02/2014
_____________________________________________________________________________________________________________________
14
Devices with intrinsically safe circuit may be connected over the contact and transistor output with devices with
operating voltages under 250V only!
Alarm conditions are indicated with yellow front-
side LED’s!
Number:
4 independently adjustable limit values
Setting:
physically values with WINSMART
-Program
Accuracy:
like measured value accuracy
Alarm type:
free configurable
Alarm output:
2x relay contact and 2x transistor output
Alarm delay:
free configurable from 0 ... 9.9 s
Switching hysteresis:
free configurable from 0 ... 99.9 %
Mode of operation:
operating or zero current principle
Alarm function:
input signal monitoring and maintenance requirement report
Contact outputs REL1/REL2
Contact:
Opening or closing contact (corresponding to jumper adjustment)
Breaking capacity:
max. 62.5 VA resp. max. 30 W
Voltage:
max. 125 V AC or 110 V DC
Switching current:
max. 1 A
Min. contact voltage:
10 mVDC
Min. contact current:
10 µA
Contact material:
AG Pd + 10 µAu
Relay-type:
as per IEC 947-5-1 resp. EN60947
Transistor output DO1/DO2
Switching performance:
< 1.4 W
Switching Voltage:
< 28 VDC
Switching current:
< 50 mA
Devices with intrinsically safe circuit may be connected over the contact of the relay with devices with
operating voltages under 250 V only!
Alarm conditions are indicated with a red front-side LED!
Mode of operation:
zero current principle
Alarm function:
maintenance requirement report
Contact position:
closed in good condition
Switching performance:
max. 62.5 VA resp. max. 30 W
Switching Voltage:
max. 125 V AC or 110 V DC
Switching current:
max. 1 A
Min. contact voltage:
10 mVDC
Min. contact current:
10 µA
Contact material:
AG Pd + 10 µAu
Relay-type:
as per IEC 947-5-1 resp. EN60947
Galvanic separation of COM and RS485 to power supply and all other circuit elements!
RS232/COM:
via front socket for PC-connection with Mütec-interface cable
RS485:
Half-duplex, without scheduling
Baud rate / Device address:
9600 bps, 1-248
Power supply indicator:
green LED signal = good condition
Power supply range:
19 … 30 VDC or 18 … 28 VAC
Power consumption:
1.2 W (at 24VDC and 4 mA at analogue output)
1.5 W (at 24VDC and 20 mA at analogue output)
CONTACT OUTPUTS (REL1, REL2), TRANSISTOR OUTPUT (DO1, DO2)
CONTACT OUTPUT (REL3) for MAINTENANCE REQUIREMENT
INTERFACES (COM, RS485)
POWER SUPPLY