Instruction manual for devices of the MASI20 series
V 1.0
7
Owing to the signal shape for the data transmission, it is not necessary to provide terminating resistors.
Thanks to the intelligent data protocol, AS-Interface systems are extremely non-sensitive to disturbance.
Consequently, you can use a non-screened bus cable.
The structure of AS-Interface systems can be compared to an ordinary electrical installation with different
network topologies : line, star or tree structure.
Fig. 2-3 :
Topology of the
AS-Interface
system
The data cycle time depends on the network topology and the entire scope of the system. For a complete
system with 31 slaves it is about 5 ms and with 62 slaves (extended specifications) about 10 ms.