Section 75
00-02-0522
04-06-11 -
26 -
A more easily understood method is to connect the iGUARD to the output terminals, with the
CTs sized for maximum current in the low wye configuration. This way, the controller can read
what is actually coming out of the generator, without any need to interpolate and assume. This
will offer increased accuracy, and is generally easier to understand.
Output Parameters
1. Relay 1
- Preheat.
2. Relay 2
- Crank.
3. Relay 3
- Fuel.
4. Relay 4
- Common Alarm.
5. Relay 5
- Common Alarm.
6. Relay 6
- Remote Alarm.
7. Relay 7
- Enable ECU.
8. Relay 8
- Not in Auto.
Output States
1. Not Used
.
2. Preheat
- Relay follows the selected preheat state.
3. Crank
- Relay follows the crank setting.
4. Fuel
- Relay operates as "Energized to run" suitable for fuel control.
5. Shutdown Lockout
- Relay is active when system has shutdown on a fault and is
energized until reset.
6. At Load Contactor
- Relay closes when controller goes to "AT LOAD".