SAFETY PRECAUTIONS
(Always read these precautions before using this equipment.)
Before using this product, please read this manual and the relevant
manuals introduced in this manual carefully and pay full attention to
safety to handle the product correctly.
The precautions given in this manual are concerned with this
product.
In this manual, the safety precautions are ranked as "WARNING"
and "CAUTION".
Note that the
CAUTION level may lead to a serious accident
according to the circumstances.
Always follow the instructions of both levels because they are
important to personal safety.
Please save this manual to make it accessible when required and
always forward it to the end user.
[DESIGN PRECAUTIONS]
Indicates that incorrect handling may cause
hazardous conditions, resulting in death or
severe injury.
Indicates that incorrect handling may cause
hazardous conditions, resulting in medium or
slight personal injury or physical damage.
Some failures of the GOT or cables may keep the outputs on or off.
Some failures of a touch panel may cause malfunction of the input objects
such as a touch switch.
An external monitoring circuit should be provided to check for output signals
which may lead to a serious accident.
Not doing so can cause an accident due to false output or malfunction.
Do not use the GOT as the warning device that may cause a serious
accident.
An independent and redundant hardware or mechanical interlock is required
to configure the device that displays and outputs serious warning.
Failure to observe this instruction may result in an accident due to incorrect
output or malfunction.
The GOT backlight failure disables the operation on the touch switch(s).
When the GOT backlight has a failure, the POWER LED blinks (orange/blue)
and the display section dims. In such a case, the input by the touch switch(s)
is disabled.
The display section of the GOT is an analog-resistive type touch panel.
When multiple points of the display section are touched simultaneously, an
accident may occur due to incorrect output or malfunction.
Do not touch the display section in 2 points or more simultaneously.
If you touch the display section simultaneously in 2 points or more, the switch
that is located around the center of the touched point, if any, may operate.
Doing so may cause an accident due to incorrect output or malfunction.
When programs or parameters of the controller (such as a PLC) that is
monitored by the GOT are changed, be sure to reset the GOT, or turn on the
unit again after shutting off the power as soon as possible.
Not doing so can cause an accident due to false output or malfunction.
If a communication fault (including cable disconnection) occurs during
monitoring on the GOT, communication between the GOT and PLC CPU is
suspended and the GOT becomes inoperative.
A system where the GOT is used should be configured to perform any
significant operation to the system by using the switches of a device other
than the GOT on the assumption that a GOT communication fault will occur.
Not doing so can cause an accident due to false output or malfunction.
WARNING
CAUTION
WARNING
[MOUNTING PRECAUTIONS]
To maintain the safety of the system incorporating the GOT, take measures
against unauthorized access from external devices via a network.
To maintain the safety against unauthorized access via the Internet, take
measures such as installing a firewall.
Products with the Cl.I, DIV.2 mark on the rating plate are suitable for use in
Class I, Division 2, Groups A, B, C and D hazardous locations, or
nonhazardous locations only.
This mark indicates that the product is certified for use in the Class I,
Division2 environment where flammable gases, vapors, or liquids are not
likely to exist under normal conditions.
When using the products in the Class I, Division 2 environment, observe the
following to reduce the risk of explosion.
• This device is open-type and is to be installed in an enclosure suitable for
the environment and require a tool or key to open.
• Warning - Explosion Hazard - Substitution of any component may impair
suitability for Class I, Division 2.
• Warning - Explosion Hazard - Do not disconnect equipment unless power
has been removed or the area is known to be non-hazardous.
• The wireless LAN communication unit interface of this device cannot be
used in Class I, Division 2 environment.
Les produits marqués Cl.I, DIV.2 sur la plaque signalétique peuvent être
utilisés en Class I, Division 2, local dangereux de groupe A, B, C et D, ou
uniquement en local non dangereux.
Ce logo indique que le produit est homologué pour utilisation en
environnement de Class I, Division 2 où, dans des circonstances anormales,
il peut y avoir présence de gaz, vapeurs ou liquides inflammables.
Si le produit est utilisé en environnement de Class I, Division 2, observer les
précautions suivantes pour réduire le risque d'explosion.
•
Cet appareil est de type ouvert et il doit être installé dans une enceinte
appropriée à l'environnement et ne pouvant être ouverte qu'au moyen
d'une clé ou d'un outil.
•
Avertissement - Danger d'explosion - Toute substitution de composant
peut compromettre l'aptitude à l'utilisation en Class I, Division 2.
•
Avertissement - Danger d'explosion - Ne pas déconnecter l'équipement
quand le circuit est sous tension, ni avant de d'être assuré de l'absence
d'atmosphère inflammable.
•
L’interface de l'unité de communication LAN sans fil de cet équipement ne
peut pas être utilisée dans les environnements de Classe I, Division 2.
Do not bundle the control and communication cables with main-circuit, power
or other wiring.
Run the above cables separately from such wiring and keep them a minimum
of 100 mm apart.
Not doing so noise can cause a malfunction.
Do not press the GOT display section with a pointed material as a pen or
driver.
Doing so can result in a damage or failure of the display section.
When the GOT is connected to the Ethernet network, the available IP
address is restricted according to the system configuration.
When a GOT2000 series model and a GOT1000 series model are on an
Ethernet network, do not set the IP address 192.168.0.18 for the GOTs and
the controllers on this network.
Doing so can cause IP address duplication at the GOT startup, adversely
affecting the communication of the device with the IP address 192.168.0.18.
The operation at the IP address duplication depends on the devices and the
system.
When using the Ethernet interface, set a different network for port 1 and
port 2.
Turn on the controllers and the network devices to be ready for
communication before they communicate with the GOT.
Failure to do so can cause a communication error on the GOT.
When the GOT is subject to shock or vibration, or some colors appear on the
screen of the GOT, the screen of the GOT might flicker.
Be sure to shut off all phases of the external power supply used by the
system before mounting or removing the GOT main unit to/from the panel.
Not doing so can cause the unit to fail or malfunction.
Be sure to shut off all phases of the external power supply used by the
system before mounting or removing the option unit onto/from the GOT.
Use the GOT in the environment that satisfies the general specifications
described in this manual.
Not doing so can cause an electric shock, fire, malfunction or product
damage or deterioration.
When mounting the GOT to the control panel, tighten the mounting screws in
the specified torque range (0.36 N•m to 0.48 N•m) with a Phillips-head
screwdriver No.2.
Undertightening can cause the GOT to drop, short circuit or malfunction.
Overtightening can cause a drop, short circuit or malfunction due to the
damage of the screws or the GOT.
When mounting the wireless LAN communication unit on the GOT, fit it to the
wireless LAN communication unit interface and tighten the mounting screws
in the specified torque range (0.10 N•m to 0.14 N•m) with a Phillips-head
screwdriver No.1.
Under tightening can cause the GOT to drop, short circuit or malfunction.
Overtightening can cause a drop, failure or malfunction due to the damage of
the screws or unit.
When closing the USB environmental protection cover, fix the cover to the
GOT by pushing the [PULL] mark on the latch firmly to comply with the
protective structure.
Remove the protective film of the GOT.
When the user continues using the GOT with the protective film, the film may
not be removed.
Operate and store the GOT in environments without direct sunlight, high
temperature, dust, humidity, and vibrations.
WARNING
CAUTION
WARNING
CAUTION
[WIRING PRECAUTIONS]
[TEST OPERATION PRECAUTIONS]
[STARTUP/MAINTENANCE PRECAUTIONS]
Be sure to shut off all phases of the external power supply used by the
system before wiring.
Failure to do so may result in an electric shock, product damage or
malfunctions.
Make sure to ground the FG terminal of the GOT power supply section solely
for the GOT (ground resistance: 100 Ω or less, ground cable diameter: 1.6
mm or more).
Not doing so may result in an electric shock or malfunction.
When tightening the terminal screws, use a Phillips-head screwdriver No.2.
Terminal screws which are not to be used must be tightened always at torque
0.5 N•m to 0.8 N•m.
Otherwise there will be a danger of short circuit against the solderless
terminals.
Use applicable solderless terminals and tighten them with the specified
torque. If any solderless spade terminal is used, it may be disconnected
when the terminal screw comes loose, resulting in failure.
Correctly wire the GOT power supply section after confirming the rated
voltage and terminal arrangement of the product.
Not doing so can cause a fire or failure
Tighten the terminal screws of the GOT power supply section in the specified
torque range (0.5 N•m to 0.8 N•m). Undertightening can cause a short circuit
or malfunction. Overtightening can cause a short circuit or malfunction due to
the damage of the screws or the GOT.
Exercise care to avoid foreign matter such as chips and wire offcuts entering
the GOT. Not doing so can cause a fire, failure or malfunction.
The module has an ingress prevention label on its top to prevent foreign
matter, such as wire offcuts, from entering the module during wiring.
Do not peel this label during wiring. Before starting system operation, be sure
to peel this label because of heat dissipation.
Plug the communication cable into the GOT interface or the connector of the
connected unit, and tighten the mounting screws and the terminal screws in
the specified torque range. Undertightening can cause a short circuit or
malfunction. Overtightening can cause a short circuit or malfunction due to
the damage of the screws or unit.
Before performing the test operations of the user creation monitor screen
(such as turning ON or OFF bit device, changing the word device current
value, changing the settings or current values of the timer or counter, and
changing the buffer memory current value), read through the manual
carefully and make yourself familiar with the operation method.
During test operation, never change the data of the devices which are used to
perform significant operation for the system.
False output or malfunction can cause an accident.
When power is on, do not touch the terminals.
Doing so can cause an electric shock or malfunction.
Correctly connect the battery connector.Do not charge, disassemble, heat,
short-circuit, solder, or throw the battery into the fire.Doing so will cause the
battery to produce heat, explode, or ignite, resulting in injury and fire.
Before starting cleaning or terminal screw retightening, always switch off the
power externally in all phases. Not switching the power off in all phases can
cause a unit failure or malfunction. Undertightening can cause a short circuit
or malfunction. Overtightening can cause a short circuit or malfunction due to
the damage of the screws or unit.
Do not disassemble or modify the unit.
Doing so can cause a failure, malfunction, injury or fire.
Do not touch the conductive and electronic parts of the unit directly.
Doing so can cause a unit malfunction or failure.
The cables connected to the unit must be run in ducts or clamped.
Not doing so can cause the unit or cable to be damaged due to the dangling,
motion or accidental pulling of the cables or can cause a malfunction due to a
cable connection fault.
When unplugging the cable connected to the unit, do not hold and pull from
the cable portion. Doing so can cause the unit or cable to be damaged or can
cause a malfunction due to a cable connection fault.
Do not drop the module or subject it to strong shock. A module damage may
result.
Doing so may damage the battery, causing the battery fluid to leak inside the
battery. If the battery is dropped or given an impact, dispose of it without
using.
Before touching the unit, always touch grounded metals, etc. to discharge
static electricity from human body, etc.
Not doing so can cause the unit to fail or malfunction.
Use the battery manufactured by Mitsubishi Electric Corporation.
Use of other batteries may cause a risk of fire or explosion.
Dispose of used battery promptly.
Keep away from children.Do not disassemble and do not dispose of in fire.
Be sure to shut off all phases of the external power supply before replacing
the battery or using the dip switch of the terminating resistor. Not doing so
can cause the unit to fail or malfunction by static electricity.
WARNING
CAUTION
WARNING
WARNING
CAUTION
[TOUCH PANEL PRECAUTIONS]
[PRECAUTIONS WHEN THE DATA STORAGE IS IN
USE]
[PRECAUTIONS FOR USE]
[PRECAUTIONS FOR REMOTE CONTROL]
[PRECAUTIONS FOR EXCLUSIVE AUTHORIZATION CONTROL]
[DISPOSAL PRECAUTIONS]
For the analog-resistive film type touch panels, normally the adjustment is not
required.
However, the difference between a touched position and the object position
may occur as the period of use elapses.
When any difference between a touched position and the object position
occurs, execute the touch panel calibration.
When any difference between a touched position and the object position
occurs, other object may be activated.
This may cause an unexpected operation due to incorrect output or
malfunction.
If the SD card is removed from drive A of the GOT while being accessed by
the GOT, the GOT may stop processing data for about 20 seconds.The GOT
cannot be operated during this period. The functions that run in the
background including a screen updating, alarm, logging, scripts, and others
are also interrupted. Since this interruption makes an impact to the system
operation, it might cause failure.After checking the light off of SD card access
LED, remove the SD card.
If the data storage is removed from the GOT while being accessed by the
GOT, the data storage and files may be damaged. Before removing the data
storage from the GOT, check the SD card access LED, system signal, or
others to make sure that the data storage is not accessed.
Turning off the GOT while it accesses the SD card results in damage to the
SD card and files.
When inserting a SD card into the GOT, make sure to close the SD card
cover. Failure to do so causes the data not to be read or written.
When removing the SD card from the GOT, make sure to support the SD card
by hand as it may pop out.Failure to do so may cause the SD card to drop
from the GOT, resulting in a failure or break.
When inserting a USB device into a USB interface of the GOT, make sure to
insert the device into the interface firmly.Failure to do so may cause the USB
device to drop from the GOT, resulting in a failure or break
Before removing the USB device from the GOT, follow the procedure for
removal on the utility screen of the GOT. After the successful completion
dialog is displayed, remove the USB device by hand carefully. Failure to do
so may cause the USB device to drop from the GOT, resulting in a failure or
break.
Do not touch the edges of the touch panel (display section) repeatedly.
Doing so may result in a failure.
Do not turn off the GOT while data is being written to the storage memory
(ROM) or SD card.
Doing so may corrupt the data, rendering the GOT inoperative.
Remote control is available through a network by using GOT functions,
including theSoftGOT-GOT link function, the remote personal computer
operation function, the VNC server function, and the GOT Mobile function.
If these functions are used to perform remote control of control equipment,
the field operator may not notice the remote control, possibly leading to an
accident.
In addition, a communication delay or interruption may occur depending on
the network environment, and remote control of control equipment cannot be
performed normally in some cases.
Before using the above functions to perform remote control, fully grasp the
circumstances of the field site and ensure safety.
Make sure to fully understand the GOT network interaction function before
using this function to control the authorization among pieces of equipment to
prevent simultaneous operations.
The exclusive authorization control of the GOT network interaction function
can be enabled or disabled for each screen. (For all screens, the exclusive
authorization control is disabled by default.)
Properly determine the screens for which the exclusive authorization control
is required, and set the control by screen.
A screen for which the exclusive authorization control is disabled can be
operated simultaneously from pieces of equipment. Make sure to determine
the operation period for each operator, fully grasp the circumstances of the
field site, and ensure safety to perform operations.
When disposing of this product, treat it as industrial waste.
When disposing of batteries, separate them from other wastes according to
the local regulations.
(Refer to the GOT2000 Series User’s Manual (Hardware) for details of the
battery directive in the EU member states.)
CAUTION
WARNING
CAUTION
CAUTION
WARNING
WARNING
CAUTION
[TRANSPORTATION PRECAUTIONS]
Manual
The following shows manuals relevant to this product.
For detailed manuals and relevant manuals, refer to the Help or the PDF
manuals stored in the DVD-ROM for the drawing software used.
The latest manuals are also available from MITSUBISHI ELECTRIC FA Global
Website (http://www.MitsubishiElectric.com/fa/).
Compliance with the new China RoHS directive
GOT 相关的基于 “ 电器电子产品有害物质限制使用管理办法 ” 要求的表示方法
含有有害 6 物质的名称、含有量、含有部件
本产品中所含有的有害 6 物质的名称、含有量、含有部件如下表所示。
产品中有害物质的名称及含量
本表格依据 SJ/T11364 的规定编制。
○ : 表示该有害物质在该部件所有均质材料中的含量均在 GB/T26572 规定的限量要
求以下。
×
: 表示该有害物质至少在该部件的某一均质材料中的含量超出 GB/T26572 规定的
限量要求。
Referenced Standard: GB/T15969.2
(Requirement of Chinese standardized law)
Before using the GOT
Connect the connector of the GOT to the connector of the battery.
Refer to the GOT2000 Series User’s Manual (Hardware) for the connection
instructions.
For details on the GOT specifications, installing instructions, wiring, maintenance
and inspection, or checking procedure for the version and the compatible standard,
refer to the GOT2000 Series User’s Manual (Hardware).
When transporting lithium batteries, make sure to treat them based on the
transport regulations.
(Refer to the GOT2000 Series User’s Manual (Hardware) for details of the
regulated models.)
Make sure to transport the GOT main unit and/or relevant unit(s) in the
manner they will not be exposed to the impact exceeding the impact
resistance described in the general specifications of this manual, as they are
precision devices.
Failure to do so may cause the unit to fail.
Check if the unit operates correctly after transportation.
When fumigants that contain halogen materials such as fluorine, chlorine,
bromine, and iodine are used for disinfecting and protecting wooden
packaging from insects, they cause malfunction when entering our products.
Please take necessary precautions to ensure that remaining materials from
fumigant do not enter our products, or treat packaging with methods other
than fumigation (heat method).
Additionally, disinfect and protect wood from insects before packing products.
Manual name
Manual number (Model code)
GOT2000 Series User’s Manual (Hardware)
SH-081194ENG (1D7MJ5)
GOT2000 Series User’s Manual (Utility)
SH-081195ENG (1D7MJ6)
Note: This symbol mark is
for China only.
部件名称
有害物质
铅
(Pb)
汞
(Hg)
镉
(Cd)
六价铬
(Cr(VI))
多溴联苯
(PBB)
多溴二苯醚
(PBDE)
电路板组件
×
○
○
○
○
○
树脂壳体、电缆、膜材
○
○
○
○
○
○
钣金部件、螺丝等金属部件
×
○
○
○
○
○
CAUTION
Packing List
The GOT product package includes the following:
1. FEATURES
(1) Abundant standard equipment
• Variety of connection with FA devices
• SD card interface compatible with the SDHC card having a large capacity
and allowing high-speed communication
• Connection with various peripheral devices with the USB host
• One sound output interface
• Two Ethernet interfaces
(2) Improved usability
• Abundant troubleshooting
• Easy and clear screen creation
• PC-like operation screen
• Support for the vertical installation
(3) Enhanced compatibility with Mitsubishi FA devices
(4) LED backlight
2. Part Names and Settings
The following shows the part names for GT2510 and GT2507.
Description
Quantity
GT25 Wide Model
1
Battery (GT11-50BAT) (Attached to the GOT)
1
Installation fitting
4
GT25 Wide Model General Description (This manual)
1
GT25 ワイドモデル本体概要説明書
1
No.
Name
Description
1)
Display screen
Displays the utility and the user-created screen.
2)
Touch panel
For operating the touch switches in the utility and the user-
created screen
3)
USB interface (Device
/Front face)
For connecting a personal computer (connector type: Mini-
B)
4)
POWER LED
Lit in blue
: Power is properly supplied.
Lit in orange
: Screen saving
Blinks in orange/blue
: Backlight failure
Not lit
: Power is not supplied
5)
Unit installation fitting
Mounting fixtures for fixing the GOT to the control panel
6)
Reset switch
Hardware reset switch
7)
Installation switch
Used for OS installations at the GOT startup
8)
SD card access LED
Lit: SD card mounted
Blinking: SC card accessed
No lit: SD card not mounted or SD card mounted
(removable)
9)
SD card interface
For installing a SD card
10) SD card cover
With a switching function for accepting and stopping the
access to the SD card
When the cover is opened : Access is prohibited
When the cover is closed : Access is allowed
GT2510
1)2)
3)
21)
14)
15)
20)
18)19) 17)
5)
5)
5)
5)
4)
7)
23)
10)
8)
11)12)
9)
6)
22)
16)
13)
24)
GT2507
1)2)
3)
21)
14)
15)
20)
18)19) 17)
5)
5)
5)
5)
4)
7)
23)
10)
8)
11)12)
9)
6)
22)
16)
13)
24)
3. Specifications
3.1 General Specifications
*1: The operating ambient temperature includes the temperature
inside the
enclosure of the control panel to which the GOT is
installed.
La température ambiante de fonctionnement inclut la température à l'intérieur
du boîtier du tableau de commande sur lequel le GOT est installé.
*2: Do not use or store the GOT under pressure higher than the atmospheric
pressure of altitude 0 m (0ft.).
Failure to observe this instruction may cause a malfunction.
When an air purge is made inside the control panel by adding pressure, there
may be a clearance between the surface sheet and the screen making it difficult
to use the touch panel, or the sheet may come off.
*3: This indicates the section of the power supply to which the equipment is
assumed to be connected between the public electrical power distribution
network and the machinery within the premises.
Category II applies to equipment for which electrical power is supplied from
fixed facilities.
The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V.
*4: This index indicates the degree to which conductive material is generated in the
environment where the equipment is used.
In pollution degree 2, only non-conductive pollution occurs but temporary
conductivity may be produced due to condensation.
11) Battery holder
Houses the battery
12)
Terminating resistor
setting switch
(Inside cover)
For switching on and off of the terminating resistor for the
RS-422/485 communication port (Default (Off))
13)
Wireless LAN
communication unit
interface
For installing a communication unit
14)
USB interface
(Host/Back face)
For connecting a USB mouse, a USB keyboard, or a USB
barcode reader, and transferring or saving data
(connector type: TYPE-A)
15)
Hole for attaching a
cable clamp
For attaching a cable clamp to prevent the USB cable or the
sound output cable from being accidentally pulled out
(Recommended product: RSG-130-V0 made by
KITAGAWA INDUSTRIES CO.,LTD)
16)
Vertical installation
arrow mark
For the vertical installation, install the GOT so that the arrow
points upward.
17) Power terminal
Power input terminal, FG terminal
18)
Ethernet interface
(port 1)
For communicating with a controller or connecting a
personal computer (connector type: RJ-45 (modular jack))
19)
Ethernet interface
(port 2)
20)
Ethernet
communication status
LED
SD/RD LED ON
: Data sent or received
SD/RD LED OFF: Data not sent or received
SPEED LED ON
: Communicating at 100 Mbps
SPEED LED OFF: Communicating at 10 Mbps or
disconnected
21) RS-422/485 interface
For communicating with a controller (Connector type: D sub
9-pin (female))
22) RS-232 interface
For communicating with a controller (Connector type: D sub
9-pin (male))
23) Sound output interface
For outputting sounds (applicable plug: Φ3.5 stereo mini-
plug (3-prong))
24) Rating plate
-
Item
Specifications
Operating ambient
temperature
*1
Température
ambiante de
fonctionnement
*1
0 to 55
0 à 55
Storage ambient
temperature
-20 to 60
Operating ambient
humidity
10 to 90% RH, non-condensing
Storage ambient
humidity
10 to 90% RH, non-condensing
Vibration resistance
Compliant
with JIS B
3502 and
IEC
61131-2
Frequency
Acceleration
Half-
amplitude
Sweep
count
Under
intermittent
vibration
5 to
8.4 Hz
-
3.5 mm
10 times
each in X,
Y and Z
directions
8.4 to
150 Hz
9.8 m/s
2
-
Under
continuous
vibration
5 to
8.4 Hz
-
1.75 mm
-
8.4 to
150 Hz
4.9 m/s
2
-
Shock resistance
Compliant with JIS B 3502 and IEC 61131-2 147 m/s
2
(15G),
3 times each in X, Y and Z directions
Operating
atmosphere
No greasy fumes, corrosive gas, flammable gas, excessive
conductive dust, and direct sunlight (Same as storage atmosphere)
Operating altitude
*2
2000 m (6562 ft) max.
Installation location
Inside control panel
Overvoltage
category
*3
II or less
Pollution degree
*4
2 or less
Cooling method
Self-cooling
Grounding
Grounding with a ground resistance of 100 Ω or less by using a ground
cable that has a cross-sectional area of 2 mm
2
or more.
If impossible, connect the ground cable to the control panel.
No.
Name
Description
3.2 Power Supply Specifications
The following indicates the power supply specifications for GT25 wide model
.
3.3 External Dimensions
Point
Refer to the GOT2000 Series User’s Manual (Hardware) for details on the performance
specifications of each GOT.
Note
Operation at momentary failure
• If an instantaneous power failure occurs in the power supply and continues for more
than the permissible period, the GOT will be reset.
• Make sure to power on the unit more than 5 seconds after power-off.
Item
Specifications
GT2510-WXTSD,
GT2510-WXTBD
GT2507-WTSD,
GT2507-WTBD
Power supply voltage
DC24V (+25%, -20%)
Power
consum
ption
maximum load
16 W or less
16 W or less
Stand alone
9 W
9 W
Stand alone with
backlight off
5 W
5 W
Inrush current
59 A or less (2 ms, operating ambient temperature 25,
maximum load)
Allowable momentary power
failure time
5 ms or less
Noise immunity
500 Vp-p noise voltage, 1 s noise width (when
measuring with a noise simulator under 25 to 60 Hz
noise frequency)
Dielectric withstand voltage
350 VAC for 1 minute across power terminals and earth
Insulation resistance
10 M or more across power terminals and earth by a 500
V DC insulation resistance tester
Applicable wire size
0.75[mm
2
] to 2[mm
2
]
Applicable solderless terminal
Solderless terminal for M3 screw RAV1.25-3, V2-S3.3,
V2-N3A, FV2-N3A
Applicable tightening torque
(Terminal block terminal screw)
0.5[N•m] to 0.8[N•m]
GT2507
142(5.59)
180(7.09)
142(5.59)
133(5.24)
48(1.89)
6
GT2510
203(7.99)
194(7.64)
185(7.28)
10
10
48(1.89)
6
243(9.57)
10
10
203(7.99)
252(9.92)
145(5.71)
189(7.44)
24.5
Unit : mm (inch)
(0.39)
(0.39)
(0.39)
(0.24)
(0.96)
(0.39)
(0.24)