SYSTEM

 Main Control board supports up to two (2) Addressable Fire SLCs       

   (addressable Signaling Line Circuit controllers). 

(Note: Only 1 SLC is     

    accomodated within the Medium panel enclosure.*)

 Fire 4-wire bus for keypads and non-SLC (conventional) devices, 

including 12V devices

 Power Supply includes either 4A or 7A @ 24V

 RS-232 Printer Module for optional onsite parallel printer

 Supports up to 7 fire keypads, GEMC-FK1, mounted anywhere on the 

bus. (As few as one keypad required on system for equipment savings.)

 

  Easy-to-use Gemini-style menu-driven operation with backlit custom  

  alphanumeric display and  functionality for       

 

 

  Reset, Acknowledge, Silence (with disable). 

  Full Keyswitch Support 

 Synch module built in on each NAC  (System Sensor & Wheelock 

protocols)

 Dual Phone Line built in

 

  2 On board serial ports - one for internet reporting; one for  

    high-speed local downloading

 TCP/IP Internet reporting module

 Regulated Auxiliary Power Supplies - Commercial fire, 12V regulated 

2A or 1.75A version with plug in transfomer

• 

Addressable SLC Loop Isolator (

optional use 

- for some fire 

applications requiring increased circuit integrity, e.g., meets Class A, 

Style 7 loop requirements.

 

Choice of two enclosures

 

 - 

Between the studs enclosures, recess or 

surface mount  – 

 

•  

Larger version supports up to 32 AH at 24V.  Dimensions: 24” x    

14.25” x 5.2” (H x W x D) without cover. Removable battery shelves, 

accommodate pairs of 7Ah, 7.5Ah and 8Ah batteries, etc. 

 

 Medium Enclosure – supports 16 AH at 24V. Dimensions: 16”x 

14.25” x 5.2” (H x W x D) without cover. (*

Note: Only 1 SLC is     

    

accomodated.) 

16Ah battery backup capacity.

INPUTS

Up to 255 Zones. Zones can come from any of the following 
initiating devices:

 Addressable SLC Loop – supports up to (2) 126 point loops

 Commercial RF Receiver – 

 Supports Commercial Wireless Fire devices

 

 Wireless Smoke Detector

 

 Wireless Heat Detector

 Conventional 1- to 4-zone EZM Expansion modules on the 4-wire fire 

bus or SLC loops

 Conventional 2-wire or 4-wire smoke detector input module

 SLC Fire Devices Supported:  

 

 Analog Smoke Detector 

 

 Analog Heat Detector 

 

 Duct Detector 

 

 Pull Station 

 

 Conventional Zone Module  

  •

 Short Circuit Isolator

OUTPUTS

Up to 96 outputs

 Four on board Class B or 2 Class A NAC circuits, 2 amps each, total 6.5 

amps at 24V

 Built in Wheelock and System Sensor NAC sync/strobe/horn protocol 

allows initial silence of audible appliances while maintaining visual 

notification, 

without the use of additional modules.

 Addressable SLC Fire Devices: Supervised relay, unsupervised relay

 Fire 4-wire bus devices: 8 zone form C relay (GEMC-RM3008), 8 open 

collector output (GEMC-OUT8)

Advantages

 Easy Wire Compatibility 

- Addressable SLC 

controller supports shielded, unshielded, 

twisted and untwisted wire - ideal for retrofits

 Longer SLC loop lengths, support more 

device loads each, too 

(see below for 

distance at maximum device load in alarm/

standby each):

 

 10,000 ft. #14AWG 

 6,200 ft. #16AWG  

 

4,000 ft. #18AWG

 

Support for Legacy and Existing Notification Appliances -

One 

NAC output configurable for 12V for compatibility for easy retrofit 

compatibility

 UL Regulated NAC outputs

 

Automatic drift compensation for smoke detectors

 Keypads mount anywhere on the bus and have flash-able firmware – 

for updates via Quickloader command 

(# GEMC-FK1, shown above)

 

Programmable obscuration level by smoke detector device

 

Smoke Obscuration Report genererated remotely or locally or in any 

of 3 ways - 

Quickloader device sensitivity report allows the printout of 

a report for the AHJ listing the current status of all smoke detectors 

in the system including the programmed obscuration level and the 

actual sensitivity reading for each device. This report can be generated 

remotely (uploaded) or locally through notebook PC or use optional 

onsite printer.

 

Full line of UL Commercial Devices for more flexibility & labor-savings 

Example, Use Gemini  Commercial Wireless 2-input module (GEMC-

WL-WD2) to convert any UL listed fire device into a UL wireless device, 

ideal for sprinkler supervisories or for use with pull stations (mounts on 

top of wall/conduit or in deep sngle-gang box (plastic).  

 

Separate 7Amp 4-NAC Extender

 (GEM-NAC7) 4 onboard NACs with 

up to 2A ea., expandable for up to 24 per system. Up to 16Ah total 

battery capacity. Regulated 24V Aux. power. Monitors AC, battery 

trouble, tamper and ground fault on Napco bus 

-

 

Also 

Provides 

Universal FACP support for easy standardization in upgrades

 

(Shown above)  
32-Point GEM-C Firewolf™ 24V Commercial Fire System

Agencies

NFPA 72, UL Commercial Fire, UL864 9th Ed., UL985.  

(

CSFM, FM, 

MEA

 listings pending.)

Napco Commercial

  Firewolf-Series  Components                                

for 32 to 255 Point 24V Commercial Fire Systems: