Section 75
00-02-0522
04-06-11 -
4 -
Energized to Stop
The Energized to Stop timer is ON and the Energized to Stop
output is active.
Stopped Mode
Generator has come to a complete stop.
Postlube Mode
In larger generators there may be a requirement for
automatic lubrication after a normal start/run/stop cycle
before the engine can be restarted (set to 0 to bypass). After
postlube, the system returns to Ready to start. Additionally
there are two fault shutdown modes:
Shutdown / Lockout with Cooldown Mode
- In
the case of some faults the controller will open the
"at load
’
contact and then go through a normal
cooldown and stop sequence, but will not allow an
automatic restart without a system reset.
Immediate Shutdown/Lockout (no Cooldown)
Mode
- Because of the severity of most faults, the
controller will cause an immediate
Shutdown/Lockout without a cooldown period, and
will not allow an automatic restart without a system
reset.
Shutdown / Lockout with
Cooldown Mode
In the case of some faults the controller will open the "at
load
’
contact and then go through a normal cooldown and
stop sequence, but will not allow an automatic restart without
a system reset
Immediate
Shutdown/Lockout (no
Cooldown) Mode
Because of the severity of most faults, the controller will
cause an immediate Shutdown/Lockout without a cooldown
period, and will not allow an automatic restart without a
system reset.