
erases the dealer program
. Use this feature to start
a customized default program. Program Data and Sys-
tem Status Memory is erased where Scheduled Data and
Zone Descriptions are maintained.
Access address 2285, then press
u
. Data entry is not allowed.
NOTE:
Enter Easy Menu Driven Program Mode to program system
again.
Cold Start (Erases Entire Program)
This erases the entire program including Dealer Pro-
gram by erasing Program Data, Zone Description
Data and System Status Data (similar to a new
panel).
Access address 2286, then press
u
. Data entry is not allowed.
NOTE:
Some features (schedules) can only be programmed again
with the Downloading Software. If power fails, time and date restarts at
00:00:00 and a date of 01-01-04 (January 1, 2004).
2285 XX H
2286 XX H
USER PROGRAM MODE
PRELIMINARY INFORMATION
The User Program Mode is covered in detail in the operating instructions for the keypad in use.
The Program Mode cannot be accessed while the communicator is transmitting except during the first three minutes after power-
up.
After entering codes or data, press the save
u
button.
Data will not be stored into memory unless this button is pressed.
If the keypad is in the Program Mode and no activity is detected for longer than 4 minutes, a steady tone will sound.
Press the
y
button to silence the sounder and exit the User Program Mode.
For ease of programming, it is recommended that a GEM-DXRP1 or GEM-DXK1 be used. For Programming Instructions with the
GEM-DXRP2 / GEM-DXK2, GEM-DXRP3 / GEM-DXK3 and the GEM-DXK4RF series, see WI1771.