NPC 015 TO 230
7.12.7 Displaying t he operating hou rs o f loads “C1Hr - C2Hr - PF Hr”
1.
Press
*
button to enter Function menu.
2.
Press
(
or
'
button until the Label of a single load appears in the bottom of the display:
C1Hr
(operating hours of compressor
1),
C2Hr
(operating hours of compressor 2),
PFHr
(operating hours of water pump and of outlet fan).
The operating hours will appear in the top of the display.
3.
The icon
will be lit.
7.12. 7. 4 Reset o f th e load operatin g h ours
1.
Press
*
button to enter Function menu.
2.
Press
(
or
'
button until the Label of a single load appears in the bottom of the display (
C1Hr
,
C2Hr
only 201÷351 units,
PFHr
) and the operating hours appear in the top of the display.
3.
Press
-
button for 3 seconds: in the top of the display it will appear “0”. It indicates that the reset has happened.
4.
To exit Function menu, press
*
button or wait for time out (15 seconds).
5.
For the other loads repeat the operations from point 2. to point 4.
7 . 1 3 O t h e r f u n c t i o n s b y k e y b o a r d
7.13.1 How to display th e Set Poin t
Press and release
-
button.
In the bottom part of the display it appears
SetC
(chiller set).
7.13.2 How to modify the Set Po int
1.
Press
-
button for 5 seconds at least.
2.
The set point will flash.
3.
Use
(
or
'
button to modify the set point value.
4.
To store the new set point value press
-
button or wait for time out to exit programming procedure.
7 . 1 4 C o m p r e s s o r s u n l o a d i n g f u n c t i o n
This procedure is necessary when sudden peaks in cooling demand occur, for instance if the machine is restarted after a long period of inactivity.
Under these conditions the evaporator inlet water temperature might be so high as to require a cooling delivery in excess of system capacity.
The consequent system overload would require the start-up of all the compressors at once, which would be forced to operate in near-limit
conditions.
The overburdened compressors would thus be subject to dangerous overheating which would cause the activation of the thermal protections, or
the pressure of the refrigerant gas could reach alarm levels which would cause the machine to shut down.
This function enables the machine to run (through the switch-off or capacity step operation of the compressors) even when the temperature of the
water at the evaporator’s inlet is high (summer start-up with hot water accumulation), preventing the possible triggering of high pressure alarms.
It is not present in one compressor units.
The following messages will flash on the display:
AEUn
= evaporator unloading function
ACUn
= condensation unloading function
7 . 1 5 P r o b e k e y
In this chapter are indicated the probes
BEWOT
,
BTWOT
,
BCP1
and
BAT1
, for their positioning consult the refrigerant drawing.
Their description is indicated in the following table:
Name in the manual
Borne name
Description
-BEWOT
PB1
EVAPORATOR WATER OUTLET TEMPERATURE PROBE
-BTWOT
PB2
TANK WATER OUTLET TEMPERATURE PROBE
-BCP1
PB3
CONDENSING PRESSURE TRANSDUCER (only with electronic regulation)
-BAT1
PB4
AMBIENT AIR TEMPERATURE PROBE (Only with antifreeze protection
function)