SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
APPLICATION:
'Smart' Brushless DC motor technology provides continuous
monitoring, automatic compensation and precise control and
maintenance of discharge airflow regardless of discharge static
pressure variations incurred by a HEPA filter. Available in three
unit sizes, suitable for 200 – 3000 cfm (94 – 1416 l/s) zone
designs with up to a maximum total external discharge static
pressure of 1.0" w.g. (250 Pa).
Ideally suited to clean room applications such as hospital
isolation wards, operating rooms, pharmaceutical and
biotechnology manufacturing and research facilities.
DESCRIPTION:
• 18 ga. (1.31) galv. steel channel frame with 20 ga. (1.00)
casing components.
• 16 ga. (1.61) galvanized steel inclined opposed blade primary
air damper. 45° rotation. CW to close.
• Multi-point averaging 'Diamond' flow sensor.
• Low leakage access panels on all 4 sides.
• Ultra Energy efficient ECM fan motor with overload protection
and Nailor EPIC volume controller.
• Solid metal 'IAQ' liner. Meets requirements of NFPA 90A and
UL 181.
• Single point electrical connection.
• Discharge opening for flanged duct connection.
• Controls mounted as standard on RH side as shown. Terminals
ordered with LH controls (optional) are inverted and discharge
duct hanging elevation will therefore change.
OPTIONS:
q
Fan unit fusing.
q
Toggle disconnect switch.
q
Hanger brackets.
q
Left hand control location option.
q
Special features ______________________________ .
Page 1 of 2.
Dimensions are in inches (mm).
DATE
B SERIES
SUPERSEDES DRAWING NO.
3 - 25 - 17
3500
2 - 8 - 16
35S-CVP-1
FAN POWERED PRESSURIZATION TERMINAL UNIT
EPIC ECM MOTOR
SERIES FLOW • CONSTANT VOLUME
MODELS: 35S-CVP, 35SW-CVP AND 35SE-CVP
UNIT SIZES 3 & 5
OPTIONAL
PRIMARY
AIR VALVE
CONTROLS
ENCLOSURE
H
H -
1" (25)
PRIMARY
AIR
6"
(152)
H
2
11"
(279)
L
W
FAN
5 3/4"
(146)
DRIVESHAFT
W
2
1" (25)
DH
B
DW
DIA. =
NOM. -
1/8" (3)
PRIMARY
AIR
14" (356)
14" (356)
MAX.
MULTI-POINT
FLOW
SENSOR
HINGED FAN
CONTROLS
ENCLOSURE
Model 35S-CVP
Dimensional Data
Electrical Data
*
The EPIC ECM is a variable horsepower motor.
Refer to Selectworks schedule for actual power
consumption.
FLA = Full load amperage.
All motors are single phase/60 Hz.
Unit
Size
EPIC ECM Motor FLA
Motor HP 120V
208V
240V
277V
3
*
4.8
3.3
3.2
3.1
5
*
9.6
6.2
5.9
5.8
Unit
Size
Inlet
Size
W
H
L
B
Outlet Discharge
DW x DH
3
6, 8, 10 (152, 203, 254) 18 (457) 18 (457) 36 (914) 3 1/2 (89)
9 1/4 x 10 1/2
(235 x 267)
5
8, 10, 12 (203, 254, 305) 26 (660) 18 (457) 41 (1041) 5 (127)
13 1/4 x 11 1/2
(337 x 292)