2. Electrical maximum values
Not intrinsically safe electric circuits:
Not intrinsically supply circuit
(contacts d/z2, d/z4)
Voltage
DC
19 ... 30
V
AC
18 … 28
V
Max. voltage
Um
AC/DC
250
V
not intrinsically safe RS485-interface circuit
(contacts b16, b18)
not intrinsically safe RS232-interface circuit
(connection front socket)
Voltage
DC
6
V
Current intensity
100
mA
Max. voltage
Um
AC/DC
48
V
not intrinsically safe relay contact circuit
(contacts d/z6, d8, d10/12, z8/10, d14, z12/14)
Voltage
DC
30
V
Current intensity
1
A
Or
Voltage
AC
125
V
Current intensity
0.5
A
Max. voltage
Um
AC/DC
125
V
not intrinsically safe digital output circuit
(contacts d/z16 and d/z18)
Voltage
DC
28
V
Current intensity
50
mA
Max. voltage
Um
AC/DC
125
V
not intrinsically safe analog output circuit
(contacts d/z 20)
Voltage
DC
28
V
Current intensity
50
mA
Max. voltage
Um
AC/DC
125
V
Intrinsically safe electric circuits:
Pt-100/slide-wire sensor input circuit (contacts d/z28 and d/z30)
in the explosion protection EEx ia IIC
(MTP200ia-E)
or
EEx ib IIC
(MTP200ib-E)
Voltage
Uo
DC
12
V
Current intensity
Io
6.5
mA
Power
Po
10
mW
Max. outer capacity
Co
1.2
µF
Max. outer inductivity
Lo
700
mH
Input circuit for thermocouple/mV
(contacts d/z32)
in the explosion protection EEx ia IIC
(MTP200ia-E)
or
EEx ib IIC
(MTP200ib-E)
Voltage
Uo
DC
6
V
Current intensity
Io
0.7
mA
Power
Po
1.1
mW
Max. outer capacity
Co
10
µF
Max. outer inductivity
Lo
1000
mH