background image

02/2014

 

                                                                                                                                                      

                  

 

 

_____________________________________________________________________________________________________________________                                                                                                                                

 

26 

6.1.10.  Calibration 

 Calibrate input 

 Thermocouple 

The set of parameters from the MTP200 has to be read in before beginning the calibration. For calibration of 
the  thermocouple  measurement  input  place  the  jumpers  according  to  the  specifications  in  the  WINSMART 
mask for activation of the thermocouple measurement input (see section 10.4 Measurement inputs). 

 

For the 2-point calibration you can freely select the calibration points within the characteristic curve range. In 
the  case  of  high  accuracy  requirements,  we  always  recommend  the  required  measuring  range  as  the 
calibration  range.  Before  starting  calibration,  you  have  to  clarify  the  question  of  whether  or  not  to  take  the 
temperature reference junction (TRJ) into account, i.e. should the ambient temperature measured by the TRJ 
apply as the reference temperature or 0°C. For calibration with the TRJ you have to mark the box 

Take TRJ 

into account in the calibration

 in the mask. 

The calibration procedure begins with simulation of the temperature value for the 1

st

 calibration point and entry 

of the command 

Read in

. The messages 

Measurement running

 and 

finished

 appear one after the other in 

the mask. After acknowledgement with 

OK

 the calibration value is accepted and shown analogously as a bar 

in the mask. The proportional representation in the bar chart serves as a check and helps to avoid calibration 
errors (equal calibration values 

 equal bar lengths 

 measured value display not possible 

 output jumps 

back and forth. The same procedure is repeated for the 2

nd

 calibration point. Transfer of the calibration values 

to the MTP200 marks the conclusion of the calibration procedure. For this mark the box 

Overwrite calibration 

values

  in  the  main  MTP  menu,  and  start  the  transfer  with  the  button 

Program  MTP

  (see  screen  area 

Interface). The message 

Existing parameters will be overwritten.

 

Still continue

? appears in the mask. Use 

OK

  to  start  the  process;  the  next  message  is: 

Transfer  parameters

.  A  last 

OK

  ends  the  entire  transfer 

process and thus the calibration as well. 

Temperature reference junction (TRJ) 

The TRJ calibration requires a correctly calibrated resistance input as a 2-wire circuit in a 
range from 0 

– 50 Ω. 

The  internal  TRJ  consists  of  a  Pt  100  sensor  placed  in  the  terminal  block  so  that  the  KL19  +  KL20  are  not 
necessary. The terminals KL19 + KL20 are used for connection of an external Pt 100 sensor in a 2-wire circuit 
only in the case of an external TRJ. Then you have to use a standard terminal block with the terminals KL17 to 
KL20. A more or less substantial error in the cold junction temperature results from the lead resistance of an 
internal/external Pt 100 sensor. 

 

There are two options for error correction: 

One is to enter the measured resistance value of the lead directly in the mask. The second option is to correct 
the sensor error as well as the lead resistance. In this case the read-off TRJ temperature value of the online 
mask and a precise measured value of the cold junction temperature are required. You can calculate the lead 
resistance for the TRJ calibration via the resistance gradient of the Pt 100 sensor at  0.39 

/

C and enter it in 

the mask. 

Example 1: 

TRJ-value

 in the online-mask 

27.40  °C

 

 

Measured cold junction temperature 

22.80  °C

 

 

 

-------------------------------- 

 

ΔT = (27,4  -  22,8) °C 

4.60  °C 

 

Load resistance = 0.39 Ω/°C x 4.6 °C 

1.79 

Ω 

Summary of Contents for MTP200ia-E

Page 1: ...______________________________________ M tec Instruments GmbH Tel 49 0 4185 80 83 0 Email muetec muetec de Bei den K mpen 26 Fax 49 0 4185 80 83 80 Web www muetec de D 21220 Seevetal Ramelsloh Manual...

Page 2: ...he user in making reliable and efficient use of the unit Transmission and duplication of this document as well as utilization and disclosure of its content are prohibited unless expressly permitted An...

Page 3: ...rights Enter password 23 6 1 7 Access rights Change password Password level 1 24 6 1 8 Access rights Change password Password level 2 24 6 1 9 Calibration Calibrate input PT 100 24 6 1 10 Calibration...

Page 4: ...sures are not taken CAUTION without a triangular warning sign means that material damage may occur if the appropriate precautionary measures are not taken ATTENTION means that an undesired result or s...

Page 5: ...ty lose their conformity certification as soon as they have been operated in circuits that do not meet the values specified in the test certificate Flawless and safe operation of this device requires...

Page 6: ...Bit 2x 10 Bit 1 D A converter 15 Bit 5 Self monitoring circuits 5 Galvanic separated alarm outputs 3x relay contact 2x transistor 4 Intrinsically safe measurement signal input Ex ia ib IIC Guaranteed...

Page 7: ...may be accomplished only under attention by 9 of the ex regulation Elex V Devices with intrinsically safe circuits may be never operated in not intrinsically safe circuits If ex devices in not intrin...

Page 8: ...ic circuits amount to the metallic housing parts at least 3 mm and to the bright parts of the not intrinsically safe electric circuits at least 6 mm According to the EN 60079 11 connecting units for t...

Page 9: ...nt intensity 0 5 A Max voltage Um AC DC 125 V not intrinsically safe digital output circuit contacts d z16 and d z18 Voltage DC 28 V Current intensity 50 mA Max voltage Um AC DC 125 V not intrinsicall...

Page 10: ...on of an intrinsically safe circuit with following maximum values Voltage Ui DC 30 V Current intensity Ii 110 mA Power Pi 700 mW Effective inside capacity Ci negligible Effective inside inductivity Li...

Page 11: ...k The related electrical equipment meets all requirements of the basic specification EN 60079 0 2004 and is EMC tested 16 Bit processor and 8 Bit processor in accordance with DuoTec technology Intrins...

Page 12: ...with 4 deviation from the reference value 6 Analog output signal deviation constant light alarm value or instantaneous value on off active automatic configurable from 0 2 7 A D Converter signal devia...

Page 13: ...e 100 mV measuring input AE4 Measurement range 35 70 mV free configurable Input resistance 1 M Thermocouple DIN IEC 584 AE4 Input resistance 1 M Cold compensation internally or externally with PT 100...

Page 14: ...per IEC 947 5 1 resp EN60947 Transistor output DO1 DO2 Switching performance 1 4 W Switching Voltage 28 VDC Switching current 50 mA Devices with intrinsically safe circuit may be connected over the c...

Page 15: ...ring cycle Ref voltage redundant and monitored Semi conductor memory cyclic running tests secure relative integrity P controller technology Relay REL1 REL3 indirect contact monitoring Maintenance requ...

Page 16: ...device can only be operated outside a potentially explosive area Form of construction 19 europecard with 4 TE front panel Protection class IP20 Mounting for the required protection class the device h...

Page 17: ...s OUTPUT Area beginning 4 00 mA Area ending 20 00 mA MIN limit 3 60 mA MAX limit 20 50 mA Alarm value 21 00 mA Filter time 0 5 s ALARM 1 Alarm type MIN Alarm Function zero signal current Alarm value...

Page 18: ...02 2014 _____________________________________________________________________________________________________________________ 18 5 2 Basic Circuit Diagram...

Page 19: ...02 2014 _____________________________________________________________________________________________________________________ 19 5 3 General view...

Page 20: ...02 2014 _____________________________________________________________________________________________________________________ 20 5 4 Contacts and female multipoint connector s coding...

Page 21: ...rrent mA X X X X X Thermocouple with internal TVG X X X X Thermocouple with external TVG X X X Thermocouple with thermostat X X X X Pt 100 2 wire circuit X X X X Pt 100 3 wire circuit X X X Pt 100 4 w...

Page 22: ...address in the field PC Interface and MTP address left area of the screen in the section Interface A device with unknown address can be identified by using the function Search address After finding th...

Page 23: ...Windows is used The character font and print format are fixed and cannot be changed by the user 6 1 4 File Print comment The extensive comments saved in the device as dated protocol with a maximum 20...

Page 24: ...ion and the function Overwrite calibration values It is reserved exclusively for technicians with special knowledge of the device and its functions Password level 2 is secured by a password 5180 assig...

Page 25: ...bar in the mask The proportional representation in the bar chart serves as a check and helps to avoid calibration errors Same calibration values for the 1 st and 2 nd calibration point same bar lengt...

Page 26: ...th The same procedure is repeated for the 2 nd calibration point Transfer of the calibration values to the MTP200 marks the conclusion of the calibration procedure For this mark the box Overwrite cali...

Page 27: ...by using the jumpers see section 10 4 Measurement inputs Resistance input for 2 or 4 wire circuit The input is defined as a 2 wire or 4 wire circuit using the jumpers JP8 JP9 and the calibration is de...

Page 28: ...ration values The output signal 0 2 10 V is generated by a constant current 0 4 20 mA which runs over a resistive shunt of 500 assuming that JP1 JP3 is set on V Therefore a voltage results in a fault...

Page 29: ...and MTP address 1 255 Should the MTP address be unknown or not marked on the device then the unknown address can be determined with the command Search for addresses After conclusion of the correct tra...

Page 30: ...6 3 MTP identification 6 3 1 Serial No The serial number is a 8 digit manufacturer specific unit number ensuring clear identification for each MTP200 It consists of a date code year calendar week and...

Page 31: ...nt input A filter time of minimum 0 1 to maximum 99 9 seconds defines a first order filter for the measure signal With a larger filter time the measured value is more damped For compensation of the le...

Page 32: ...e decimal point Start of range Physical measure value at start of range End of range Physical measure value at end of range MIN value Minimal measure value for initiation of fault alarm MAX value Maxi...

Page 33: ...correct recording of the measured value is no longer possible in the input due to a fault and is programmed in the screen for System controlling with the function Alarm value for analogue output Squar...

Page 34: ...m of 9 9 seconds guarantees that briefly exceeded alarm values do not activate the alarm Available alarm types MAX alarm with rising measured value MIN alarm with falling measured value Gradient MAX a...

Page 35: ...arm Time interval 60 s 20 samples in 60s Temp C 40 Start 60 3 Time s MAX alarm MIN alarm Every time interval contains 20 samples The minimum pulse duration at the alarm output is 0 05 x 60 s 3 s 2 Exa...

Page 36: ...he fault event The configuration for the alarm outputs function alarm type etc takes place exclusively in the Alarm output screen where defined alarm outputs are dimmed out no function switched off an...

Page 37: ...ere is no limit value alarm limit The alarm function is only the limit value monitoring Truth table for limit values and maintenance alarm Function Limit value alarm Maintenance alarm Alarm output Not...

Page 38: ...alue on on on The behaviour of the outputs determined by the ranking Analogue output stays on Alarm value Relay 1 changes from relay off to relay on Relay 2 changes from relay limit to relay on Logic...

Page 39: ...relay 3 The diagnostic manager shows the source of these faults in the window current faults and fault memory It is not possible to delete the fault memory for a current fault in case the fault is no...

Page 40: ...MTP200 device The allowed capacity for comments is a maximum 2000 ASCII characters and may be sufficiently dimensioned for most applications For protocols this text can be printed out with the comman...

Page 41: ...____ 41 6 10 Online representation The online representation shows the input and output signal both analogue and digital Additional the alarms with their limit values are figured During exceeded limit...

Reviews: