8

setting until the overspeed trips.  When switch is
released, the set point will be 10% above normal
running speed.  This is the method used to make the
factory setting.  With engine speed at 1800 RPM or
3540 Hz.

(g)  Cooldown circuit;  this circuit keeps the engine running

for five minutes after the transfer switch has removed the
load from the generator and signaled the A902 to stop
the engine.  This feature may be selected (turned On,
standard setting is Off) with a switch on the back of the
Control / Display Module.

3-4.1.4  Seven (7) First-out Shutdown Circuits;  provide first-out
indication of cause of shutdown.  These circuits deactivate the
fuel relay and lockout the A902 until reset. Shutdown circuits
are activated by the crank disconnect circuit and are not active
when the engine is stopped.  Six (6) Red Shutdown Indicating
Lights are provided.  The Remote Shutdown circuit does not
have an indicator light.

(a)  Overcrank;  tripped by the overcrank sensing circuit which

counts the number of cranking attempts.

(b)  Overspeed;  tripped by overspeed switch when engine

exceeds a preset speed.

(c)  Oil Pressure;  tripped by the oil pressure SWICHGAGE

®

if

pressure drops below preset point while the engine is
running.

(d)  Water Temperature;  tripped by the water temperature

SWICHGAGE

®

if engine coolant temperature exceeds the

switch setting.

(e)  Spare Shutdown;  tripped by an external switch.  This

circuit is provided for an additional shutdown that may be
recommended by the engine supplier.

(f)  Loss of Speed Signal;  tripped by an internal sensing

circuit that detects the loss of the Magnetic Pickup
frequency signal for the speed switches while the engine
is still running.  Since the Overspeed shutdown circuit is
activated by the frequency input, it prevents the engine
from running without overspeed protection.

(g)  Remote Shutdown;  this circuit is provided to shutdown

the engine generator from a remote location.  No
indicating light is provided.

3-4.1.5 Two (2) Alarm Indicating Circuits;  provide indication
of cause of alarm.  These circuits activate the alarm relay.  Alarm
circuits are active as long as power is applied to the A902.  All
are active when the engine is running, shutdown or on standby.
Two (2) Amber Alarm Indicating Lights are provided.

(a) Low Water Temperature;  operated by low water

temperature SWICHGAGE

®

.

(b)  Spare Alarm;  operated by an external switch.  This circuit

is provided for an additional alarm that may be required
by the user.

3-4.2  Relay Module.  The Relay Module, figure 3-4.2, includes
all of the control, alarm and shutdown relays that are required to
make up the generator engine control.  Relays are available for
operation on either 12 or 24 volt battery systems.  Three (3)
relays are included for:
3-4.2.1 Fuel Relay;  this relay provides two outputs, one to
energize the engine fuel solenoid and a separate circuit to
energize the battery charging alternator field.
3-4.2.2  Shutdown Relay;  this relay is operated by the shutdown
circuits of the Control / Display Module and provides an output

that can be used to trip the generator circuit breaker on an
emergency shutdown.

3-4.2.3 Local Audible Alarm Relay;  provides a contact closure
to operate a local audible alarm as required by NFPA- 110, Level
1 and Level 2.
3-4.3  Status Signals.  The relay module also includes three
outputs that can be used with external circuits for signaling or
control functions.
3-4.3.1  The Control On function at terminal 12 is on (closed to
negative) as long as the Mode Selector Switch is in either Auto
or Test.  When the Mode Selector is turned Off, the Control On
signal is open.  This can be used to signal switch position or to
reset an external circuit when the Mode Selector is turned Off.
3-4.3.2 The System Ready signal at terminal 13 is on (closed
to negative) as long as the Mode Selector Switch is in either
Auto or Test and no shutdown TATTLETALE

®

circuit is

latched on.  This can be used to signal that the generator engine
is ready to automatically start or is running in Test.
3-4.3.3  The Control On function at terminal 14 is on (closed to
positive) as long as the Mode Selector Switch is in either Auto
or Test.  When the Mode Selector is turned Off, the Control On
signal is open.  This can be used to signal switch position or to
reset an external circuit when the Mode Selector is turned Off.

3-5  A902-2.
3-5.1  
Control / Display Module.  The Control / Display Module,
figure 3-5.1, includes the control and test switches, the solid state
logic elements, shutdown and alarm TATTLETALE

®

lights that

make up the generator engine control for a two-cycle engine.
3-5.1.1 Mode Selector Switch, OFF-AUTO-TEST: 

(a)  OFF; turns off the control system and resets any shutdown

circuits.

(b)  AUTO; turns on the engine controls and shutdown circuits.

System is on standby waiting for a contact closure to start
engine.

DC12V

3A Fuse

1A

4

5

6

7

8

9

16

17

18

19

20

21

22

23

24

25

DC12V

DC12V

6-1/4 in.

(159 mm)

4-1/2 in.

(114 mm)

Figure 3-4.2

Summary of Contents for MURPHYMATIC A900 Series

Page 1: ...SERIES A900 MURPHYMATIC GENERATOR ENGINE CONTROL SYSTEM DESIGN INSTALLATION AND OPERATING MANUAL A900 9025N Revised 10 99 Section 40 00 02 0197...

Page 2: ...ot operate during installation Follow all safety warnings of the machine manufacturer Read and follow all installation instructions Certain danger to human safety and to equipment may occur if some eq...

Page 3: ...4 Installation 14 4 1 Location 14 4 2 Wiring 14 4 3 Crank Disconnect 19 4 4 Pre Operational Check Out 19 Section 5 Operation 21 5 1 Operator Controls 21 5 2 Operating Modes 21 Section 6 Routine Maint...

Page 4: ...phy c SWICHGAGE A combination indicating gauge and switch d TATTLETALE A term that refers to a shutdown indicating device or circuit in the control panel 1 5 How to use this manual 1 5 1 Section 1 2 4...

Page 5: ...of a two cycle engine 3 1 7 Table 3 1 7 illustrates the alarm and shutdown require ments of NFPA 110 NFPA99 and CAN CSA C282 M89 and compares the features of the A900 series controls to those require...

Page 6: ...X X X O O i Control Switch not set in Auto X X X X O O O X X X X X X X X O O j High Battery Voltage X X X O O O X X X O O k Low VoltageBattery X X X O O O X X X X X X X O O l Lamp Test X X X X X X X...

Page 7: ...preset speed c Oil Pressure tripped by the oil pressure SWICHGAGE if pressure drops below preset point while the engine is running d Water Temperature tripped by the water temperature SWICHGAGE if en...

Page 8: ...automatic control and the engine start sequence begins 3 3 1 2 Lamp Test Pushbutton Tests the lights on the A 901 2 module 3 3 1 3 Alarm Silence Pushbutton Turns off any audible alarm that is connecte...

Page 9: ...ill running Since the Overspeed shutdown circuit is activated by the frequency input it prevents the engine from running without overspeed protection g Remote Shutdown this circuit is provided to shut...

Page 10: ...ntrol Module includes the following engine control features a Cycle crank circuit will crank the engine for 15 seconds then rest for 15 seconds until the engine starts The crank rest time is selectabl...

Page 11: ...s circuit is provided for an additional alarm that may be required by the user 3 4 2 Relay Module The Relay Module figure 3 4 2 includes all of the control alarm and shutdown relays that are required...

Page 12: ...is depressed the set point of the speed switch is lowered approximately 10 3 The push to test switch can also be used to set the overspeed switch at approximately 110 of running speed Hold the switch...

Page 13: ...he Mode Selector Switch is in either Auto or Test When the Mode Selector is turned Off the Control On signal is open This can be used to signal switch position or to reset an external circuit when the...

Page 14: ...ing With engine speed at 1800 RPM or 3540 Hz g Cooldown circuit this circuit keeps the engine running for five minutes after the transfer switch has removed the load from the generator and signaled th...

Page 15: ...Test and no shutdown TATTLETALE circuit is latched on This can be used to signal that the generator engine is ready to automatically start or is running in Test 3 6 3 3 The Control On function at term...

Page 16: ...tdown Circuits provide first out indication of cause of shutdown These circuits deactivate the fuel relay and lockout the A903 until reset Shutdown circuits are activated by the crank disconnect circu...

Page 17: ...ces recommended for installation 4 1 3 Wiring Terminals Terminal blocks are provided on both sides of the Control Display enclosure and the Relay Module Torque all terminal screws to 12 inch pound max...

Page 18: ...3 4 in 171 mm 9 3 8 in 238 mm 6 in 152 mm 4 15 32 in 114 mm Mounting Holes 1 8 in 3 mm diameter 1 1 2 in 38 mm clearance 5 in 127 mm maximum between A 900 Series module relay module when mounting 1 7...

Page 19: ...REMOTE AUDIBLE LOCAL AUDIBLE N C N C OVERSPEED RELAY SHUTDOWN RELAY FUEL RELAY CRANK RELAY AUX CRANK DISCONNECT N C CONTROL ON SYSTEM READY FUSED B B Energize to Stop solenoid Energize to Run solenoid...

Page 20: ...Alarm I Fuel Relay J1 J2 Q2 Q1 J1G Red Blk LOW WATER LEVEL REMOTE VISUAL REMOTE AUDIBLE LOCAL AUDIBLE N C N C OVERSPEED RELAY SHUTDOWN RELAY FUEL RELAY CRANK RELAY AUX CRANK DISCONNECT N C CONTROL ON...

Page 21: ...dible Alarm H Shut Down Relay D Local Audible Alarm I Fuel Relay J1 J2 Q2 Q1 J1G Red Blk LOW WATER LEVEL REMOTE VISUAL REMOTE AUDIBLE LOCAL AUDIBLE N C N C OVERSPEED RELAY SHUTDOWN RELAY FUEL RELAY CR...

Page 22: ...e to increase setting The adjustments are 20 turn controls without stops at either end 4 4 1 1 Be sure to have a fully charged battery to do these tests Low battery voltage can cause improper results...

Page 23: ...on and the engine shuts down f Release pushbutton check Overspeed light on front panel to be sure it is on g Turn Mode Selector switch OFF to reset shutdown circuits then back to TEST h When engine s...

Page 24: ...the Mode Selector switch in the AUTOMATIC position When a start signal is received the engine will start 5 2 3 2 When the start signal is removed the engine will stop It is now ready to restart 5 2 4...

Page 25: ...put Voltage Input Voltage Input Voltage Input Voltage Input Voltage 13 8 27 6 13 8 27 6 13 8 27 6 13 8 27 6 13 8 27 6 31 6 6 6 6 6 6 6 6 6 6 32 6 6 6 6 6 6 6 6 6 6 33 6 6 6 6 6 6 6 6 6 6 34 6 6 6 6 6...

Page 26: ...o shutdown the engine and generator a The TATTLETALE light for that function turns on b Shutdown relay K 2 is energized closing its contacts at terminal 9 These contacts can be wired to a shunt trip s...

Page 27: ...e OEM parts and are available only to Detroit Diesel and their distributors 8 2 1 The A900 DDC parts are the same as the Murphy A900 series that has been covered throughout the A900 manual except the...

Page 28: ...1722 410697 fax 44 1722 410088 e mail france fwmurphy co uk www fwmurphy co uk francais htm In order to consistently bring you the highest quality full featured products we reserve the right to chang...

Reviews: