Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
DATE
B SERIES
SUPERSEDES DRAWING NO.
12 - 20 - 23
3500
11 - 4 - 22
35SXC-1
Page 1 of 2.
For heat options; see page 2.
Dimensions are in inches (mm).
FAN POWERED TERMINAL UNIT W/ EPIC ECM MOTOR
STEALTH XC • SERIES FLOW • SUPER QUIET
EXPOSED CEILING APPLICATIONS
VARIABLE VOLUME FAN OPERATION
MODELS: 35SXC, 35SWXC & 35SEXC • UNIT SIZES 1, 3 & 5
W
2
MULTI-POINT
FLOW SENSOR
DRIVESHAFT
PRIMARY
PRIMARY
AIR
DIA. =
NOM. –
1/8" (3)
14" (356)
5 1/2"
(140)
H
2
H -
1" (25) H
HINGED FAN
CONTROLS
ENCLOSURE
OPTIONAL
PRIMARY
AIR VALVE
CONTROLS
ENCLOSURE
11"
(279)
L
FAN
1" (25)
B
DW
DH
IW
W
OPTIONAL
INDUCED
AIR FILTER
1" (25)
AIR
INDUCED
AIR
IH
5 3/4"
(146)
14" (356)
HINGED FAN
CONTROLS ENCLOSURE
6 3/4"
(171)
W2
5 3/4"
(146)
15"
(381)
OPTIONAL
90° FN2
CONTROLS
ENCLOSURE
Dimensional Data
STANDARD FEATURES:
• 18 ga. (1.31) galvanized steel
channel frame with 20 ga. (1.00)
casing components.
• 16 ga. (1.61) galvanized steel
inclined opposed blade damper.
45° rotation. CW to close.
• Multi-point averaging Diamond
Flow sensor.
Supplied with
balancing tees.
• Full size access panels on 3
sides.
•
Steri-liner insulation. 13/16"
(21) thick, 4 lb./sq. ft. (64 kg/m
3
)
density rigid fiberglass with alum.
FSK facing. Meets requirements
of NFPA 90A and UL 181.
• Stealth XC tuned inlet silencer.
Perforated galvanized steel liner
with fiberglass acoustic media.
•
Single point electrical
connection.
• Discharge opening for flanged
duct connection.
• Full primary air valve low voltage
NEMA 1 type enclosure for factory
mounted DDC controls.
• Controls mounted as standard
on RH side as shown. Terminals
ordered with LH controls (optional)
are inverted and discharge duct
hanging elevation will therefore
change.
•
Ultra-high efficiency ECM
fan motor. EPIC fan volume
controller.
OPTIONS:
Digital Controls:
q
Factory mounted (supplied by
others)
q
Field mounted (supplied by
others)
Model 35SXC • Basic Unit
Electrical Data
Unit
Size
EPIC ECM Motor FLA
Motor
HP
120V 208V 240V 277V
1
*
2.1
1.4
1.3
1.2
3
*
4.8
3.4
3.1
3.0
5
*
10.5 6.8
6.4
6.2
*
The ECM is a variable horsepower motor.
Refer to Selectworks schedule for actual
power consumption.
FLA = Full load amperage. All motors are
single phase/60 Hz.
Unit
Size
Inlet
Size
W
W2
H
L
B
Induced Air
Inlet
IW x IH
Outlet
Discharge
DW x DH
Filter
Size
1
4, 5, 6, 8
(102, 127, 152, 203)
20
(508)
41
(1041)
14
(356)
36
(914)
6
(152)
6 x 14
(152 x 356)
8 1/8 x 4 1/4
(206 x 108)
6 x 14
(152 x 356)
3
6, 8, 10, 12
(125, 203, 254, 305)
26
(660)
47
(1194)
18
(457)
41
(1041)
7
(178)
6 x 18
(152 x 457)
9 1/8 x 10 1/2
(232 x 267)
6 x 18
(152 x 457)
5
10, 12, 14
(254, 305, 356)
26
(660)
53
(1346)
20
(508)
55
(1397)
7
(178)
12 x 20
(305 x 508)
13 1/8 x 15 5/8
(333 x 397)
12 x 20
(305 x 508)
Terminal Liner:
q
Steri-liner
q
Steri-liner + Perforated metal
Silencer Liner:
q
Fiberglass acoustic media
q
Steri-Liner/Polymer film
Other:
q
Left-hand controls location
q
Toggle disconnect switch
q
Fan unit fusing
q
24/24V Isolation transformer
q
Cross Flow Sensor
q
1" (25) Throwaway filter
q
2" (51) Filter rack only
q
Hanger brackets
q
1/4-turn fasteners (access
panel)
q
FN2 90° Line Voltage
Enclosure
q
FN3 Remote Line Voltage
Controls Enclosure
(See submittal FN3)
q
Du
s
t tight enclosure seal
q
Remote user disconnect
q
Special features:
____________.