26
Name
Data Type
Byte
Bits
Description
Command
Byte
1
Command for index pointer (which message you’re sending)
Ctrl Mode Reset
2 bit
2
1,2
Enables Controller Mode Output Reset. Enabled (0,1) = cycling the output will reset the fault.
Enable
(Status Msg 1)
3,4
Enables the constant transmission of status message 1
Enable
(Status Msg 2)
5,6
Enables the constant transmission of status message 2
Enable
(Amp Msg)
7,8
Enable the constant transmission of amperage message
Enable 24 vdc
3
1,2
Enables the low and over voltage fault limits for 24 vdc system
Save
Configuration
3,4
Saves the configuration to the module (otherwise changes only valid until a power cycle occurs),
set to 1 to write configuration to module
5,6
7,8
4
1,2
3,4
5,6
7,8
FREQ1
Word
5
Low Byte
Sets the configuration of the frequency for all channels (30-1140 Hz) value = 0x 01-FE
6
High Byte
MODE1
4 bit
7
Sets the configuration of ALL the outputs, overides Command 53 and 54. (0=Node 1 NOT USED,
1=ON/OFF, 2=Data 0-4000, 3= Percent 0-100.0%(0-1000))
MODE2
Sets the configuration of ALL the inputs. (NOT USED ON THIS MODULE)
ID1
Byte
8
User defined byte for configuration ID, this will be transimitted in the STAT message.
J1939 Output Configuration 1
6. MESSAGE STRUCTURE
All PGNs are shown as module configured with no jumpers (Offset = 0)
PGN
61408 (0xEFE0) Node offset of 0
Source Address
(0x?? (CSA*))
PDU Format
239 (0xEF)
PDU Specific
224 (0xE0)
Built Message
(0x
18EFE0??
)
Transmit rate
50 ms
Msg timeout
200 ms
Priority
6
DP
0
Value
82 (0x52)
*CSA = Controller Source Address