NPC 015 TO 230
A07
Antifreeze alarm
Digital input
enabled if
BTWOT
< “
set value
” and
actives for the “
time
set
”
“open collector” outlet / alarm relay is
activated
The buzzer is activated
The icon for general alarm flashes
The alarm code is displayed
Automatic
It becomes manual after “
tripping per hour
”
Manual
Disabling:
- when the antifreeze regulation probe
BTWOT
> “
set value
” in chiller modality;
and resetting procedure
A07
Antifreeze alarm
Digital input
enabled
“open collector” outlet / alarm relay is
activated
The buzzer is activated
The icon for general alarm flashes
The alarm code is displayed
Automatic
It becomes manual after “
tripping per hour
”
Manual
Disabling: digital input not enabled
resetting procedure
A07
Antifreeze alarm
motocondensing
units (Not enabled)
Digital input
enabled
“open collector” outlet / alarm relay is
activated
The buzzer is activated
The icon for general alarm flashes
The alarm code is displayed
Automatic
It becomes manual after “
tripping per hour
”
Manual
Disabling: digital input not enabled
resetting procedure
A08
Flow meter alarm
and pump thermal
alarm (air/water or
water/water units)
Digital input
enabled
enabled for “
time
set
”
“open collector” outlet / alarm relay is
activated
The buzzer is activated
The icon for flow meter alarm flashes
The alarm code is displayed
Automatic
It becomes manual after “
tripping per hour
”
Manual
Disabling: Digital input disabled for “
time
set
” and reset procedure
A09
Compressor 1
thermal alarm
Digital input
enabled
“open collector” outlet / alarm relay is
activated
The buzzer is activated
The icon for general alarm flashes
The alarm code is displayed
Manual
Digital input disabled and the resetting
procedure is carried out
A10
Compressor 2
thermal alarm
Digital input
enabled
“open collector” outlet / alarm relay is
activated
The buzzer is activated
The icon for general alarm flashes
The alarm code is displayed
Manual
Digital input disabled and the resetting
procedure is carried out
A09-
A10
Compressor 1-2
thermal alarm
The alarm is
visualized but not
enabled during
“compressor
thermal delay time”
after compressor
start up
Relay alarm + buzzer activated
If ID is not activated
Manual
To reset the alarm enter the programming
A11
Condensation fan
(Not enabled)
Digital input
enabled
“open collector” outlet / alarm relay is
activated
The buzzer is activated
The icon for general alarm flashes
The alarm code is displayed
Manual
Digital input disabled and the resetting
procedure is carried out
A12
Error alarm during
defrosting (not
enabled
Defrosting end
(max. time)
Displayed code
Only signalling
Automatic
With following correct defrosting cycle
Manual
Reset procedure
A13
Compressor 1
maintenance alarm
Operating hours >
“
set threshold
”
“open collector” outlet / alarm relay is
activated
The buzzer is activated
The alarm code is displayed
Manual
Operating hours reset
A14
Compressor 2
maintenance alarm
Operating hours >
“
set threshold
”
“open collector” outlet / alarm relay is
activated
The buzzer is activated
The alarm code is displayed
Manual
Operating hours reset
A15
Water pump
maintenance alarm
Operating hours>
“
set threshold
”
“open collector” outlet / alarm relay is
activated
The buzzer is activated
The alarm code is displayed
Manual
Operating hours reset
A20
Low water
temperature alarm
at evaporator outlet
Only units operating
if the temperature
measured by PB2 is
lower than AL23
“open collector” outlet / alarm relay
activated
The buzzer is activated
The alarm code is displayed
Automatic
CODE
MEANING
CAUSE
ACTION
RESET