Technical data
User manual 58185_TREE M4/6-TX PN IP20_hdb_en_10
37/103
Electromagnetic compatibility (EMC)
Immunity
Parameters
Conditions
Value
Conducted emission
EN 55022 /
EN 55011,
Section 5
Class A
(Industrial)
24 V DC power sup-
ply
150 kHz to 30 MHz
Radiated emission
EN 55022 / EN 55011,
Section 6
Class A
(Industrial)
30 MHz to 1000 MHz
Parameters
Conditions
Value
ESD
IEC 61000-4-2
Criterion A
4 kV / 8 kV
Radiated HF
IEC 61000-4-3
Criterion A
10 V/m
(80 MHz ... 1 GHz),
3 V/m
(1,4 GHz ... 2 GHz),
1 V/m
(2 GHz ... 2.7 GHz)
Burst on 24 V DC power
supply
IEC 61000-4-4
Criterion A
2 kV
Burst on data line
IEC 61000-4-4
Criterion A
2 kV
Overvoltage
IEC 61000-4-5
Criterion A
0.5 kV on 24 V DC
supply symmetrical
and asymmetrical,
1 kV on data lines
Conducted
IEC 61000-4-6
Criterion A
10 V
Magnetic fields
IEC 61000-4-8
Criterion A
30 A/m
1 min. all 3 spatial
axes