FAN POWERED TERMINAL UNITS
C
C90
2 Row (multi-circuit)
300
500
700
900
1100
1300
142
236
330
425
519
613
CFM
l/s
32
29
26
23
20
17
14
11
9.4
8.5
7.6
6.7
5.9
5.0
4.1
3.2
kW MBH
GPM l/s
7.5
5
4
3
2
1.5
1
0.5
.47
.32
.25
.19
.13
.09
.06
.03
1 Row (single circuit)
3 Row (multi-circuit)
300
500
700
900
1100
1300
142
236
330
425
519
613
CFM
l/s
60
55
50
45
40
35
30
25
20
15
10
17.6
16.1
14.7
13.2
11.7
10.3
8.8
7.3
5.9
4.4
2.9
kW MBH
GPM l/s
15
10
7.5
5
4
3
2
1.5
1
0.5
.95
.63
.47
.32
.25
.19
.13
.09
.06
.03
300
500
700
900
1100
1300
142
236
330
425
519
613
CFM
l/s
80
75
70
65
60
55
50
45
40
35
30
25
20
15
23.4
22.0
20.5
19.0
17.6
16.1
14.7
13.2
11.7
10.3
8.8
7.3
5.9
4.4
kW MBH
GPM l/s
15
10
7.5
5
4
3
2
1.5
1
0.5
.95
.63
.47
.32
.25
.19
.13
.09
.06
.03
Unit Size 3
1 ROW
2 ROW
3 ROW
1 ROW
2 ROW
3 ROW
Air Pressure Drop
Water Pressure Drop
WATER FLOW
AIRFLOW
HEAD LOSS (WATER PRESSURE DROP)
1
2
3 4
6
8 10
GPM
.06
.13
.19 .25 .38
.50 .63
l/s
10.0
8.0
6.0
4.0
2.0
1.0
0.8
0.6
0.4
0.2
0.1
kPa ft.
H
2
0
29.8
23.9
17.9
11.9
6.0
3.0
2.4
1.8
1.2
0.6
0.3
100 200 400 600 1000 2000
CFM
47
94
189 283 472 944
l/s
AIR PRESSURE DROP
1.00
0.80
0.60
0.40
0.20
0.10
0.08
0.06
0.04
0.02
0.01
Pa in.
w.g.
249
447
149
100
50
25
20
15
10
5
2
Correction factors at other entering conditions:
1. Capacities are in MBH (kW), thousands of Btu
per hour (kiloWatts).
2. MBH (kW) values are based on a
∆
t (temperature
difference) of 110°F (61°C) between entering air
and entering water. For other
∆
t's; multiply the
MBH (kW) values by the factors below.
3. Air Temperature Rise.
4. Water Temp. Drop.
5. Connections: 1 Row 1/2" (13), 2 and 3 Row 7/8"
(22); O.D. male solder.
ATR (°C) = 829 x
kW
l/s
ATR (°F) = 927 x
MBH ,
cfm
WTD (°C) = .224 x
kW
l/s
WTD (°F) = 2.04 x
MBH ,
GPM
NOTES:
∆t °F (°C)
50 (28)
60 (33)
70 (39)
80 (44)
90 (50)
100 (56)
110 (61)
120 (67)
130 (72)
140 (78)
150 (83)
Factor
.455 (.459)
.545 (.541)
.636 (.639)
.727 (.721)
.818 (.820)
.909 (.918)
1.00 (1.00)
1.09 (1.10)
1.18 (1.18)
1.27 (1.28)
1.36 (1.36)
Altitude Correction Factors:
Altitude
ft. (m)
Sensible Heat
Factor
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
1.00
0.94
0.90
0.87
0.84
0.81
0.78
FAN POWERED TERMINAL UNITS • 35S SERIES
Performance Data • Hot Water Coil
Models: 35SW, 35SWST, 35SW-OAI, 35SWST-OAI, 35SW-CVP • Series Flow