background image

  

11 of 32

www.NabcoEntrances.com

SwingandFoldDoorOpusControlWiringandProgrammingInstallationManual

Rev. 8-11-21 

P/N C-00139

SECTION 6.1: Copy Data from Type 2 (Master Control) to Type 1 (Slave Control) 

1. Go to the Type 2 (Master Control). 
2. Push the Rotary Dial in for 2 seconds, release.
3. Push the Rotary Dial in again 2 seconds for (Copy Data (YES or NO).
4. Upon exiting the (Copy Data (SimPair) screen will display. 

1. Turn the Rotary Dial to highlight (YES)
2. Briefly press down on the Rotary Dial to select.

a.  Programming/Settings made to the Type 2 Control will automatically copy to the Type 1 Control.

DN 2312

Copy Data (SimPair)?

                          No

Yes

Figure 7 

Programming/Settings for Sim Pair Controls

SECTION 6.2: Resetting a Type 2 Control back to a Type 1 Control

There can never be (2) Master Controls, or (2) Slave Controls. There must always be (1) Type 1 Control, and (1) Type 2 Control.

1. Go to the Control without activation devices connected to it. This will be the Type 1 (Slave Control). Perform a Factory Reset.

1. Press down on the Rotary Dial until the next screen is displayed.
2. Turn the Rotary Dial clockwise to highlight (Reset to Default Set). 
3. Briefly press down on the Rotary Dial. Enter the passcode: 0045.

1. Turn the Rotary Dial clockwise to highlight a preferred number, then briefly press down. 

2. Repeat until the passcode is complete.

4. Briefly press down on the Rotary Dial to display the (Setting Category) Screen.

DN 2271

Passcode

Reset to Default Set

Stroke Learning

Yes   No

Reset to Default Set

0

If you don’t know

the passcode, 

Keep Pushing Switch, 

Return to normal mode

11

20

10

12

Type: 1

GT710 Swing

Status:

Slow Closing

Error:

-----

Ac va on:

IN EXT

Posi on:

> > > > > > >

Other:

BA  6B  SWL

Push and Hold Dial

Go to Se  ng Mode

Copy Data (SimPair)?

               Yes    

No

11

20

10

12

Type: 2

GT710 Swing

Status:

Slow Closing

Error:

-----

Ac va on:

IN EXT

Posi on:

> > > > > > >

Other:

BA  6B  SWL

Push and Hold Dial

Go to Se  ng Mode

Fully Closed

Fully Closed

Figure 8 

Reset Control

2. Turn the Rotary Dial to highlght (Optional Setting). Briefly press down on the Rotary Dial. Turn the Rotary Dial to highlight 

(Simpair Setting). Briefly press down on the Rotary Dial to select.

3. Turn the Rotary Dial to highlight the desired Paired Setting. Briefly press down on the Rotary Dial to select.
4. Press and hold the Rotary Dial until the (Setting Category) screen is displayed.     
5. Press and hold the Rotary Dial until the (Copy Data) Screen is displayed. 
6. Turn the Rotary Dial to select (NO). 
7. Briefly press down on the Rotary Dial. The Type 2 (Master Control) will automatically reset to the Type 1 (Slave Control).

Summary of Contents for C-00139

Page 1: ...N 2 4 QR Code Links 4 CHAPTER 3 GETTING STARTED 5 SECTION 3 1 Features 5 SECTION 3 2 Wiring 5 SECTION 3 3 General Specifications 5 SECTION 3 4 Electrical Specifications 5 SECTION 3 5 Output Power Guid...

Page 2: ...gs 18 CHAPTER 10 SHUT OFF CIRCUIT BREAKER 19 CHAPTER 11 SWING DOOR WIRING DIAGRAMS 19 SECTION 11 1 120 VAC General Wiring 19 SECTION 11 2 Motor Wiring 20 SECTION 11 3 Other 20 SECTION 11 4 Activation...

Page 3: ...isconnect all power to the junction box prior to making any electrical connections Failure to do so may result in serious personal or fatal injury When uncertain whether power supply is disconnected a...

Page 4: ...be installed within new Swing Sliding and Folding Door Units plus X Existing swing sliding and folding doors using Analog Magnum or U01 U19 controls works with encoders or microswitches X Existing sl...

Page 5: ...cation Description Temperature Range 13 degrees to 140 degrees Fahrenheit Motor Type High voltage Brushless Motor with Encoder 115V Number of Signal Inputs 1 x Activation 2 x Door Mode 2 x Safety 1 x...

Page 6: ...mA 50 mA Total 350 mA 350mA does not exceed total current draw An Auxiliary Power Supply does not need to be used SECTION 3 6 The Opus Control for Swing Doors Note The Hold Close feature is enabled w...

Page 7: ...TION 3 10 CAN Bus Communication Used to connect Sim Pair Astragal Sequencing and the NET HT Cable when programming CHAPTER 4 LCD CATEGORY SCREENS Passcode Go to Se ng Menu Stroke Learning Yes No UNIT...

Page 8: ...se refer to Subsection Table 5 The screen above shows the Opus control installed on a GT710 X Error Specifications This screen will only display an Error Code in the event there is an Error Otherwise...

Page 9: ...eset to Default Set If you don t know the passcode Keep Pushing Switch Return to Normal mode 0 0 Short Push Reset to Default Set If you don t know the passcode Keep Pushing Switch Return to Normal mod...

Page 10: ...data Since monitored sensors are only connected to one control Type 2 you don t want the monitoring settings to be copied to the control without sensors connected Type 1 Any changes to one control suc...

Page 11: ...Rotary Dial Enter the passcode 0045 1 Turn the Rotary Dial clockwise to highlight a preferred number then briefly press down 2 Repeat until the passcode is complete 4 Briefly press down on the Rotary...

Page 12: ...lly need to be copied are already established X Door mounted safety sensors should be connected to the control running the door which those sensors apply to X When monitored sensor wiring is different...

Page 13: ...Open time after Door reaches Full Open and activation signal is no longer present Reaction Power 0 7 3 Determines how fast the door reacts to a reactivation when closing Open Recycle Sens 0 7 3 Recycl...

Page 14: ...9 Latch Check LCHK Lockout Angle Back Check BCHK Lockout Angle Available Angle Con nuous Safety Available Angle for Low Energy Door Mount Approach Side Sensor Available Angle Safety with lockout Avail...

Page 15: ...happened Output closes when recycle occurs Electric Strike Lock Set for electric strike functionality N O Electric Magnetic Lock Set for Mag lock functionality N C Air lock Set for Air lock functional...

Page 16: ...ock if equipped Hold Open Mode Holds door in open position Asia Only Do Not Use ANSI does not allow Activation Sensor to be mounted on the swing side of door If activated Opus will ignore the Activati...

Page 17: ...not operating until the problem is fixed Monitoring settings are OFF by default except when used as 1175 Opus Slide in which case standard settings have monitoring enabled SECTION 8 6 History Setting...

Page 18: ...tary Dial 2 Sec 11 20 10 12 Enter Passcode 0045 Clear Recycle Cnt 0045 If you don t know the passcode Keep Pushing Switch Return to Normal mode 11 20 10 12 LEVEL 4 1 Rotate Dial to select History Se n...

Page 19: ...the grounding screw or grounding wire whichever is provided Attention Insert all Incoming 120 VAC Power wires into the pre drilled Electric Service Access Hole located at the left or right side of He...

Page 20: ...tor Fuse SECTION 11 3 Other DN 1333 EXAMPLE OF A PROGRAMMABLE INPUT I O Terminal 8 14 8 BA Breakout Used mainly for sliding door can be used for ON OFF with Swing Doors 9 SQ Sequen al Ac va on Signal...

Page 21: ...DER RADIO RECEIVER ETC WARNING TOTAL POWER OF ALL SENSORS AND POWERED ACTIVATION DEVICES MUST NOT EXCEED 750 MA POWERED ACTIVATION DEVICES Radio Receiver DN 1329 8 12 14 11 13 9 10 N O COM N O COM Ext...

Page 22: ...ensor Card Reader Radio Receiver etc WARNING TOTAL POWER OF ALL SENSORS AND POWERED ACTIVATION DEVICES MUST NOT EXCEED 750 mA NON POWERED ACTIVATION DEVICES Radio Receiver 8 Rocker Switch P N A 00805...

Page 23: ...ation Manual Rev 8 11 21 P N C 00139 SECTION 11 6 Safety without Monitoring DN 1331 2 4 5 1 6 N O COM PWR PWR N O COM PWR PWR N O COM PWR PWR Door Mounted Approach Side Sensor Door Mounted Swing Side...

Page 24: ...t be set to BODYGUARD OUTPUT Please see programming instruc ons for details PWR PWR TEST TEST Door Mounted Approach Side Sensor N O COM PWR PWR TEST TEST N O COM PWR PWR TEST TEST 5 2 4 5 1 2 3 4 6 7...

Page 25: ...DN 1332 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Fail Secure Electric Strike Fail Secure Lock Shown Fail Safe and Mag Locks will use N C instead of N O Power Supply For Electric Strike N O COM N C Varistor M...

Page 26: ...P N A 00805 1 5 6 Door Mounted Approach Side Sensor Door Mounted Swing Side Sensor BLUE 8 12 14 11 13 9 10 1 5 7 2 3 4 6 Ac va on Sensor Overhead Swing Side Sensor if used WARNING TOTAL POWER CONSUMP...

Page 27: ...SENSORS MUST NOT EXCEED 750 MA N O COM PWR PWR N O COM PWR PWR N O COM PWR PWR COM PWR PWR N O Door Mounted Approach Side Sensor Door Mounted Swing Side Sensor 5 2 4 1 2 3 4 6 7 1 5 8 12 14 11 13 9 10...

Page 28: ...P N A 00430 Clear A 70430 Dark Bronze RED BLACK 14 13 12 11 10 9 8 8 WHITE Off Hold Open On Off 14 13 12 11 10 9 8 8 14 BA break out input must be set to N C on the Opus Control is by default Panic L...

Page 29: ...OCK OPEN DELAY TIMER must be set to an appropriate me for the door to unlock before opening LOCK CONDITION must be set to ONE WAY NIGHT ONLY NOTE If the Rocker Switch is not being used Interior Ac va...

Page 30: ...connected Type 1 Any changes to one control such as speed or timing should be entered on the other control manually not copied SECTION 12 1 Switches and Sensors with Monitoring DN 1895 Approach Side A...

Page 31: ...Latch Check Software Revision up to and including 19 Symptom When the door is used manually it closes every time However when the door is activated once in a while it will stop at latch check and not...

Page 32: ...rror MPU Clock error MPU Interrupt error MPU SW reset error MPU HW WDT error MPU EEPROM error No Motor Motor disconnection error Check all connections between the Control and Motor Thrml Warning Therm...

Reviews: