02/2014
_____________________________________________________________________________________________________________________
35
6.6.1.
Differentiated gradient alarm and the parameter settings
1. Example:
Alarm value
= 40 °C
Alarm type
= Gradient-MAX + MIN-alarm
Time interval
= 60 s (20 samples in 60s)
Temp
(°C)
40
Start
60
3
Time (s)
MAX-alarm
MIN-alarm
Every time interval contains 20 samples. The minimum pulse duration at
the alarm output is 0.05 x 60 s = 3 s!
2. Example:
Alarm value
= - 20 °C
Alarm type
= Gradienten-MAX + MIN-Alarm
Time interval
= 20 s (20 samples in 20s)
Temp
(°C)
20
Start
20
4
Time (s)
MAX-alarm
MIN-alarm
Every time interval contains 20 samples. The minimum pulse duration at
the alarm output is 0.05 x 20 s = 1 s!