Instruction manual for devices of the MASI20 series
26
V 1.0
4.2.1 Configuration with an AS-Interface addressing device
•
Address the slaves with the addressing device.
(For slaves with an addressing plug, this operation can be performed after step
‚
).
‚
Install the slaves and connect them to the system cable.
ƒ
Switch the master into configuration mode (
Ä
Master user's manual).
„
Check if all the slaves have been detected and stored into the LDS list (List of Detected Slaves),
(
Ä
Master user's manual).
…
Configure the system (
Ä
Master user's manual).
†
Switch into protected configuration mode (
Ä
Master user's manual).
‡
Check the master displays. The display of configuration errors must not be enabled
(
Ä
Master user's manual).
4.2.2 Configuration via the AS-Interface master
•
Switch the master into configuration mode (
Ä
Master user's manual).
‚
Connect the slave to the AS-Interface system cable.
ƒ
Change the slave address via the master (
Ä
Master user's manual).
„
Repeat steps
‚
and
ƒ
until all the slaves are connected and addressed.
…
Check if all the slaves have been detected and stored into the LDS list (List of Detected Slaves),
(
Ä
Master user's manual).
†
Configure the system (
Ä
Master user's manual).
‡
Switch into protected configuration mode (
Ä
Master user's manual).
Check the master displays. The display of configuration errors must not be enabled.
(
Ä
Master user's manual).
4.3 Automatic configuration
In case of a slave failure while the system is operating, it can be easily replaced by a new slave if the
following conditions are complied with :
•
the master must be in protected operating mode and the automatic configuration must be active,
‚
failure of only one slave,
ƒ
the new slave is assigned to address 0,
„
the profile of the new slave is identical to the profile (stored by the master) of the slave to be
replaced.
Only under these conditions the new slave is integrated into the system and automatically configured by
the master, which immediately assigns the address of the faulty slave.