Carefully unscrew nozzle from nozzle fitting. Blow compressed air through nozzle orifice to free it from 

dirt. Replace nozzle if necessary. 

Ignition Electrodes 

Clean, adjust and if necessary replace ignition electrode. For electrode gaps see Fig. 4-5 (dimensions 

in mm). 

      Fig.4  

Fig.5 

Fuel pump pressure adjustment (Fig. 6) 

The fuel pressure is factory set and must be checked and adjusted by qualified 

technicians only. Tampering with the unit may be dangerous. 

Remove pressure gauge cap (P). Connect a pressure gauge on the pressure measuring port on pump. 

Start heater and read fuel pressure value. If necessary adjust pressure to the correct value turning the 

adjusting screw (P1) clockwise to increase, anticlockwise to decrease the pressure: 

Fig.6 

Air collar 

adjustment (Fig. 7) 

The air collar position is factory set and must be checked and adjusted by qualified technicians 

only. Tampering with the unit may be dangerous. 

Pump Pressure (bar) 

9.5 

10.0 

M1.0.WD340.EN

Summary of Contents for BGO-100A-16-F

Page 1: ...Instruction Manual Diesel Kerosene Heater WD340 M1 0 WD340 EN Please read and keep for future reference...

Page 2: ...ranty or representation for any particular purposes The information is offered in good faith and with the understanding that any use of the units or accessories in breach of the directions and warning...

Page 3: ...EN INCORRECTLY USED E G INDOORS WITHOUT ADEQUATE AIR CIRCULATION OR IF NOT PROPERLY WORKING CO POISONING MAY LEAD TO DEATH GENERAL HAZARD WARNING FAILURE TO COMPLY WITH THE PRECAUTIONS AND INSTRUCTION...

Page 4: ...et Weight kg 40 8 Length mm 1215 Width mm 580 Height mm 705 Tank Capacity l 69 Operating range h 7 Standard Accessories Fuel gauge yes Handle 1 Ambient thermostat built in Malfunction detection signal...

Page 5: ...of at least 25 cm kW equally distributed between floor and high level with a minimum of 250 cm BGO 100A 16 F Minimum Opening Size 2500 cm Only install the heater in normal upright position Do not pla...

Page 6: ...FF O position The post ventilation phase will cool down the combustion chamber for 90 seconds Unplug the unit when not used for a long time Never disconnect the heater from mains to stop it while in o...

Page 7: ...er into the heater Never use solvents gasoline toluene and similar aggressive chemicals to clean the heater The following checks BY QUALIFIED PERSONNEL ONLY are recommended before every seasonal use F...

Page 8: ...usted by qualified technicians only Tampering with the unit may be dangerous Remove pressure gauge cap P Connect a pressure gauge on the pressure measuring port on pump Start heater and read fuel pres...

Page 9: ...e setting pressure on fuel pump Fig 6 This setting adjustment can be necessary to prevent excessive smoke emission due to lack of Oxygen Fig 7 Electrical Inspect cables electrical parts and connection...

Page 10: ...ged Clean nozzle blowing compressed air replace if necessary Fuel viscosity increased at low temperature Mix Diesel with 10 20 kerosene Heater starts but combustion is not good Insufficient airflow in...

Reviews: