12
Sensor Power
The module shall monitor Port Sensor Power current and shut off the sensor power in a port if the maximum current exceeds 3 amps
per port. Both short circuit and overcurrent protection is provided.
Module Power
The module power delivered by the CAN ports has short circuit protection. This circuit has a separate ground that is supplied by the
CAN port as well, Ground (A)
S1 = Port 1 power, 3 amps.
S2 = Port 2 power, 3 amps.
S3 = Port 3 power, 3 amps.
S4 = Port 4 power, 3 amps.
S5 = Port 5 power, 3 amps.
S6 = Port 6 power, 3 amps.
S7 = Port 7 power, 3 amps.
S8 = Port 8 power, 3 amps.
Module default configuration:
• Factory Default Config returns 1 in Status message 1-Status 1, this should not be on if the module has been configured.
• Default operation of the module is on/off digital control. PWM control messages are not needed.
• Default configuration does not require a Command 0x52 message to enable operation.
Value
Name
Data Type
Byte
Bits
Description
82 (0x52)
Command
Byte
1
Command for index pointer (which message your sending)
Ctrl Mode Reset
2 bit
2
1,2
Enables Controller Mode Output Reset
Enable Status 1 Msg
3,4
Enables the constant transmission of status message 1
Enable Status 2 Msg
5,6
Enables the constant transmission of status message 2
Enable Amp Msg
7,8
Enables the constant transmission of amperage messages
Enable 24 vdc
3
1,2
Enables the low and over voltage fault limits for 24V DC system
Save Configuration
3,4
Saves the configuration to the module (otherwise changes only valid until a power cycle occurs),
set to 1 to write configuration to module
Analog raw value
5,6
Sets all analog to be read in raw value as opposed to scaled (.005668/bit)
7,8
4
1,2
3,4
5,6
7,8
FREQ1
Word
5
Sets the configuration of the frequency for all channels (30-1140 Hz)
6
MODE1
4 Bit
7
Not used on this module
MODE2
4 Bit
Sets the configuration of the inputs.(0=Mode 2 Not Used, 1=Digital Positive, 2=Digital Ground)
No analog.
ID1
Byte
8
User defined byte for configuration ID, this will be transimitted in the STAT message.
4.5 CIRCUIT PROTECTION
5. MODULE CONFIGURATION
5.1 CONFIGURATION STEPS
Command 0x52 (This message needs to be sent until the message confirmation bit is set true):