background image

current rating that is equal to or greater than the forward current
that the coil draws to operate. For example, a relay less than 1 A,
use a 1 A diode since they are readily available. The wiring
shown in Figures 4-2.3.1, 4-2.3.2 and 4-2.3.3 have examples of
the places that a reverse diode is required.

4-3  Crank Disconnect.
4-3.1  
A magnetic pickup is recommended to supply the speed
signal for the A900 series primary crank termination circuit and
for the overspeed switch.  This pickup will be mounted in the
flywheel housing in line with the ring gear on the flywheel and
wired to the A900 using either a twisted pair or a shielded cable
to reduce the possibility of electrical noise pickup in the wiring.
4-3.1.1  The tachometer terminal, of the battery charging
alternator, may be used for the speed signal but a broken drive
belt will disable this source and some alternators have electrical
noise which will cause the speed switches to operate at speeds
well below the desired RPM.
4-3.2  An auxiliary crank disconnect circuit, required by
NFPA-110, is provided in the A900.  Any signal that detects
when the engine is running and provides a contact closure
between Terminals 4 and 16 can be used.  This circuit
terminates cranking even if the speed signal fails.  The “Loss
Of Speed” shutdown / alarm on the A900 will indicate if the
speed signal is lost while the engine is running by either
shutdown of the engine or operation of the alarm circuit.
“Loss Of Speed” alarm will only operate if the auxiliary crank
disconnect circuit is used.  Provision is also made for a second
N.C. contact between Terminals 17 and 18 to interrupt the
output to the auxiliary starter solenoid.  This would disconnect
cranking even if both crank disconnect circuits in the A900
should fail.  If this contact is not provided, you must jumper
Terminals 17 and 18 for the start signal to reach the auxiliary
starter solenoid.  A voltage sensing relay wired to one output
phase of the generator is one way to provide both of these
contacts.

4-4  Pre-operational Check-out.
4-4.1  
After installation is complete, it is necessary to make
some adjustments to the A900 SELECTRONIC

®

Control before

the system is operational.  All shutdown and alarm circuits also
should be tested.  Table 4-4.1 lists the standard factory setting of
the adjustable functions on the A900 series control.  To

determine if the frequency of the speed switches must be
changed, calculate the required setting using the following
formulas:

Refer to Table 4-4.1 to determine if the speed switch settings are
below the factory settings listed.  If required frequency will be
higher than the standard, increase the setting before proceeding.
Turn The Crank Disconnect Set and Overspeed Set pots
clockwise to increase setting.  The adjustments are 20 turn
controls without stops at either end.
4-4.1.1 Be sure to have a fully charged battery to do these tests.
Low battery voltage can cause improper results during the tests.
4-4.1.2  The “Air Damper Closed” alarm on A900 series for 2
cycle engines can be actuated by either an internal circuit that
senses the output to the overspeed relay, from the “Overspeed”
shutdown circuit or by an external switch wired to terminal 34
of the Control / Display Module.  The “Air Damper Closed”
switch, Table 4-4.1 must be turned On for internal sensing and
Off for external switch.  This circuit is a Spare alarm on A900
for 4 cycle engines and the switch must be turned Off to
prevent this circuit from operating with the “Overspeed”
shutdown.
4-4.1.3  All of the adjustments and controls shown in Table 4-4.1
are located on the rear of the control/display module. See Figure
4-4.1.3. Each light and switch is labeled for ease of
identification. The LED's are supplied as an aid in installation
and troubleshooting of the A900.
4-4.2  Crank Disconnect Speed Setting;  to set this speed switch,
proceed as follows:

(a)  Disconnect the run solenoid wire from terminal 6 on the

Relay Module.

(b)  Check engine to be sure it is safe to crank.
(c)  Be sure Mode Selector switch is in OFF position.
(d)  Connect battery cables to a fully charged cranking battery.
(e)  Turn Mode Selector switch to TEST position and watch

the lights on the A900 control module back panel.

1. The engine should start cranking and the “Fuel Relay”,

“Crank Relay”, and “Pickup Present” lights turn on.

2. If engine does not crank, check the lights.  If green

light next to Mode Selector Switch on front panel is
not on, check the DC power input wiring and fuse.

3.  If green light, “Fuel Relay” and “Crank Relay” lights

are on, check wiring from A900 Terminal 18 to
auxiliary start solenoid and than on to the starter on
engine.

4.  With engine cranking, check “Pickup Present” light.  It

must be on.  If off, check the wiring to magnetic
pickup and check gap between pickup face and ring
gear.

5. If “Crank Disconnect Speed” light comes on and

cranking stops, setting of Crank Disconnect Switch is
still to low. Turn Mode Selector switch OFF and turn
crank disconnect adjustment clockwise 1 or 2 turns
and repeat test.

19

No. of Gear Teeth x RPM set points

60

Set point 

frequency in HZ

Pulley ratio x No. of Alternator Poles x RPM set points

60

Set point 

frequency in HZ

=

=

Function

Standard 

Setting

Adjustment

Range

Adjustment

Type

Crank/Rest 
Time

15 

seconds

10, 15, 20, 25 

and 30 Seconds

Switch

Overcrank

3 cranks

1, 2, 3, 4, 5, 6 and 

No overcrank

Switch

Crank 
Disconnect

1180 Hz

Turn CW 

to increase

25 to 2 KHz

Overspeed

3894 Hz

Turn CW 

to increase

300 to 10 KHz

Cooldown

OFF

Fixed 5 minute

ON-OFF switch

Loss of speed 
Signal

Shutdown

Shutdown or

Alarm

Switch

ON with 

Overspeed 

shutdown

Internal switch ON

External switch OFF

Switch

Table 4-4.1

OR

Air Damper Closed
Alarm on 2 Cycle
Engines only

Summary of Contents for MURPHYMATIC A900 Series

Page 1: ...SERIES A900 MURPHYMATIC GENERATOR ENGINE CONTROL SYSTEM DESIGN INSTALLATION AND OPERATING MANUAL A900 9025N Revised 10 99 Section 40 00 02 0197...

Page 2: ...ot operate during installation Follow all safety warnings of the machine manufacturer Read and follow all installation instructions Certain danger to human safety and to equipment may occur if some eq...

Page 3: ...4 Installation 14 4 1 Location 14 4 2 Wiring 14 4 3 Crank Disconnect 19 4 4 Pre Operational Check Out 19 Section 5 Operation 21 5 1 Operator Controls 21 5 2 Operating Modes 21 Section 6 Routine Maint...

Page 4: ...phy c SWICHGAGE A combination indicating gauge and switch d TATTLETALE A term that refers to a shutdown indicating device or circuit in the control panel 1 5 How to use this manual 1 5 1 Section 1 2 4...

Page 5: ...of a two cycle engine 3 1 7 Table 3 1 7 illustrates the alarm and shutdown require ments of NFPA 110 NFPA99 and CAN CSA C282 M89 and compares the features of the A900 series controls to those require...

Page 6: ...X X X O O i Control Switch not set in Auto X X X X O O O X X X X X X X X O O j High Battery Voltage X X X O O O X X X O O k Low VoltageBattery X X X O O O X X X X X X X O O l Lamp Test X X X X X X X...

Page 7: ...preset speed c Oil Pressure tripped by the oil pressure SWICHGAGE if pressure drops below preset point while the engine is running d Water Temperature tripped by the water temperature SWICHGAGE if en...

Page 8: ...automatic control and the engine start sequence begins 3 3 1 2 Lamp Test Pushbutton Tests the lights on the A 901 2 module 3 3 1 3 Alarm Silence Pushbutton Turns off any audible alarm that is connecte...

Page 9: ...ill running Since the Overspeed shutdown circuit is activated by the frequency input it prevents the engine from running without overspeed protection g Remote Shutdown this circuit is provided to shut...

Page 10: ...ntrol Module includes the following engine control features a Cycle crank circuit will crank the engine for 15 seconds then rest for 15 seconds until the engine starts The crank rest time is selectabl...

Page 11: ...s circuit is provided for an additional alarm that may be required by the user 3 4 2 Relay Module The Relay Module figure 3 4 2 includes all of the control alarm and shutdown relays that are required...

Page 12: ...is depressed the set point of the speed switch is lowered approximately 10 3 The push to test switch can also be used to set the overspeed switch at approximately 110 of running speed Hold the switch...

Page 13: ...he Mode Selector Switch is in either Auto or Test When the Mode Selector is turned Off the Control On signal is open This can be used to signal switch position or to reset an external circuit when the...

Page 14: ...ing With engine speed at 1800 RPM or 3540 Hz g Cooldown circuit this circuit keeps the engine running for five minutes after the transfer switch has removed the load from the generator and signaled th...

Page 15: ...Test and no shutdown TATTLETALE circuit is latched on This can be used to signal that the generator engine is ready to automatically start or is running in Test 3 6 3 3 The Control On function at term...

Page 16: ...tdown Circuits provide first out indication of cause of shutdown These circuits deactivate the fuel relay and lockout the A903 until reset Shutdown circuits are activated by the crank disconnect circu...

Page 17: ...ces recommended for installation 4 1 3 Wiring Terminals Terminal blocks are provided on both sides of the Control Display enclosure and the Relay Module Torque all terminal screws to 12 inch pound max...

Page 18: ...3 4 in 171 mm 9 3 8 in 238 mm 6 in 152 mm 4 15 32 in 114 mm Mounting Holes 1 8 in 3 mm diameter 1 1 2 in 38 mm clearance 5 in 127 mm maximum between A 900 Series module relay module when mounting 1 7...

Page 19: ...REMOTE AUDIBLE LOCAL AUDIBLE N C N C OVERSPEED RELAY SHUTDOWN RELAY FUEL RELAY CRANK RELAY AUX CRANK DISCONNECT N C CONTROL ON SYSTEM READY FUSED B B Energize to Stop solenoid Energize to Run solenoid...

Page 20: ...Alarm I Fuel Relay J1 J2 Q2 Q1 J1G Red Blk LOW WATER LEVEL REMOTE VISUAL REMOTE AUDIBLE LOCAL AUDIBLE N C N C OVERSPEED RELAY SHUTDOWN RELAY FUEL RELAY CRANK RELAY AUX CRANK DISCONNECT N C CONTROL ON...

Page 21: ...dible Alarm H Shut Down Relay D Local Audible Alarm I Fuel Relay J1 J2 Q2 Q1 J1G Red Blk LOW WATER LEVEL REMOTE VISUAL REMOTE AUDIBLE LOCAL AUDIBLE N C N C OVERSPEED RELAY SHUTDOWN RELAY FUEL RELAY CR...

Page 22: ...e to increase setting The adjustments are 20 turn controls without stops at either end 4 4 1 1 Be sure to have a fully charged battery to do these tests Low battery voltage can cause improper results...

Page 23: ...on and the engine shuts down f Release pushbutton check Overspeed light on front panel to be sure it is on g Turn Mode Selector switch OFF to reset shutdown circuits then back to TEST h When engine s...

Page 24: ...the Mode Selector switch in the AUTOMATIC position When a start signal is received the engine will start 5 2 3 2 When the start signal is removed the engine will stop It is now ready to restart 5 2 4...

Page 25: ...put Voltage Input Voltage Input Voltage Input Voltage Input Voltage 13 8 27 6 13 8 27 6 13 8 27 6 13 8 27 6 13 8 27 6 31 6 6 6 6 6 6 6 6 6 6 32 6 6 6 6 6 6 6 6 6 6 33 6 6 6 6 6 6 6 6 6 6 34 6 6 6 6 6...

Page 26: ...o shutdown the engine and generator a The TATTLETALE light for that function turns on b Shutdown relay K 2 is energized closing its contacts at terminal 9 These contacts can be wired to a shunt trip s...

Page 27: ...e OEM parts and are available only to Detroit Diesel and their distributors 8 2 1 The A900 DDC parts are the same as the Murphy A900 series that has been covered throughout the A900 manual except the...

Page 28: ...1722 410697 fax 44 1722 410088 e mail france fwmurphy co uk www fwmurphy co uk francais htm In order to consistently bring you the highest quality full featured products we reserve the right to chang...

Reviews: