Section 75
00-02-0522
04-06-11 -
22 -
Digital Input 8
- User Input 6.
Digital Input 9
- Remote Call to Run. (Transfer switch input)
Digital Input 10
- Low Lubrication Oil Level.
Digital Input 11
- Low Coolant Level.
Digital Input 12
- Low Fuel Level Warning.
Digital Input 13
- Fuel Leak.
Digital Input 14
- Battery Charger AC Fail.
Digital Input 15
- Emergency Stop N/O.
Digital Input 16
- Air Damper Closed.
Digital Input 17
- Generator Config 1.
Digital Input 18
- Generator Config 2.
Digital Input 19
- Generator Config 3.
Digital Input 20
- Generator Config 4.
Digital Input 21
- Generator Config 5.
Digital Input 22
- Generator Config 6.
Digital Input 23
- Fuel Filter Restriction.
Digital Input 24
- Air Filter Restriction.
Menu Selections for Digital Inputs
1. Disabled
- Not used
2. Remote Call to Run
- In automatic mode, when this input is grounded, the system will
initiate an automatic start sequence.
3. Remote Alarm Acknowledge
- When grounded will acknowledge (silence) remote audible
alarms.
4. Engine Overspeed
- When grounded, initiates an immediate shutdown and lockout and
displays "Engine overspeed" as cause of shutdown.
5. Crank Termination
- When active will cause immediate cessation of cranking, and no
cranking can occur while this input is active.
Phase-out
/ Discontinued
Product
Check
Availability