of cause of alarm. These circuits activate the alarm relay.
Alarm circuits are active as long as power is applied to the
A902-2. All are active when the engine is running, shutdown or
on standby. Two (2) Amber Alarm Indicating Lights are
provided.
(a) Low Water Temperature; operated by low water
temperature SWICHGAGE
®
.
(b) Air Damper Closed; operated by an external switch or by
the Overspeed Relay circuit. This circuit is provided with
a selector switch to allow the user to determine the source
of the signal.
3-5.2 Relay Module. The Relay Module, figure 3-5.2, includes
all of the control, alarm and shutdown relays that are required to
make up the generator engine control. Relays are available for
operation on either 12 or 24 volt battery systems. Four (4)
relays are included for:
3-5.2.1 Fuel Relay; this relay provides two outputs, one to
energize the engine fuel solenoid and a separate circuit to
energize the battery charging alternator field.
3-5.2.2 Shutdown Relay; this relay is operated by the shutdown
circuits of the Control / Display Module and provides an output
that can be used to trip the generator circuit breaker on an
emergency shutdown.
3-5.2.3 Overspeed Relay; operates only on an Overspeed
shutdown. This relay provides an output to trip an air shut off
solenoid to close the air damper on a two-cycle engine.
3-5.2.4 Local Audible Alarm Relay; provides a contact closure
to operate a local audible alarm as required by NFPA- 110, Level
1 and Level 2.
3-5.3 Status Signals. The relay module also includes three
outputs that can be used with external circuits for signaling or
control functions.
3-5.3.1 The Control On function at terminal 12 is on (closed to
negative) as long as the Mode Selector Switch is in either Auto
or Test. When the Mode Selector is turned Off, the Control On
signal is open. This can be used to signal switch position or to
reset an external circuit when the Mode Selector is turned Off.
3-5.3.2 The System Ready signal at terminal 13 is on (closed
to negative) as long as the Mode Selector Switch is in either
Auto or Test and no shutdown TATTLETALE
®
circuit is
latched on. This can be used to signal that the generator
engine is ready to automatically start or is running in Test.
3-5.3.3 The Control On function at terminal 14 is on (closed to
positive) as long as the Mode Selector Switch is in either Auto
or Test. When the Mode Selector is turned Off, the Control On
signal is open. This can be used to signal switch position or to
reset an external circuit when the Mode Selector is turned Off.
3-6 A903.
3-6.1 Control / Display Module. The Control / Display Module,
figure 3-6.1, includes the control and test switches, the solid
state logic elements, shutdown and alarm TATTLETALE
®
lights
that make up the generator engine control for a four cycle
engine. This module is the same as Model A- 901 except 7 of
the alarm circuits are un-labeled. This allows the customer to
specify labels other than those recommended in NFPA-110.
This model has shutdown and alarm circuits labeled to meet the
requirements of NFPA-110, Level 2.
3-6.1.1 Mode Selector Switch, OFF-AUTO-TEST:
(a) OFF; turns off the control system and resets any shutdown
circuits.
(b) AUTO; turns on the engine controls and shutdown circuits.
System is on standby waiting for a contact closure to start
engine.
(c) TEST; turns on the engine controls and shutdown circuits.
A start signal is applied to the automatic control and the
engine start sequence begins.