
Installation
operation and installation manual
zappi
47
Advanced Installation Options
Load Balancing / Current Limiting / Load Curtailment
CTs can also be used to limit the current drawn by
myenergi
devices to avoid overloading circuits; this is referred
to as load balancing or load curtailment. There are four different ways to limit current and they can be used alone
or combined for more complex situations. See the table below:
Function
Operation
Example
Device Limit
Sets a maximum current that can be
drawn by the device (e.g.
zappi
). The
current will not be exceeded even
during Boost or Fast charge.
A
zappi
is wired to a 20A supply (rather than 32A).
The maximum current drawn will not exceed the set
limit (e.g. 20A)
Grid Limit
Sets the limit that can be drawn from
the
grid
connection
(i.e.
the
maximum import current). The
zappi
and any other linked
myenergi
device, will limit the current they
draw if there is a danger of exceeding
the set Grid Limit.
A property may have a grid supply limit of 65A.
Several appliances are on, so the property is
consuming 12kW (52A). The user wants to charge in
FAST mode. Without the Grid Limit set, the total
consumption would exceed the allowed import
current and trip the supply or blow a fuse. However,
with a Grid Limit setting of 60A,
zappi
would
temporarily limit the charging current to 8A (about
1.8kW) and the maximum allowed import current
would not be exceeded.
Group Limit
(internal CT)
Sets the combined current limit for
several
myenergi
devices.
A property has a large PV array, a swimming pool
and two
zappi
s. The supply to the
zappi
s is only
rated at 40A so to be safe a Group Limit of 40A is
set.
Group Limit
(with
external CT)
Sets the combined current limit for
several
myenergi
devices that are
sharing a supply with another large
appliance.
A
zappi
is installed in a garage which also has a
washer and a dryer (2.5kW each). The garage has a
supply of 32A coming from the main consumer unit
in the house. If all appliances were on together and
no limit had been set the total current would exceed
the maximum supply current. By setting the Group
Limit to 32A an overload will be avoided.
Three-Phase Systems
If the installation has a three-phase supply, you can use the 3 CT connectors either directly connected to the
zappi
(hard wired) or a
harvi
device (wireless – optional). We recommend you use one CT per phase; this will allow the
zappi
to show the total grid import and export figures rather than just one of the phases.
If all three phases are monitored then it is also possible to net the export power across phases, to do this, enable
Net Phases in the Supply Grid menu see
Supply Grid – Net Phases
(page 24). This allows the
zappi
to use surplus
power from any phase and not just the phase which the
zappi
is installed on. However, you must be sure that the
electricity is metered in such a way as to allow this.
For a three phase
zappi
, Net Phases should be turned on.