NPC 015 TO 230
1 2 . 2 O u t l e t b l o c k i n g
NOTE
The electronic control board is furnished with a “history” loop, see chapter 7.12.5 “How to display the alarm historic “ALoG”” .
Alarm code Alarm Description
Comp. 1
Comp. 2
Antifreeze
Resistances Pump
P1
BEWOT
probe
Yes
Yes
Yes
P2
BTWOT
probe
Yes
Yes
Yes
P3
BCP1
probe
Yes
Yes
Yes
P4
BAT1
probe
Yes
Yes
Yes
A01
High pressure switch
Yes
Yes
Fan thermal protection
Yes
Yes
A02
Low pressure switch
Yes
Yes
A03
Ambient air low temperature
A04
Air low temperature at unit
outlet
Yes
Yes
Yes
A05
High temperature High
pressure
Yes
Yes
A06
Low pressure Low
temperature
Yes
Yes
A07
Analogue input antifreeze
Yes
Yes
A07
Digital input antifreeze
Yes
Yes
A07
Motorcondensing antifreeze
Yes
Yes
A08
Flow meter/pump thermal
protection
Yes
Yes
Boiler Res.
Yes
Yes
A09
Compressor 1 thermal
protection
Yes
A10
Compressor 2 thermal
protection
Yes
A09-A10
Compressor 1-2 thermal
protection
Yes
Yes
A13
Compressor 1 maintenance
A14
Compressor 2 maintenance
A15
Water pump maintenance
A20
Low water temperature
BTWOT
A21
High water temperature
BTWOT
rtC
Clock alarm
rtF
Clock alarm
EE
Eeprom error
Yes
Yes
Yes
Yes
ACF2
Configuration alarm
Yes
Yes
Yes
Yes
ACF3
Configuration alarm
Yes
Yes
Yes
Yes
ACF4
Configuration alarm
Yes
Yes
Yes
Yes
ACF6
Configuration alarm
Yes
Yes
Yes
Yes
FErr
Operating error
(motorcond.)
Yes
Yes
Yes
Afr
Net frequency alarm
Yes
Yes
Yes
Yes
ALOC
Generic alarm
Yes
Yes
Yes
Yes